Heat & Glo Heat & Glo 6000TRXI-IPI Owner'S Manual Download Page 25

28

Heat & Glo  •  6000TRXI-IPI  •  386-901  Rev. I  •  1/06

Optional Accessories

Optional fan and remote control kits require that 110-120

VAC be wired to the factory installed junction box before

the fireplace is permanently installed.

Wall Switch

Position the wall switch in the desired position on a wall.

Run a maximum of 25 feet (7.8 m) or less length of 18

A.W.G. minimum wire and connect it to the fireplace ON/

OFF switch pigtails.

CAUTION: LABEL ALL WIRES PRIOR TO DISCON-

NECTION WHEN SERVICING CONTROLS. WIRING

ERRORS CAN CAUSE IMPROPER AND DANGEROUS

OPERATION. VERIFY PROPER OPERATION AFTER

SERVICING.

Figure 35. Intensifire Switch Wiring Diagram

SWITCH

BATTERY

HOLDER

9 VOLT

MANIFOLD ASSEMBLY

RED

RED

WHITE

Figure 34. Intermittent Pilot Ignition (IPI) Wiring Diagram

Appliance Requirements

This appliance requires 110-120 VAC be wired to the factory

installed junction box. Maintain correct polarity when wir-

ing the junction box.

Step 9.  Wiring the Fireplace

Intermittent Pilot Ignition (IPI) Wiring
3 Volt Transformer

This appliance comes with a 3 volt transformer. The trans-

former plugs into the junction box and the two leads plug

into the green control module (see Figure 34).

Intensifire Switch

This model is equipped with an intensifire switch. This switch

allows you to turn On/Off the rear log burners. The switch is

located on the control panel. Install the 9 volt battery into

the battery holder located in the lower compartment right

next to the control panel (see Figure 35).

IGNITION MODULE

3 VAC

TRANSFORMER

3 VAC

G

RN

O

RG

INTERMITTENT

PILOT

IGNITOR

IGNITION

MODULE

(3V)

ON/OFF

WALL 

SWITCH

LOW VOLTAGE

PLUG-IN

3V TRANSFORMER

NEUTRAL

HOT

GROUND

FLAME SPARKER/

SENSOR

REMOTE

CONTROL

SEE NOTE 1

ORG

WHT

VALVE

PIGGYBACK 

ON/OFF SWITCH

WHITE WIRE

CAN BE

PLUGGED

INTO ANY

OF #1-#5

LOCATIONS

ON THE

NEUTRAL SIDE

BLACK WIRE CAN BE

PLUGGED INTO ANY OF

#1 - #5 LOCATIONS

ON THE HOT SIDE

BRN

BR

N

VALVE

PLUG IN

GROUND TO

FIREPLACE

CHASSIS

I

S

WARNING

Wire 110V to electrical junction box.

Do NOT wire 110V to valve.

Do NOT wire 110V to wall switch.

• Incorrect wiring will damage millivolt valves.

• Uninterrupted  or  continuous  power  is

required at all times in IPI system EXCEPT

when using battery back-up.

• Incorrect wiring will override IPI safety lockout and may

cause  explosion.

Summary of Contents for Heat & Glo 6000TRXI-IPI

Page 1: ...located manufac tured mobile home wherenotprohibited by local codes 2 This appliance is only for use with the type of gas indicated on the rating plate This appliance is not convertible for use with o...

Page 2: ...ce front READ and UNDERSTAND all instructions carefully before starting the installation FAILURE TO FOLLOW these installation instructions may result in a possible fire hazard and will void the warran...

Page 3: ...tem Approvals 13 B Installing Vent Components 20 C Vent Termination 23 Step 4 Positioning Leveling and Securing the Fireplace 25 Step 5 Install the Optional Heat Zone Gas Kit 26 Step 6 The Gas Control...

Page 4: ...local codes or in the absence of local codes with the National Electric Code ANSI NFPA No 70 in the United States or to the CSAC22 1 Canadian Electric Code in Canada These models may be installed in...

Page 5: ...re maximum safety and benefit Failure to follow these instructions will void the owner s warranty and may present a fire hazard The Heat Glo Warranty will be voided by and Heat Glo disclaims any respo...

Page 6: ...LECTRICAL ACCESS GAS CONTROLS RATING PLATE AND LABELS TRIM DOOR HOOD TOP STANDOFFS 41 1 8 1044mm 38 965mm 36 1 8 916mm 25 1 4 642mm 34 5 8 879mm VENT COLLARS ELECTRICAL ACCESS 26 7 8 682mm 12 3 4 323m...

Page 7: ...ilt to enclose the gas fireplace and or its vent system Vertical vents that run on the outside of a building may be but are not required to be installed inside a chase CAUTION TREATMENT OF FIRESTOP SP...

Page 8: ...ference dimensions CAUTION MEASURE FIREPLACE DIMENSIONS AND VERIFY FRAMING METHODS AND WALL COVERING DETAILS BEFORE FRAMING Shows center of 10 x 12 vent framing holes for top and rear venting The cent...

Page 9: ...Vent Component Specifications 5 inch inner pipe 8 inch outer pipe NOTE PIPES OVERLAP 1 1 4 INCHESAT EACH JOINT DVP90ST 12 9 16 11 1 4 7 1 4 1 1 4 TYP 1 2 TYP 8 9 16 DVP36 DVP48 48 24 36 4 6 DVP4 DVP6...

Page 10: ...g configuration used Termination Kits Identifying Vent Components The vent systems installed on this gas fireplace may in clude one two or three 90 elbow assemblies The rela tionships of vertical rise...

Page 11: ...estricting chart see Figure 9 Figure 8 Figure 7 5 4 3 2 1 1 2 3 4 5 Adjustable Flue Restrictor see Figure 8 Figure 6 Straight Up Vertical Venting STRAIGHT UP VERTICAL VENTING V FT 40 MAX 12 4 M NOTE O...

