Heat & Glo Heat & Glo 6000TRXI-IPI Owner'S Manual Download Page 10

13

Heat & Glo  •  6000TRXI-IPI  •  386-901  Rev. I  •  1/06

Figure 5. Vent System Components and Termination Kits

Step 3.  Installing the Vent System

A.  Vent System Approvals

These models are approved to use DVP-series direct vent

pipe components and terminations (see Figures 4 and 5).

Approved vent system components are labeled for identifi-

cation. This pipe is tested and listed as an approved com-

ponent of the fireplace. The pipe is tested to be run inside

an enclosed wall. There is no requirement for inspection

openings at each joint within the wall. There is no required

pitch for horizontal vent runs. 

NO OTHER VENTING SYS-

TEMS OR COMPONENTS MAY BE USED

.

Detailed installation instructions are included with each vent

termination kit and should be used in conjunction with this

Installers Guide

.

The flame and ember appearance may vary based on the type

of fuel burned and the venting configuration used.

Termination Kits

Identifying Vent Components

The vent systems installed on this gas fireplace may in-

clude one, two, or three 90° elbow assemblies. The rela-

tionships of vertical rise to horizontal run in vent configura-

tions using 90° elbows 

MUST BE

 strictly adhered to. The

rise to run relationships are shown in the venting drawings

and tables. Refer to the diagrams on the next several pages.

NOTE:  Two 45° elbows may be used in place of one

90° elbow. Rise to run ratios in the vent system must

be followed if 45° elbows are used.

This model has vent starting collars on both the top and the

back of the unit. Depending upon the installation, decide

which

ONE

 set of starting collars will be used to attach the

vent system. The starting collar sealing cap must remain

on the starting collar 

NOT

used.

(Required to have a

minimum of 3 feet of

vertical in the vent system)

DVP-TV

PVK-80

DVP-TVHW

DVP-TRAP

DVP-TB1

SERIES

HORIZONTAL

TERMINATION

VERTICAL

TERMINATION

STORM COLLAR

ROOF FLASHING

PIPE LENGTH

CEILING

FIRESTOP

90 DEGREE

ELBOW

WALL FIRESTOP

Summary of Contents for Heat & Glo 6000TRXI-IPI

Page 1: ...located manufac tured mobile home wherenotprohibited by local codes 2 This appliance is only for use with the type of gas indicated on the rating plate This appliance is not convertible for use with o...

Page 2: ...ce front READ and UNDERSTAND all instructions carefully before starting the installation FAILURE TO FOLLOW these installation instructions may result in a possible fire hazard and will void the warran...

Page 3: ...tem Approvals 13 B Installing Vent Components 20 C Vent Termination 23 Step 4 Positioning Leveling and Securing the Fireplace 25 Step 5 Install the Optional Heat Zone Gas Kit 26 Step 6 The Gas Control...

Page 4: ...local codes or in the absence of local codes with the National Electric Code ANSI NFPA No 70 in the United States or to the CSAC22 1 Canadian Electric Code in Canada These models may be installed in...

Page 5: ...re maximum safety and benefit Failure to follow these instructions will void the owner s warranty and may present a fire hazard The Heat Glo Warranty will be voided by and Heat Glo disclaims any respo...

Page 6: ...LECTRICAL ACCESS GAS CONTROLS RATING PLATE AND LABELS TRIM DOOR HOOD TOP STANDOFFS 41 1 8 1044mm 38 965mm 36 1 8 916mm 25 1 4 642mm 34 5 8 879mm VENT COLLARS ELECTRICAL ACCESS 26 7 8 682mm 12 3 4 323m...

Page 7: ...ilt to enclose the gas fireplace and or its vent system Vertical vents that run on the outside of a building may be but are not required to be installed inside a chase CAUTION TREATMENT OF FIRESTOP SP...

Page 8: ...ference dimensions CAUTION MEASURE FIREPLACE DIMENSIONS AND VERIFY FRAMING METHODS AND WALL COVERING DETAILS BEFORE FRAMING Shows center of 10 x 12 vent framing holes for top and rear venting The cent...

Page 9: ...Vent Component Specifications 5 inch inner pipe 8 inch outer pipe NOTE PIPES OVERLAP 1 1 4 INCHESAT EACH JOINT DVP90ST 12 9 16 11 1 4 7 1 4 1 1 4 TYP 1 2 TYP 8 9 16 DVP36 DVP48 48 24 36 4 6 DVP4 DVP6...

Page 10: ...g configuration used Termination Kits Identifying Vent Components The vent systems installed on this gas fireplace may in clude one two or three 90 elbow assemblies The rela tionships of vertical rise...

Page 11: ...estricting chart see Figure 9 Figure 8 Figure 7 5 4 3 2 1 1 2 3 4 5 Adjustable Flue Restrictor see Figure 8 Figure 6 Straight Up Vertical Venting STRAIGHT UP VERTICAL VENTING V FT 40 MAX 12 4 M NOTE O...

Page 12: ...in corner installations Match the amount of vertical you have in the system with the chart to find the appropriate position to set the Flue Restrictor CHART Vertical Top Vent NG Top Vent LP Rear Vent...

Page 13: ...1 Venting with One 90 Elbow VENTING WITH ONE 1 90 ELBOW VENTING WITH ONE 1 90 ELBOW V FT H FT 1 MIN 305mm 5 MAX 1 52m 2 MIN 610mm 10 MAX 3 1m 3 MIN 914mm 15 MAX 4 65m 4 MIN 1 22m 20 MAX 6 2m V H 40 MA...

Page 14: ...3 1m 3 MIN 914 mm 6 MAX 1 86 m 15 MAX 4 65m 4 MIN 1 22 m 8 MAX 2 48 m 20 MAX 6 2m V H H1 40 MAX 12 4 m H 8 MAX 2 48 m H H1 20 MAX 6 2m Figure 14 Venting with Two 90 Elbows VENTING WITH TWO 2 90o ELBOW...

Page 15: ...3 1m 3 MIN 914mm 6 MAX 1 86m 15 MAX 4 65m 4 MIN 1 22m 8 MAX 2 48m 20 MAX 6 2m V H H1 H2 40 MAX 12 4 m H 8 MAX 2 48 m H H1 H2 20 MAX 6 2 m V H H H1 H2 1 MIN 305mm 2 MAX 610mm 5 MAX 1 52m 2 MIN 610mm 4...

Page 16: ...0 MAX 3 1m 3 MIN 914mm 15 MAX 4 65m 4 MIN 1 22m 20 MAX 6 2m NOTE H H1 20 MAX 6 2m V V1 H H1 40 MAX 12 4m V V1 FT H H1 FT 1 MIN 305mm 5 MAX 1 52m 2 MIN 610mm 10 MAX 3 1m 3 MIN 914mm 15 MAX 4 65m 4 MIN...

Page 17: ...SYSTEM IS AT TACHED TO THE TOP STARTING COLLARS WARNING FAILURE TO REMOVE INSULATION IN THE SET OF COLLARS YOU ARE USING COULD CAUSE A FIRE WARNING YOUMUSTLEAVETHEINSULATION IN PLACE IN THE SET OF COL...

Page 18: ...positioned so that it creates a 1 2 inch airspace between the shield and the combustible surface See Figure 20 4 Install Support Brackets Refer to Cinch Pipe and Termination Cap installation in struc...

Page 19: ...HIELD TRIM HEAT SHIELD IF TOO LONG ADD TO SHIELD IF TOO SHORT EXTERIOR FIRESTOP INTERIOR FIRESTOP HEAT SHIELD NOTE There must be NO INSULATION or other combustibles inside the framed firestop opening...

Page 20: ...ic Firestop JOIST CEILING FIRESTOP CEILING NAILS 4 REQUIRED CEILING CEILING FIRESTOP RAFTER NAILS 4 REQUIRED NOTE There must be NO INSULATION or other combustibles inside the framed firestop opening C...

Page 21: ...ly on one side and with an overhang are permitted with the dimensions specified for vinyl or non vinyl siding and soffits 1 There must be 3 feet minimum between termination caps 2 All mechanical air i...

Page 22: ...Slide the termination cap over the end of the vent pipe and snap into place Step 4 Positioning Leveling and Securing the Fireplace Place the fireplace into position Level the fireplace from side to s...

Page 23: ...WIREDDIRECTLYTOTHEFIRE PLACE JUNCTION BOX Figure 32 Gas Controls System Step 5 Installing the Optional Heat Zone Gas Kit NOTE There must be NO INSULATION or other com bustibles inside the framed fires...

Page 24: ...e can be plugged with non combustible insulation to pre vent cold air infiltration Open the fireplace lower grille insert the gas supply line throughthegaslinehole andconnectittotheshut offvalve When...

Page 25: ...with a 3 volt transformer The trans former plugs into the junction box and the two leads plug into the green control module see Figure 34 Intensifire Switch This model is equipped with an intensifire...

Page 26: ...BLE SPEED CONTROL TEMPERATURE SENSOR SWITCH WHT GRN BLK BLK 110 120 VAC BLOWER BLOWER RECEPTACLE BLK BLK BLK BLK WHT GROUND WHT BLK BLK BLK Figure 37 Cabin Kit Relay Wiring Diagram 3 16 MALE RED BLACK...

Page 27: ...EALED A 300 F MINIMUM SEALANT MATE RIAL MUST BE USED THESE JOINTS ARE NOT RE QUIRED TO BE SEALED ONLY NON COMBUSTIBLE MATERIAL USING 300 F MINIMUM ADHESIVE IF NEEDED CAN BE APPLIED AS FACING TO THE FI...

Page 28: ...ight need to be repositioned slightly to avoid excessive flame impingement Step 11 Installing Trim Logs and Ember Material Placing the Ember Material Ember material is shipped with this gas fireplace...

Page 29: ...hutter handle in you will be closing the air shutter To adjust loosen the wing nut Care should be taken when adjusting the air shutter so as not to cause the fireplace to soot If sooting occurs the ai...

Page 30: ...SE REFER TO THE USER S MANUALFORALL CAUTIONS SAFETY AND WARNING INFORMATION PERTAINING TO THE LIGHTING AND OPERATION OF THE FIREPLACE Step 14 Climate Control This model is equipped with a baffle which...

Page 31: ...cally By Qualified service technician Task Make a visual check of the straight flame sensor rod see Figure 32 Use emery cloth to carefully remove any existing film or white deposits Checking Flame Pat...

Reviews: