Heat & Glo  •  Passage  •  700-900  Rev. M  •  12/07

8

For all side wall horizontally vented gas fueled equipment

installed in every dwelling, building or structure used in

whole or in part for residential purposes, including those

owned or operated by the Commonwealth and where the

side wall exhaust vent termination is less than seven (7)

feet above finished grade in the area of the venting, includ-

ing but not limited to decks and porches, the following re-

quirements shall be satisfied:

Installation of Carbon Monoxide Detectors

At the time of installation of the side wall horizontal vented

gas fueled equipment, the installing plumber or gasfitter

shall observe that a hard wired carbon monoxide detector

with an alarm and battery back-up is installed on the floor

level where the gas equipment is to be installed. In addi-

tion, the installing plumber or gasfitter shall observe that a

battery operated or hard wired carbon monoxide detector

with an alarm is installed on each additional level of the

dwelling, building or structure served by the side wall hori-

zontal vented gas fueled equipment. It shall be the respon-

sibility of the property owner to secure the services of qual-

ified licensed professionals for the installation of hard wired

carbon monoxide detectors.

In the event that the side wall horizontally vented gas fu-

eled equipment is installed in a crawl space or an attic, the

hard wired carbon monoxide detector with alarm and bat-

tery back-up may be installed on the next adjacent floor

level.

In the event that the requirements of this subdivision can

not be met at the time of completion of installation, the

owner shall have a period of thirty (30) days to comply with

the above requirements; provided, however, that during said

thirty (30) day period, a battery operated carbon monoxide

detector with an alarm shall be installed.

Approved Carbon Monoxide Detectors

Each carbon monoxide detector as required in accordance

with the above provisions shall comply with NFPA 720 and

be ANSI/UL 2034 listed and IAS certified.

Signage

A metal or plastic identification plate shall be permanently

mounted to the exterior of the building at a minimum height

of eight (8) feet above grade directly in line with the ex-

haust vent terminal for the horizontally vented gas fueled

heating appliance or equipment. The sign shall read, in

print size no less than one-half (1/2) inch in size, 

“GAS

VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OB-

STRUCTIONS”.

Inspection

The state or local gas inspector of the side wall horizontally

vented gas fueled equipment shall not approve the installa-

tion unless, upon inspection, the inspector observes carbon

monoxide detectors and signage installed in accordance with

the provisions of 248 CMR 5.08(2)(a)1 through 4.

Exemptions

The following equipment is exempt from 248 CMR 5.08(2)(a)1

through 4:
• The equipment listed in Chapter 10 entitled “Equipment

Not Required To Be Vented” in the most current edition

of NFPA 54 as adopted by the Board; and

• Product Approved side wall horizontally vented gas fu-

eled equipment installed in a room or structure sepa-

rate from the dwelling, building or structure used in whole

or in part for residential purposes.

MANUFACTURER REQUIREMENTS
Gas Equipment Venting System Provided

When the manufacturer of Product Approved side wall hor-

izontally vented gas equipment provides a venting system

design or venting system components with the equipment,

the instructions provided by the manufacturer for installa-

tion of the equipment and the venting system shall include:
• Detailed instructions for the installation of the venting

system design or the venting system components; and

• A complete parts list for the venting system design or

venting system.

Gas Equipment Venting System NOT Provided

When the manufacturer of a Product Approved side wall

horizontally vented gas fueled equipment does not provide

the parts for venting the flue gases, but identifies “special

venting systems”, the following requirements shall be sat-

isfied by the manufacturer:
• The referenced “special venting system” instructions shall

be included with the appliance or equipment installation

instructions; and

• The “special venting systems” shall be Product Approved

by the Board, and the instructions for that system shall

include a parts list and detailed installation instructions.

A copy of all installation instructions for all Product Ap-

proved side wall horizontally vented gas fueled equipment,

all venting instructions, all parts lists for venting instruc-

tions, and/or all venting design instructions shall remain

with the appliance or equipment at the completion of the

installation.

See Gas Connection section for additional Common-

wealth of Massachusetts requirements.

NOTE:

The following requirements reference various

Massachusetts and national codes not contained in

this document.

Requirements for the Commonwealth of

Massachusetts

Summary of Contents for Passage

Page 1: ...T DISCARD THIS MANUAL CAUTION Important operating and maintenance instructions included This appliance may be installed as an OEM installation in manufactured home USA only or mobile home and must be installed in accordance with the manufacturer s instruc tions and the manufactured home construction and safety standard Title 24 CFR Part 3280 or Standard for Installa tion in Mobile Homes CAN CSA Z2...

Page 2: ...cts within 36 inches of the appliance front READ and UNDERSTAND all instructions carefully before starting the installation FAILURE TO FOLLOW these installation instructions may result in a possible fire hazard and will void the warranty Prior to the first firing of the appliance READ the Using Your Fireplace section of the Owners Guide DO NOT USE this appliance if any part has been under water Im...

Page 3: ...ystem 13 A Vent System Approvals 13 B Installing Vent Components 18 C Vent Termination 20 Step 4 Positioning Leveling and Securing the Appliance 23 Step 5 The Gas Control Systems 23 Step 6 The Gas Supply Line 24 Step 7 Gas Pressure Requirements 24 Step 8 Wiring the Appliance 25 Step 9 Finishing 26 Step 10 Finishing Strip instructions 26 Step 11 Installing Trim and Logs 28 Installing the Trim 28 Ad...

Page 4: ... or in the absence of local codes with the National Electric Code ANSI NFPA No 70 in the United States or to the CSAC22 1 Canadian Electric Code in Canada These models may be installed in a bedroom or bed sitting room in the U S A and Canada 1Approvals and Codes High Altitude Installations U L Listed gas appliances are tested and approved with out requiring changes for elevations from 0 to 2 000 f...

Page 5: ... print size no less than one half 1 2 inch in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF ALL OB STRUCTIONS Inspection The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installa tion unless upon inspection the inspector observes carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR 5 08 2 a 1 throu...

Page 6: ...nsure maximum safety and benefit Failure to follow these instructions will void the owner s warranty and may present a fire hazard When planning a appliance installation it s necessary to determine Where the unit is to be installed The vent system configuration to be used Gas supply piping Electrical wiring Framing and finishing details Where to install wall switch Whether an optional remote contr...

Page 7: ... MATERIAL NON COMBUSTIBLE MATERIAL ELECTRICAL ACCESS 3 1 4 82 6mm 31 5 8 804mm 6 1 2 164mm 5 127mm 4 1 4 108mm GAS INLET 21 3 8 543mm 6 3 16 157mm NON COMBUSTIBLE MATERIAL BOTH SIDES OF UNIT 34 3 8 873mm FINISHING 39 1 16 992mm 34 864mm R17 3 8 441mm FINISHING TOP STANDOFFS TOP VENT COLLARS ELECTRICAL ACCESS GAS LINE ACCESS RATING PLATES AND LABELS GAS CONTROLS ...

Page 8: ...ertical vents that run on the outside of a building may be but are not required to be installed inside a chase CAUTION TREATMENT OF FIRESTOP SPACERS AND CONSTRUCTION OF THE CHASE MAY VARY WITH THE TYPE OF BUILDING THESE INSTRUCTIONS ARE NOT SUBSTITUTES FOR THE REQUIREMENTS OF LOCAL BUILDING CODES THEREFORE YOUR LOCAL BUILD ING CODES MUST BE CHECKED TO DETERMINE THE REQUIREMENTS FOR THESE STEPS Fac...

Page 9: ... vertical and 900 elbow Step 2 Framing the Appliance Appliance framing can be built before or after the appliance is set in place Framing should be positioned to accommo date wall coverings and appliance facing material The dia gram below shows framing reference dimensions CAUTION MEASURE APPLIANCE DIMENSIONS AND VERIFY FRAMING METHODS AND WALL COVERING DETAILS BEFORE FRAMING A B C D NOTE HORIZONT...

Page 10: ... Installers Guide The flame and ember appearance may vary based on the type of fuel burned and the venting configuration used Identifying Vent Components The vent systems installed on this gas appliance may in clude one two or three 90 elbow assemblies The rela tionships of vertical rise to horizontal run in vent configura tions using 90 elbows MUST BE strictly adhered to The rise to run relations...

Page 11: ...ES AT EACH JOINT Figure 6 DVP Series Direct Vent Component Specifications 5 inch inner pipe 8 inch outer pipe DVP90ST 12 9 16 11 1 4 7 1 4 1 1 4 TYP 1 2 TYP 8 9 16 DVP36 DVP48 48 24 36 4 6 DVP4 DVP6 12 DVP12 2 MIN DVP12A 12 3 16 MAX DVP24 9 7 8 45 0O 10 1 4 DVP45 14 1 4 ...

Page 12: ...rectly to starting collars on unit VENTING WITH ONE 1 90 ELBOW V H 3 5 MIN 1 1m 12 MAX 3 66m 4 MIN 1 22m 16 MAX 4 88m 5 MIN 1 52m 20 MAX 6 1m V H 40 MAX 12 2MM H 20 MAX 6 1m H V STRAIGHT UP VERTICAL VENTING V FT 46 MAX 14M LP ONLY V MIN 8 MIN 203MM Figure 6 Straight Up Vertical Venting CAP NOTE Horizontal termination is not permitted on units converted to use LP gas LP ...

Page 13: ...0 MAX 12 2m H H1 20 MAX 6 1m V V1 H 40 MAX 12 2m Figure 8 Venting with Two 90 Elbows VENTING WITH TWO 2 90 ELBOWS NOTE When venting with 2 elbows a straight section of venting 3 feet minimum MUST be attached directly to starting collars on unit H1 H V V V1 H NOTE Horizontal termination is not permitted on units converted to use LP gas LP INSTALLED HORIZONTALLY ...

Page 14: ...IN 1 22m 16 MAX 4 66m 5 MIN 1 52m 20 MAX 6 1m NOTE H H1 20 MAX 6 2m V V1 H H1 40 MAX 12 4m NOTE When venting with 3 elbows a straight section of venting 3 feet minimum MUST be attached directly to starting collars on unit V H H1 V1 V H H1 V1 NOTE Three elbows are not approved for units converted to use LP gas see Figure 8 LP INSTALLED HORIZONTALLY ...

Page 15: ...ut elbows a differ ent baffle 700 181 is to be used This is a service part and is to be purchased separately Part number 700 181 includes two notches in the outer circle to separate it from the 700 180 2 Continue Adding Vent Components WARNING INSTALLATION OF THIS APPLI ANCE REQUIRES THE USE OF TWO HEAT SHIELDS 385 290 ABOVE THE FIRST 900 ELBOW IN THE VENTING SYSTEM Figure 10 To Install the Heat S...

Page 16: ...ent Pipe Figure 14 Heat Shield Interior Exterior Firestops TRIM HEAT SHIELD IF TOO LONG ADD TO SHIELD IF TOO SHORT EXTERIOR FIRESTOP INTERIOR FIRESTOP HEAT SHIELD 3 Install Support Brackets The vent system must be supported every five 5 feet of horizontal run by a horizontal pipe support Refer to Cinch Pipe and Termination Cap installation in structions 4 Install Firestops For Horizontal Runs Fire...

Page 17: ...ILING CEILING FIRESTOP RAFTER NAILS 4 REQUIRED CEILING NEW FRAMING MEMBERS EXISTING CEILING JOISTS CHIMNEY HOLE 10 254mm 10 254mm C Vent Termination For Horizontal Terminations To attach and secure the termination to the last section of horizontal vent Rotate and interlock the ends as described at the begin ning of the Installing Vent Components section The termination kit should pass through the ...

Page 18: ...e side and with an overhang are permitted with the dimensions specified for vinyl or non vinyl siding and soffits 1 There must be 3 feet minimum between termination caps 2 All mechanical air intakes within 10 feet of a termination cap must be a minimum of 3 feet below the termination cap 3 All gravity air intakes within 3 feet of a termination cap must be a minimum of 1 foot below the termination ...

Page 19: ...ER EST OF SAFETY SEE THE FOLLOWING DIAGRAM FOR MINIMUM HEIGHTS PROVIDED THE TERMI NATION CAPISAT LEAST 20 INCHES FROMAVER TICAL WALLAND 2 FEET BELOWAHORIZONTAL OVERHANG NOTE This also pertains to vertical vent systems in stalled on the outside of the building Roof Pitch H min ft flat to 6 12 1 0 6 12 to 7 12 1 25 over 7 12 to 8 12 1 5 over 8 12 to 9 12 2 0 over 9 12 to 10 12 2 5 over 10 12 to 11 1...

Page 20: ... model is Intermittent Pilot Ignition IPI This system includes a 3V control valve electronic module and intermittent pilot WARNING CONTINUOUS 110 120 VAC SER VICE MUST BE WIRED TO THE APPLIANCE JUNCTION BOX 1 Place the appliance into position 2 Level the appliance from side to side and from front to back 3 Shim the appliance with non combustible material such as sheet metal as necessary 4 Secure t...

Page 21: ...th non combustible insulation to pre vent cold air infiltration Remove the appliance front insert the gas supply line through the gas line hole and connect it to the shut off valve When attaching the pipe support the control so that the lines are not bent or torn After the gas line installation is complete all connec tions must be tightened and checked for leaks with a commercially available non c...

Page 22: ...10 VAC is restored turn the battery backup switch to OFF to extend battery life Step 8 Wiring the Appliance NOTE Electrical wiring must be installed by a licensed electrician CAUTION DISCONNECT REMOTE CONTROLS IF YOU ARE ABSENT FOR EXTENDED TIME PERIODS THIS WILLPREVENTACCIDENTALAPPLIANCE OPERATION Intermittent Pilot Ignition IPI Wiring Appliance Requirements This appliance requires that 110 120 V...

Page 23: ...unit below the glass front opening 36 1 6 12 1 6 CEILING IMPORTANT Before starting wall construction complete the installation from the section titled Positioning Leveling and Securing theAppliance located in this Installer s Guide Facing Requirements Facingthicknessfrom1 2 to1 1 4inch outsidemounteddoor The doors for the Passage are designed to sit on top of the finishing material covering the in...

Page 24: ... 2 7 32 11 9 32 29 1 4 R 17 980 27 1 32 19 5 32 3 2 7 32 35 31 32 R 16 250 Figure 29 FACING TEMPLATE PASSAGE TEMPLATE NON COMBUSTIBLE BOARD Finishing instructions for the base IMPORTANT Before starting wall construction complete the installation from the section titled Positioning Leveling and Securing theAppliance located in this Installer s Guide NOTE Follow the instructions on the previous page...

Page 25: ... and front grilles for obstructions Before lighting the appliance double check the unit for possible obstructions that could be blocking the vent ter minations or the front grilles Double check for faulty components Any component that is found to be faulty MUST BE re placed with an approved component Tampering with the appliance components is DANGEROUS and voids all war ranties A small amount of a...

Page 26: ...ebris is interfering with the flow of air Inspect entire vent system for proper function Cleaning Glass Door Frequency After the first 3 to 4 hours of use As neces sary after initial cleaning By Home owner Task Remove and clean glass after the first 3 to 4 hours of use After the initial cleaning clean as necessary Film deposits on the inside of the glass door should be cleaned off using a househol...

Page 27: ...____________________________________________ _______________________________________________________________________________ DO NOT DISCARD THIS MANUAL CAUTION Important operating and maintenance instruc tions included Read understand and follow these instructions for safe installation and operation Leave this manual with party responsible for use and operation This product may be covered by one o...

Reviews: