Installing the Fireplace

Step 1.   Locating the Fireplace

The diagram below shows space and clearance require-
ments for locating a fireplace within a room. 

THE FIRE-

PLACE MUST BE LOCATED FLUSH WITH THE OUTSIDE
OF AN EXTERIOR WALL!

Indoor Minimum Clearances

 from the Fireplace to Combustible Materials

Inches

mm

Glass ............................... 36 .................... 914
Floor ................................. 0 ....................... 0
Metal Sides ...................... 1/2 .................... 13
Top ................................ 4 1/2 .................. 114
Ceiling* ............................ 31 .................... 787

   Figure 2.    Fireplace Dimensions and Locations

Clearance Requirements

The top and sides of the fireplace are defined by stand-offs.
The minimum clearance for the indoor side to a perpendicular
wall extending past the face of the fireplace is one inch (25
mm).  The metal ends of the fireplace may 

NOT

 be recessed

into combustible construction.

WARNING: TO PREVENT CONTACT WITH
SAGGING OR LOOSE INSULATION, THE

FIREPLACE MUST NOT BE INSTALLED AGAINST
VAPOR BARRIERS OR EXPOSED INSULATION. LO-
CALIZED OVERHEATING COULD OCCUR AND A
FIRE COULD RESULT.

Step 2.  Framing the Fireplace

Fireplace framing can be built before or after the fireplace is
set in place. Framing should be positioned to accommo-
date wall coverings and fireplace facing material. The dia-
gram below shows framing reference dimensions.

CAUTION: MEASURE FIREPLACE DIMENSIONS AND
VERIFY FRAMING METHODS AND WALL COVERING
DETAILS BEFORE FRAMING.

* The clearance to the ceiling is measured from the top

of the unit, excluding the standoffs (see Figure  9).

The distance from the unit to combustible construction is to
be measured from the unit outer wrap surface to the com-
bustible construction, 

NOT

 from the screw heads that se-

cure the unit together.

!

WARNING: FRAMING DIMENSIONS ASSUME
USE OF 1/2 INCH THICK WALL COVERING

MATERIALS ON EXTERIOR OF FRAMING ONLY AND
NO SHEETROCK ON INTERIOR OF FRAMING.

!

36”

1”

GLASS

FLUSH TO OUTSIDE

GLASS

Framing should be
constructed of 2 X 4
lumber or heavier.

Figure 3.
Framing Dimensions

44

[1117.6]

41 1/4

[1047.8]

22 7/8

[581]

Outdoor Minimum Clearances

 from the Fireplace to Combustible Materials

Inches

mm

Glass ............................... 36 .................... 914
Floor ................................. 0 ...................... 0
Sides* .............................. 12 .................... 305
Top* ................................. 12 .................... 305
Overhang (non-vinyl) .......... 31 .................... 787
Overhang (vinyl) ................ 60 ................... 1524

*NOTE: 

Clearance to sides and top are 36” when vinyl siding is used.

In cold northern climates pay attention to exposures and
prevailing wind conditions when locating the fireplace, the same
as you would for locating exterior windows and doors.

The Twilight has the thermal characteristics of a high quality
window system. Temperatures near the fireplace will be
cooler than what is realized with a fully insulated wall.

Summary of Contents for TWILIGHT

Page 1: ...ppliance may be installed in an af termarket permanently located manufac tured mobile home where not prohibited by local codes 2 This appliance is only for use with the type of gas indicated on the rating plate This appliance is not convertible for use with other gases unless a certified kit is used Please contact your Heat N Glo Lifestyle Products dealer with any questions or concerns For the num...

Page 2: ...OLLOW these installation instructions may result in a possible fire hazard and will void the warranty Prior to the first firing of the fireplace READ the Using Your Fireplace section of the Owners Guide DO NOT USE this appliance if any part has been under water Immediately CALL a qualified service technician to inspect the unit and to replace any part of the control system and any gas control whic...

Page 3: ...ing the Fireplace 10 Step 3 Positioning Leveling and Securing the Fireplace 12 Step 4 The Gas Control System 13 Step 5 The Gas Supply Line 13 Step 6 Gas Pressure Requirements 13 Step 7 Wiring the Fireplace 14 Step 8 Finishing 15 Step 9 Installing Trim Logs and Ember Material 15 Installing the Trim 15 Positioning the Logs 15 Shutter Settings 15 Glass Specifications 16 Placing the Ember Material 16 ...

Page 4: ...es numéros de pièce se trouve à la page suivante NG LP Exploded Parts Diagram GN PL Vue éclatée des pièces Service Parts Twilight Beginning Manufacturing Date 8 01 Ending Manufacturing Date ______ 4 8 5 12 13 11 9 Log Set Assembly 2 1 7 6 3 3 14 10 ...

Page 5: ...oor Glass Assembly Assemblée de verre d intérieur GLA INDOOR 7 Indoor Door Assembly Assemblée de Porte D intérieur DF 36H 8 Hood Hotte SRV674 174 9 Log Set Assembly Sold as a Set Only Jeu de Bûches PRE 002253964 POST 002253964 LOGS MS LOGS TWILIGHT 10 Glass Clip Indoor Agrafe de Verre D intérieur 674 138 11 Glass Clip Outdoor Agrafe de Verre Extérieure 674 137 12 Insulation Board Conseil d Isolati...

Page 6: ...4 Wire Assembly Module de fil 593 590A 5 Pilot Assembly NG Module de veilleuse GN 385 510A 5 Pilot Assembly LP Module de veilleuse PL 385 511A 6 Pilot Bracket Parenthèse Pilote 674 164 7 Burner Orifice NG 31C Orifice de brûleur GN 31C 582 831 7 Burner Orifice LP 1 8mm Orifice de brûleur PL 1 8mm 582 818 8 Valve Bracket Parenthèse de Valve 674 167 9 Flex Ball Valve Assembly Fléchir l Assemblée de S...

Page 7: ...da These models may be installed in a bedroom or bed sitting room in the U S A and Canada High Altitude Installations U L Listed gas appliances are tested and approved with out requiring changes for elevations from 0 to 2 000 feet in the U S A and in Canada When installing this appliance at an elevation above 2 000 feet it may be necessary to decrease the input rating by changing the existing burn...

Page 8: ...oid the owner s warranty and may present a fire hazard The Heat N Glo Lifestyle Products Warranty will be voided by and Heat N Glo Lifestyle Products disclaims any responsibility for the following actions Installation of any damaged fireplace Modification of the fireplace vent system Installation other than as instructed by Heat N Glo Lifestyle Products Improper positioning of the gas logs or the ...

Page 9: ...S TOP GRILLE GLASS DOOR BOTTOM GRILLE GAS CONTROLS AND LABELS ELECTRICAL ACCESS GAS LINE ACCESS INDOOR OUTDOOR 8 1 2 13 2 43 1093 3 77 3 77 42 1068 4 40 3 4 1034 42 1 2 1080 17 7 8 453 24 1 8 611 23 3 8 595 8 204 36 1 8 917 7 8 204 40 1 2 1030 36 3 8 924 ELECTRICAL ACCESS GAS LINE ACCESS ...

Page 10: ... shows framing reference dimensions CAUTION MEASURE FIREPLACE DIMENSIONS AND VERIFY FRAMING METHODS AND WALL COVERING DETAILS BEFORE FRAMING The clearance to the ceiling is measured from the top of the unit excluding the standoffs see Figure 9 The distance from the unit to combustible construction is to be measured from the unit outer wrap surface to the com bustible construction NOT from the scre...

Page 11: ...R POSSIBLE TO USE THE VINYL PROTECTOR KIT O N P R Q FP See Note 1 See Note 1 See Note 2 QMIN RMAX Twilight 10 feet 2 x Q ACTUAL 1 additional termination cap Q 3 feet 1 x Q ACTUAL 2 additional termination caps Q 6 feet 2 3 x Q ACTUAL 3 additional termination caps Q 9 feet 1 2 x Q ACTUAL RMAX 2 caps plus fireplace x QACTUAL D E L FP A H M X J or K I A G F FP FP FP FP FP B B B 60 minimum for vinyl cl...

Page 12: ...from side to side and front to back Shim the fireplace with non combustible material such as sheet metal as necessary Secure the fireplace to the framing byusing nails or screws through the nailing tabs See Figure 7 for placement of combustible housewrap or building paper and non combustible sheathing for the outside wall Combustible housewrap or building paper may be brought over the fireplace fl...

Page 13: ... are connected to the 1 2 inch 13mm inlet of the control valve NOTE If substi tuting for these components please consult local codes for compliance Locate the gas line access hole in the outer casing of the fireplace The gas line may be run from either side of the fireplace provided the hole in the outer wrap does not exceed 2 in diameter and it does not penetrate the actual firebox Open the firep...

Page 14: ... switch in the desired position on a wall Run a maximum of 25 feet 7 8 m or less length of 18 A W G minimum wire and connect it to the fireplace ON OFF switch pigtails CAUTION LABEL ALL WIRES PRIOR TO DISCONNEC TION WHEN SERVICING CONTROLS WIRING ERRORS CAN CAUSE IMPROPER AND DANGEROUS OPERATION VERIFY PROPER OPERATION AFTER SERVICING WALL SWITCH RED BLK IGNITION MODULE 3 VAC TRANSFORMER 3 VAC BRN...

Page 15: ...ugh space so that the bottom grille can be lowered and the trim door removed FOR OUTSIDE Marble brick tile stone or other non combustible materials can be used to cover up the gap between the facing material and the fireplace DO NOT obstruct or modify the air intake or exhaust Positioning the Logs If the gas logs have been factory installed they should not need to be positioned If the logs have be...

Page 16: ... of the fireplace will not require this purging of air from the gas supply lines unless the gas valve has been turned to the OFF position in which case the air would have to be purged NOTE The fireplace should be run 3 to 4 hours on the initial start up Turn it off and let it cool completely Remove and clean the glass Replace the glass and run the fireplace for an additional 8 hours This will help...

Page 17: ...replace s flame patterns Make sure the flames are steady not lifting or floating See Figure 15 The thermopile thermocouple tips should be covered with flame Checking Vent System Frequency Before initial use and at least annually thereafter more frequently if possible By Qualified service technician Home owner Task Inspect the external vent on a regular basis to ensure that no debris is interfering...

Reviews: