Heat & Glo • SL-36-Ultimate • 2141-900 Rev. i • 5/11
14
H
1
V
1
Figure 5.3
Figure 5.4
D. Vent Diagrams
1. Top Vent - Horizontal Termination
One Elbow
Two Elbows
Note:
Must have a 18 inches minimum
vertical vent before attaching a 90° elbow
to the unit.
* If the horizontal component is less than
5 feet then the total vent run can be
extended to 40 feet.
INSTALLED
HORIZONTALLY
H
1
H
2
V
1
V
1
Minimum
H
1
Maximum
1-1/2 ft.
457 mm
3 ft
924 mm
2-1/2 ft.
762 mm
6 ft
1.8 m
3-1/2 ft.
1.7 m
9 ft
2.7 m
4 ft.
1.2 m
10 ft
3.1 m
4-1/2 ft.
1.4 m
12 ft
3.7 m
5-1/2 ft.
1.7 m
15 ft
4.6 m
6-1/2 ft.
2 m
18 ft
5.5 m
7-1/2 ft.
2.3 m
21 ft
6.4 m
H
1
= 21 ft. (6.4 m) Maximum
V
1
= 40 ft. (12.2 m) Maximum
V
1
+ H
1
= 30 ft. (9.1 m) Maximum*
Fire Risk. Explosion Risk.
Do NOT pack insulation or other combustibles between ceiling fi restops.
• ALWAYS maintain specifi ed clearances around venting and fi restop systems.
• Install wall shield and ceiling fi restops as specifi ed.
Failure to keep insulation or other material away from vent pipe may cause fi re.
WARNING
V
1
Minimum
H
1
+ H
2
Maximum
1-1/2 ft.
457 mm
3 ft
924 mm
2-1/2 ft.
762 mm
6 ft
1.8 m
3-1/2 ft.
1.7 m
9 ft
2.7 m
4 ft.
1.2 m
10 ft
3.1 m
4-1/2 ft.
1.4 m
12 ft
3.7 m
5-1/2 ft.
1.7 m
15 ft
4.6 m
6-1/2 ft.
2 m
18 ft
5.5 m
7-1/2 ft.
2.3 m
21 ft
6.4 m
V
1
= 40 ft. (12.2 m) Maximum
H
1
+ H
2
= 21 ft. (6.4 m) Maximum
V
1
+ H
1
+ H
2
= 30 ft. (9.1 m) Maximum*
* If the horizontal component is less than
5 feet then the total vent run can be
extended to 40 feet.
Note:
Must have a 18 inches minimum
vertical vent before attaching a 90° elbow
to the unit.