background image

4-03                                                                                                                23                                                                                                      480-1081

North Star 

EPA Certified Fireplace

For maximum operating efficiency with the lowest 

emissions, follow these operating procedures:

1.   Regardless  of  desired  heat  output,  when  loading 

the fireplace, burn your fireplace with the Slide Air 

Control wide open (fully to the right) for a minimum 

of 5 to 15 minutes.

2.   Regulate burn rate (heat output) by using the Slide 

Air Control.  See page 22.

3.   Heat  output  settings:   Following  5  to  15  minutes 

of  burning  with  the  control  wide  open  (

see  #1 

above

):

BTU / Hr

Below 10,000

10,000 - 15,000

15,000 - 30,000

Maximum Heat

*Slide Control

Slide LEFT to Stop

Stop to 1/8” -1/2” open

1/2” - 1-1/2” open

Fully open

*These are approximate settings, and will vary with 

type of wood or chimney draft.

NOTE:  BURN DRY, WELL-SEASONED WOOD.

7.  Fan Operating Instructions

Instructions with override switch in manual position.

8.  Heat Zone Operating Instructions

1.  

Initial (cold) startup:

  Leave fan off until your fire-

place  is  hot  and  a  good  coal  bed  is  established, 

approximately 30 minutes after fuel is lit.

2.  

High Burn Setting: 

 The fan may be left on through-

out the burn.

3.  

Medium or Medium High Burn Setting:

  The fan 

should be left off until a good burn is established, 

then turned on a medium or high rate.

4.  

Low Burn Setting:

  The fan tends to cool the fire-

place.   Leave  fan  off  until  the  burn  is  well  estab-

lished; then,  if  you  wish,  turn  the  fan  on  at  a  low 

rate.  

NOTE: 

 The Fan is equipped with a snap disc that will 

turn the blower on and off depending on the tempera-

ture  of  the  fireplace.   If  the  fan  is  not  coming  on  at 

the desired time, flip the override switch to manual and 

operate the fan as described above.

The override switch and the fan speed control are hard 

wired at time of installation and installed in a standard 

wall mount with junction box on the wall.

6.  Burning Guidelines 

The  Heat-Zone  accessory  kit  conveys  warm  air  from 

the fireplace through air duct(s) to remote locations in 

the same room or other rooms of the building.  One or 

two  Heat-Zone  kits  can  be  installed  on  the  fireplace.  

Follow  the  instructions  that  is  supplied  with  the  kit.  

Installation of this kit MUST be performed by a qualified 

service technician.  If any parts are missing or damaged, 

contact  your  local  Dealer  before  starting  installation.  

DO NOT install a damaged kit.  

The Heat-Zone kit is carefully engineered and must be 

installed only as specified.  If you modify it or any of 

its  components,  you  will  void  the  warranty  and  you 

may possibly cause a fire hazard.  Installation must be 

done  according  to  applicable  local,  state,  provincial, 

and/or national codes.

CAUTION:

ALL wiring should be done by a qualified electrician and 

shall  be  in  compliance  with  local  codes  and  with  the 

National  Electric  Code  ANSI/NF  No. 70-current  (in  the 

United  States), or  with  the  current  CSC22.1  Canadian 

Electric Code (inCanada).

CAUTION:

NEVER LEAVE THE FIRE UNATTENDED WHILE USING THE 

FIRESCREEN.  NEVER LEAVE CHILDREN UNATTENDED 

WHEN THERE IS A FIRE BURNING IN THE FIREPLACE.

9.  Operation of Fireplace with Optional Fire 

Screen Instructions

Alway  wear  gloves  when  installing  or  removing  the 

screen as the screen may become extremely hot while 

in use.  Use both hands to stablize the screen.  Ensure 

that the screen is fully attached.  Be careful not to stack 

wood close to the front or too high that logs could roll out 

the front.  Start with a small fire and adjust your heat to 

desired setting.  If smoke spillage occurs, put on gloves 

and then remove the screen and close the doors.  Refer 

to Flue Draft Troubleshooting on page 4.

CAUTION:

THE FIRESCREEN MAY BECOME EXTREMELY HOT WHILE 

IN USE.  ALWAYS WEAR GLOVES TO PREVENT INJURY.

Summary of Contents for BIR50

Page 1: ...ease read entire manual before you install and use your fireplace O T L Tested and Listed by Beaverton Oregon USA OMNI Test Laboratories Inc C Hearth Home Technologies 20802 Kensington Blvd Lakeville...

Page 2: ...shock Also make sure the fireplace is completely cooled before Installation and Draft Considerations 4 A Listings and Code Approvals 3 B Description of the Fireplace System 3 C Fireplace Dimesions Cl...

Page 3: ...F THE FIREPLACE SYSTEM A LISTINGS AND CODE APPROVALS This fireplace system has been tested and listed in accordance with UL127 and ULC S610 M87 standards and has been listed by OMNI Test Laboratories...

Page 4: ...ot Recommended Recommended Location Location NOT Recommended Cathedral Ceiling Construction 2nd Floor Balcony 1st Floor Multi level Roofs The outside air kit is installed on the right hand side of the...

Page 5: ...and 8 203mm to either side of the fuel opening must be insulated with non combustible floor protection with a minimum thickness of 1 25mm and k value 0 43 2 Fireplace is flush on the floor and Hearth...

Page 6: ...36 long SL348 Chimney Section 48 long SL3 Chimney Stabilizer SL315 Chimney Offset Return 15 SL330 Chimney Offset Return 30 FS338 Firestop Straight FS339 Firestop 15 FS340 Firestop 30 AS8 Straight Att...

Page 7: ...restop Spacer 24 A 8 101 2 Inside Diameter 8 Outside Diameter 101 2 A B 14 1 2 10 1 2 2 10 1 2 JB877 Joint Band 12 24 5 8 27 3 8 12 31 24 5 8 SL306 6 4 3 4 SL312 12 10 3 4 SL318 18 16 3 4 SL324 24 22...

Page 8: ...e Termination Cap CT35 Chase Top CAK4A Chimney Air Kit 15 3 4 TR342 TERMINATION CAP TOP OF UPPERMOST CHIMNEY SECTION 14 1 2 MAX DISTANCE CHASE TOP 23 14 3 4 17 3 4 8 Flue 10 1 2 Outer 16 1 2 13 1 4 22...

Page 9: ...to you when choosing a location for your fireplace This fireplace may be used as a room divider installed along a wall across a corner or used in an exterior chase See Figure 9A Locating the fireplace...

Page 10: ...ystem and chimney components have been tested to provide flexibility in construction The following figures are the minimum distances from the base of the fireplace 2 Framing the Fireplace 1 Min overal...

Page 11: ...icular chimney parts 5 Whenever the chimney penetrates a floor ceiling a firestop spacer must be installed 6 The effective height of the fireplace assembly is measured from the base of fireplace to to...

Page 12: ...t passes through the roof See Figure 12A b These chimney heights are necessary in the interest of safety but do not ensure smoke free operation Trees buildings adjoining roof lines adverse wind condit...

Page 13: ...strips measuring approximately 23 x 4 These strips are used to provide added protection where the fireplace and the hearth extension meet Slide each metal strip 2 under the front edge of the fireplac...

Page 14: ...dimension lumber used in the ceiling joists Install the firestop spacer These firestop spacers are designed to provide the minimum 2 air space required around the chimney In all situations the firest...

Page 15: ...y of the mobile home floor wall and ceiling roof must be maintaned i e Do not cut through floor joist wall stud ceiling truss etc WARNING NEVER DRAW COMBUSTION AIR FROM A WALL FLOOR OR CEILING CAVITY...

Page 16: ...t gravity from pulling the chimney sections apart the returns and the chimney stabilizers have straps for securing these parts to joists or rafters See Figure 16B 11 Marking the Exit Point of the Roof...

Page 17: ...ks The construction of and materials used for a hearth extension are shown in Figures 17A and 17B A hearth extension of this construction may be covered with any noncombustible decorative material and...

Page 18: ...stible and must not be used The floor protection specified includes some form of thermal designation such as R value thermal resistance or k factor thermal conductivity PROCEDURE 1 Convert specificati...

Page 19: ...may be positioned no lower than 60 from base of the fireplace The combustible mantel may have a maximum depth of 12 Combustible trim pieces that project no more than 1 1 2 from the face of the firepl...

Page 20: ...ovided with it Storm Collar Chase Flashing 6 min 2 min 2 min Storm Collar Chase Flashing 2 min 14 1 2 max Top of uppermost chimney section 2 Chase Top Construct a chase of desired materials main taini...

Page 21: ...laced through cracks around windows under doors etc Most newly constructed houses or existing homes fitted with tightly sealed doors and windows are relatively air tight The North Star Fireplace comes...

Page 22: ...y important to reload your fireplace while enough lively hot coals remain in order to provide the amount of heat needed to dry and rekindle the next load of wood It is best to open the air control for...

Page 23: ...installation and installed in a standard wall mount with junction box on the wall 6 Burning Guidelines The Heat Zone accessory kit conveys warm air from the fireplace through air duct s to remote loca...

Page 24: ...ll notice an odor and perhaps see some vapor rise from the fireplace surface this is normal We recommend that you open a window until the odor dissipates and paint is cured NOTE Fireplace should be ru...

Page 25: ...species of wood you burn the single most important factor that affects the way your fireplace operates is the amount of moisture in the wood The majority of the problems fireplace owners experience ar...

Page 26: ...m These three factors work together as a system to create the flue draft Increasing or decreasing any one of them will affect the other two and thus change the amount of draft in the entire system If...

Page 27: ...terials pending final disposal If the ashes are disposed of by burial in soil or otherwise locally dispersed they should be retained in the closed container until all embers have thoroughly cooled 5 O...

Page 28: ...t affect the finish and little maintenance is required just wipe clean as needed CAUTION Do not use polishes with abrasives as it will scratch the surface IMPORTANT REMOVE ALL LABELS FROM GLASS BEFORE...

Page 29: ...SRV28111 when ordering individual brick Provide brick dimension or copy this page mark the desired brick and take it to your authroized dealer IMPORTANT The bricks are very similar in size Be certain...

Page 30: ...place After Fireplace Installation 1 Remove the firebrick from the bottom of the fireplace 2 Remove the 2 screws from the access panel in the firebox floor 3 Pry up the access panel using the screwdri...

Page 31: ...r the air channel and out of hole at the other end It is necessary to remove the first tube in order to remove the baffle 5 Slide fiber board baffle forward to front of fireplace and straight out thro...

Page 32: ...lace 480 1081 32 4 03 Service Parts Beginning Manufacturing Date 02 17 03 Ending Manufacturing Date __________ EXPLODED VIEW Door Assembly Fascia Assembly Part number list on following page 1 0 27 1 2...

Page 33: ...ng on page 32 832 3400 5 Door Handle Assembly includes 2 door handles HANDLES 480 securing bracket lock nut latch cam key and cam latch 6 Fan Replacement 812 4900 7 Fascia FASCIA NS 8 Glass Assembly f...

Page 34: ...ce Enclosure 16 17 Locations 9 Firestop Spacer 7 Installation 14 Firewood 25 26 Floor Protection 5 Flue 26 Framing 9 10 Fuel 2 25 26 G General Information 21 Glass Cleaning 28 Glass Replacement 28 Gol...

Page 35: ...ents regular maintenance cleaning and temporary repairs do not qualify for a service call fee and will not be covered The replacement of consumer replaceable items and installation of upgraded compone...

Page 36: ...4 03 36 480 1081 PLEASE RETURN THESE INSTRUCTIONS TO THE HOME OWNER WHEN INSTALLATION IS COMPLETE ATTENTION INSTALLER...

Reviews: