23
Heat & Glo • SOHO-B-CEB, SOHO-N-CEB, SOHO-P-CEB • 2111-980 Rev. i • 3/13
O
N
P
R
Q
V
= VENT TERMINAL
X
= AIR SUPPLY INLET
= AREA WHERE TERMINAL IS NOT PERMITTED
Figure 6.3 Minimum Clearances for Termination
A = 31 cm ......................clearances above grade, veranda,
porch, deck or balcony
B = 31 cm ......................clearances to window or door
that may be opened, or to perma-
nently closed window. (Glass)
C = 46 cm ......................vertical clearance to unventilated
soffit or to ventilated soffit located
above the terminal
76 cm .......................for vinyl clad soffits and below
electrical service
D = 23 cm .....................clearance to outside corner
E = 15 cm ......................clearance to inside corner
F
= 91 cm ......................not to be installed above a gas
meter/regulator assembly within 3
feet (90 cm) horizontally from the
center-line of the regulator
G = 1,8 m .......................clearance to gas service regulator
flue outlet
H = 31 cm ......................clearance to non-mechanical
air supply inlet to building or the
combustion air inlet to any other
appliance
i
= 1,8 m ......................clearance to a mechanical (pow-
ered) air supply inlet
** a vent shall not terminate directly above a sidewalk or paved driveway
which is located between two single family dwellings and serves both
dwellings.
*** only permitted if veranda, porch, deck or balcony is fully open on a
minimum of 2 sides beneath the floor, or meets Note 2.
Note 1
: On private property where termination is less than 2.1 m above a
sidewalk, driveway, deck, porch, veranda or balcony, use of a listed cap
shield is suggested. (See vents components page)
Note 2
: Termination in a covered alcove space (spaces open only on one
side and with an overhang) are permitted with the dimensions specified
for vinyl or non-vinyl siding and soffits.
1
. There must be .91 m minimum
between termination caps.
2.
All mechanical air intakes within 3 m of a
termination cap must be a minimum of .91 m below the termination cap.
3.
All gravity air intakes within .91 m of a termination cap must be a minimum
of .30 m below the termination cap.
(See Note 1)
(See Note 2)
Note 3
: Local codes or regulations may require different clearances.
Note 4:
Termination caps may be hot. Consider their proximity to
doors or other traffic areas.
Note 5:
Location of the vent termination must not interfere with
access to the electrical service.
Vent system termination is
NOT
permitted in screened porches.
Vent system termination is permitted in porch areas with two or more
sides open. You must follow all side walls, overhang and ground
clearances as stated in the instructions.
Heat & Glo assumes no responsibility for the improper performance
of the appliance when the venting system does not meet these
requirements.
C
J
B
D
i
B
F
G
B
A
A
E
X
V
V
V
V
V
V
V
M
H OR i
Electrical
Service
V
K
V
K
V
L
C
V
M*** = 46 cm ...................clearance under veranda, porch,
deck, balcony or overhang
107 cm ............ vinyl
N = 15 cm .............. non-vinyl sidewalls
31 cm .............. vinyl sidewalls
O = 46 cm .............. non-vinyl soffit and overhang
107 cm ............ vinyl soffit and overhang
P = 2.4 m
Q
MIN
R
MAX
1 cap
91 cm
2 x Q
ACTUAL
2 caps
1,8 m
1 x Q
ACTUAL
3 caps
2,7 m
2/3 x Q
ACTUAL
4 caps
3,7 m
1/2 x Q
ACTUAL
Q
MIN
= # termination caps x 3 R
MAX
= (2 / # termination caps) x Q
ACTUAL
Covered Alcove Applications
(See Note 1)
(See Note 5)
(See Note 5)
J** = 2,13 m. ................... clearance above paved
sidewalk or a paved driveway
located on
public
property
K = 15 cm .................... clearance from sides of electri-
cal service
L
= 31 cm ..................... clearance above electrical
service
Measure horizontal clearances from this surface.
Measure vertical clearances from this surface.
(See Note 2)
(See Note 2)