Page 12: ...in corner installations Match the amount of vertical you have in the system with the chart to find the appropriate position to set the Flue Restrictor CHART Vertical Top Vent NG Top Vent LP Rear Vent...

Page 13: ...1 Venting with One 90 Elbow VENTING WITH ONE 1 90 ELBOW VENTING WITH ONE 1 90 ELBOW V FT H FT 1 MIN 305mm 5 MAX 1 52m 2 MIN 610mm 10 MAX 3 1m 3 MIN 914mm 15 MAX 4 65m 4 MIN 1 22m 20 MAX 6 2m V H 40 MA...

Page 14: ...3 1m 3 MIN 914 mm 6 MAX 1 86 m 15 MAX 4 65m 4 MIN 1 22 m 8 MAX 2 48 m 20 MAX 6 2m V H H1 40 MAX 12 4 m H 8 MAX 2 48 m H H1 20 MAX 6 2m Figure 14 Venting with Two 90 Elbows VENTING WITH TWO 2 90o ELBOW...

Page 15: ...3 1m 3 MIN 914mm 6 MAX 1 86m 15 MAX 4 65m 4 MIN 1 22m 8 MAX 2 48m 20 MAX 6 2m V H H1 H2 40 MAX 12 4 m H 8 MAX 2 48 m H H1 H2 20 MAX 6 2 m V H H H1 H2 1 MIN 305mm 2 MAX 610mm 5 MAX 1 52m 2 MIN 610mm 4...

Page 16: ...0 MAX 3 1m 3 MIN 914mm 15 MAX 4 65m 4 MIN 1 22m 20 MAX 6 2m NOTE H H1 20 MAX 6 2m V V1 H H1 40 MAX 12 4m V V1 FT H H1 FT 1 MIN 305mm 5 MAX 1 52m 2 MIN 610mm 10 MAX 3 1m 3 MIN 914mm 15 MAX 4 65m 4 MIN...

Page 17: ...SYSTEM IS AT TACHED TO THE TOP STARTING COLLARS WARNING FAILURE TO REMOVE INSULATION IN THE SET OF COLLARS YOU ARE USING COULD CAUSE A FIRE WARNING YOUMUSTLEAVETHEINSULATION IN PLACE IN THE SET OF COL...

Page 18: ...positioned so that it creates a 1 2 inch airspace between the shield and the combustible surface See Figure 20 4 Install Support Brackets Refer to Cinch Pipe and Termination Cap installation in struc...

Page 19: ...HIELD TRIM HEAT SHIELD IF TOO LONG ADD TO SHIELD IF TOO SHORT EXTERIOR FIRESTOP INTERIOR FIRESTOP HEAT SHIELD NOTE There must be NO INSULATION or other combustibles inside the framed firestop opening...

Page 20: ...ic Firestop JOIST CEILING FIRESTOP CEILING NAILS 4 REQUIRED CEILING CEILING FIRESTOP RAFTER NAILS 4 REQUIRED NOTE There must be NO INSULATION or other combustibles inside the framed firestop opening C...

Page 21: ...ly on one side and with an overhang are permitted with the dimensions specified for vinyl or non vinyl siding and soffits 1 There must be 3 feet minimum between termination caps 2 All mechanical air i...

Page 22: ...Slide the termination cap over the end of the vent pipe and snap into place Step 4 Positioning Leveling and Securing the Fireplace Place the fireplace into position Level the fireplace from side to s...

Page 23: ...WIREDDIRECTLYTOTHEFIRE PLACE JUNCTION BOX Figure 32 Gas Controls System Step 5 Installing the Optional Heat Zone Gas Kit NOTE There must be NO INSULATION or other com bustibles inside the framed fires...

Page 24: ...e can be plugged with non combustible insulation to pre vent cold air infiltration Open the fireplace lower grille insert the gas supply line throughthegaslinehole andconnectittotheshut offvalve When...

Page 25: ...with a 3 volt transformer The trans former plugs into the junction box and the two leads plug into the green control module see Figure 34 Intensifire Switch This model is equipped with an intensifire...

Page 26: ...BLE SPEED CONTROL TEMPERATURE SENSOR SWITCH WHT GRN BLK BLK 110 120 VAC BLOWER BLOWER RECEPTACLE BLK BLK BLK BLK WHT GROUND WHT BLK BLK BLK Figure 37 Cabin Kit Relay Wiring Diagram 3 16 MALE RED BLACK...

Page 27: ...EALED A 300 F MINIMUM SEALANT MATE RIAL MUST BE USED THESE JOINTS ARE NOT RE QUIRED TO BE SEALED ONLY NON COMBUSTIBLE MATERIAL USING 300 F MINIMUM ADHESIVE IF NEEDED CAN BE APPLIED AS FACING TO THE FI...

Page 28: ...ight need to be repositioned slightly to avoid excessive flame impingement Step 11 Installing Trim Logs and Ember Material Placing the Ember Material Ember material is shipped with this gas fireplace...

Page 29: ...hutter handle in you will be closing the air shutter To adjust loosen the wing nut Care should be taken when adjusting the air shutter so as not to cause the fireplace to soot If sooting occurs the ai...

Page 30: ...SE REFER TO THE USER S MANUALFORALL CAUTIONS SAFETY AND WARNING INFORMATION PERTAINING TO THE LIGHTING AND OPERATION OF THE FIREPLACE Step 14 Climate Control This model is equipped with a baffle which...

Page 31: ...cally By Qualified service technician Task Make a visual check of the straight flame sensor rod see Figure 32 Use emery cloth to carefully remove any existing film or white deposits Checking Flame Pat...

Reviews: