Heat & Glo Heat & Glo 6000TRXI-IPI Owner'S Manual Download Page 7

10

Heat & Glo  •  6000TRXI-IPI  •  386-901  Rev. I  •  1/06

3

Installing the Fireplace

Step 1.       Locating the Fireplace

The following diagram shows space and clearance require-

ments for locating a fireplace within a room.

Minimum Clearances

 from the Fireplace to Combustible Materials

Inches

mm

Glass Front ........................ 36 .................... 914

Floor ................................... 0 ....................... 0

Rear ...................................1/2 ..................... 13

Sides .................................1/2 ..................... 13

Surround Sides* .................. 0 ....................... 0

Top ................................... 3 1/2 ................... 89

Ceiling** ............................. 31 .................... 787

   Figure 2.    Fireplace Dimensions, Locations,

                     and Space Requirements

Minimum Clearances

 from the Vent Pipe to Combustible Materials

Inches

mm

Vertical Sections

. ............. 1 ................ 25

Horizontal Sections

Top ..................................... 3 ................ 75

Bottom ............................... 1 ................ 25

Sides ................................. 1 ................ 25

At Wall Firestops

Top ..................................... 3 ................ 75

Bottom ............................... 1 ................ 25

Sides ................................. 1 ................ 25

*  See Figure 3.

** The clearance to the ceiling is measured from the top

of the unit, excluding the standoffs (see Figure 38).

The distance from the unit to combustible construction

is to be measured from the unit outer wrap surface to

the combustible construction, 

NOT

 from the screw heads

that secure the unit together.

For minimum clearances, see the direct vent termination

clearance diagrams on pages 23 and 24 in this manual.

1/2” MIN. (13mm)

D

C

E

B

1” MIN. (25mm)

A

Clearance Requirements

The top, back, and sides of the fireplace are defined by

stand-offs. The minimum clearance to a perpendicular wall

extending past the face of the fireplace is one inch (25 mm).

The back of the fireplace may be recessed 21 1/2 inches

(546 mm) into combustible construction.

Constructing the Fireplace Chase

A chase is a vertical box-like structure built to enclose the

gas fireplace and/or its vent system. Vertical vents that run

on the outside of a building may be, but are not required to

be, installed inside a chase.

CAUTION:

 TREATMENT OF FIRESTOP SPACERS AND

CONSTRUCTION OF THE CHASE MAY VARY WITH THE

TYPE OF BUILDING. THESE INSTRUCTIONS ARE NOT

SUBSTITUTES FOR THE REQUIREMENTS OF LOCAL

BUILDING CODES. THEREFORE, YOUR LOCAL BUILD-

ING CODES 

MUST

 BE CHECKED TO DETERMINE THE

REQUIREMENTS FOR THESE STEPS.

Factory-built fireplace chases should be constructed  in the

manner of all outside walls of the home to prevent cold air

drafting problems. The chase should not break the outside

building envelope in any manner.

This means that the walls, ceiling, base plate and cantile-

ver floor of the chase should be insulated. Vapor and air

infiltration barriers should be installed in the chase as per

regional codes for the rest of the home. Additionally, in re-

gions where cold air infiltration may be an issue, the inside

surfaces may be sheetrocked and taped for maximum air

tightness.

To further prevent drafts, the wall shield and ceiling firestops

should be caulked with high temperature caulk to seal gaps.

Gas line holes and other openings should be caulked with

high temp caulk or stuffed with unfaced insulation. If the

appliance is being installed on a cement slab, a layer of

plywood may be placed underneath to prevent conducting

cold up into the room.

THE CHASE SHOULD BE CONSTRUCTED SO THAT ALL

CLEARANCES TO THE FIREPLACE ARE MAINTAINED

AS SPECIFIED WITHIN THIS INSTALLERS GUIDE.

A

B

C

D

E

42”

22”

36”

51”

72”

Note*

42”

22”

40”

57”

80”

*

If venting with (2) 90

0

 elbows off rear of unit

 the dimensions C, D, and E, will change.

Summary of Contents for Heat & Glo 6000TRXI-IPI

Page 1: ...located manufac tured mobile home wherenotprohibited by local codes 2 This appliance is only for use with the type of gas indicated on the rating plate This appliance is not convertible for use with o...

Page 2: ...ce front READ and UNDERSTAND all instructions carefully before starting the installation FAILURE TO FOLLOW these installation instructions may result in a possible fire hazard and will void the warran...

Page 3: ...tem Approvals 13 B Installing Vent Components 20 C Vent Termination 23 Step 4 Positioning Leveling and Securing the Fireplace 25 Step 5 Install the Optional Heat Zone Gas Kit 26 Step 6 The Gas Control...

Page 4: ...local codes or in the absence of local codes with the National Electric Code ANSI NFPA No 70 in the United States or to the CSAC22 1 Canadian Electric Code in Canada These models may be installed in...

Page 5: ...re maximum safety and benefit Failure to follow these instructions will void the owner s warranty and may present a fire hazard The Heat Glo Warranty will be voided by and Heat Glo disclaims any respo...

Page 6: ...LECTRICAL ACCESS GAS CONTROLS RATING PLATE AND LABELS TRIM DOOR HOOD TOP STANDOFFS 41 1 8 1044mm 38 965mm 36 1 8 916mm 25 1 4 642mm 34 5 8 879mm VENT COLLARS ELECTRICAL ACCESS 26 7 8 682mm 12 3 4 323m...

Page 7: ...ilt to enclose the gas fireplace and or its vent system Vertical vents that run on the outside of a building may be but are not required to be installed inside a chase CAUTION TREATMENT OF FIRESTOP SP...

Page 8: ...ference dimensions CAUTION MEASURE FIREPLACE DIMENSIONS AND VERIFY FRAMING METHODS AND WALL COVERING DETAILS BEFORE FRAMING Shows center of 10 x 12 vent framing holes for top and rear venting The cent...

Page 9: ...Vent Component Specifications 5 inch inner pipe 8 inch outer pipe NOTE PIPES OVERLAP 1 1 4 INCHESAT EACH JOINT DVP90ST 12 9 16 11 1 4 7 1 4 1 1 4 TYP 1 2 TYP 8 9 16 DVP36 DVP48 48 24 36 4 6 DVP4 DVP6...

Page 10: ...g configuration used Termination Kits Identifying Vent Components The vent systems installed on this gas fireplace may in clude one two or three 90 elbow assemblies The rela tionships of vertical rise...

Page 11: ...estricting chart see Figure 9 Figure 8 Figure 7 5 4 3 2 1 1 2 3 4 5 Adjustable Flue Restrictor see Figure 8 Figure 6 Straight Up Vertical Venting STRAIGHT UP VERTICAL VENTING V FT 40 MAX 12 4 M NOTE O...

Page 12: ...in corner installations Match the amount of vertical you have in the system with the chart to find the appropriate position to set the Flue Restrictor CHART Vertical Top Vent NG Top Vent LP Rear Vent...

Page 13: ...1 Venting with One 90 Elbow VENTING WITH ONE 1 90 ELBOW VENTING WITH ONE 1 90 ELBOW V FT H FT 1 MIN 305mm 5 MAX 1 52m 2 MIN 610mm 10 MAX 3 1m 3 MIN 914mm 15 MAX 4 65m 4 MIN 1 22m 20 MAX 6 2m V H 40 MA...

Page 14: ...3 1m 3 MIN 914 mm 6 MAX 1 86 m 15 MAX 4 65m 4 MIN 1 22 m 8 MAX 2 48 m 20 MAX 6 2m V H H1 40 MAX 12 4 m H 8 MAX 2 48 m H H1 20 MAX 6 2m Figure 14 Venting with Two 90 Elbows VENTING WITH TWO 2 90o ELBOW...

Page 15: ...3 1m 3 MIN 914mm 6 MAX 1 86m 15 MAX 4 65m 4 MIN 1 22m 8 MAX 2 48m 20 MAX 6 2m V H H1 H2 40 MAX 12 4 m H 8 MAX 2 48 m H H1 H2 20 MAX 6 2 m V H H H1 H2 1 MIN 305mm 2 MAX 610mm 5 MAX 1 52m 2 MIN 610mm 4...

Page 16: ...0 MAX 3 1m 3 MIN 914mm 15 MAX 4 65m 4 MIN 1 22m 20 MAX 6 2m NOTE H H1 20 MAX 6 2m V V1 H H1 40 MAX 12 4m V V1 FT H H1 FT 1 MIN 305mm 5 MAX 1 52m 2 MIN 610mm 10 MAX 3 1m 3 MIN 914mm 15 MAX 4 65m 4 MIN...

Page 17: ...SYSTEM IS AT TACHED TO THE TOP STARTING COLLARS WARNING FAILURE TO REMOVE INSULATION IN THE SET OF COLLARS YOU ARE USING COULD CAUSE A FIRE WARNING YOUMUSTLEAVETHEINSULATION IN PLACE IN THE SET OF COL...

Page 18: ...positioned so that it creates a 1 2 inch airspace between the shield and the combustible surface See Figure 20 4 Install Support Brackets Refer to Cinch Pipe and Termination Cap installation in struc...

Page 19: ...HIELD TRIM HEAT SHIELD IF TOO LONG ADD TO SHIELD IF TOO SHORT EXTERIOR FIRESTOP INTERIOR FIRESTOP HEAT SHIELD NOTE There must be NO INSULATION or other combustibles inside the framed firestop opening...

Page 20: ...ic Firestop JOIST CEILING FIRESTOP CEILING NAILS 4 REQUIRED CEILING CEILING FIRESTOP RAFTER NAILS 4 REQUIRED NOTE There must be NO INSULATION or other combustibles inside the framed firestop opening C...

Page 21: ...ly on one side and with an overhang are permitted with the dimensions specified for vinyl or non vinyl siding and soffits 1 There must be 3 feet minimum between termination caps 2 All mechanical air i...

Page 22: ...Slide the termination cap over the end of the vent pipe and snap into place Step 4 Positioning Leveling and Securing the Fireplace Place the fireplace into position Level the fireplace from side to s...

Page 23: ...WIREDDIRECTLYTOTHEFIRE PLACE JUNCTION BOX Figure 32 Gas Controls System Step 5 Installing the Optional Heat Zone Gas Kit NOTE There must be NO INSULATION or other com bustibles inside the framed fires...

Page 24: ...e can be plugged with non combustible insulation to pre vent cold air infiltration Open the fireplace lower grille insert the gas supply line throughthegaslinehole andconnectittotheshut offvalve When...

Page 25: ...with a 3 volt transformer The trans former plugs into the junction box and the two leads plug into the green control module see Figure 34 Intensifire Switch This model is equipped with an intensifire...

Page 26: ...BLE SPEED CONTROL TEMPERATURE SENSOR SWITCH WHT GRN BLK BLK 110 120 VAC BLOWER BLOWER RECEPTACLE BLK BLK BLK BLK WHT GROUND WHT BLK BLK BLK Figure 37 Cabin Kit Relay Wiring Diagram 3 16 MALE RED BLACK...

Page 27: ...EALED A 300 F MINIMUM SEALANT MATE RIAL MUST BE USED THESE JOINTS ARE NOT RE QUIRED TO BE SEALED ONLY NON COMBUSTIBLE MATERIAL USING 300 F MINIMUM ADHESIVE IF NEEDED CAN BE APPLIED AS FACING TO THE FI...

Page 28: ...ight need to be repositioned slightly to avoid excessive flame impingement Step 11 Installing Trim Logs and Ember Material Placing the Ember Material Ember material is shipped with this gas fireplace...

Page 29: ...hutter handle in you will be closing the air shutter To adjust loosen the wing nut Care should be taken when adjusting the air shutter so as not to cause the fireplace to soot If sooting occurs the ai...

Page 30: ...SE REFER TO THE USER S MANUALFORALL CAUTIONS SAFETY AND WARNING INFORMATION PERTAINING TO THE LIGHTING AND OPERATION OF THE FIREPLACE Step 14 Climate Control This model is equipped with a baffle which...

Page 31: ...cally By Qualified service technician Task Make a visual check of the straight flame sensor rod see Figure 32 Use emery cloth to carefully remove any existing film or white deposits Checking Flame Pat...

Reviews: