background image

Heat & Glo  •  6000TR-OAK, 6000TR-OAK-IPI  •  383-901  Rev. K  •   5/06

9

Î

For all side wall horizontally vented gas fueled equipment

installed in every dwelling, building or structure used in

whole or in part for residential purposes, including those

owned or operated by the Commonwealth and where the

side wall exhaust vent termination is less than seven (7)

feet above finished grade in the area of the venting, includ-

ing but not limited to decks and porches, the following re-

quirements shall be satisfied:

Installation of Carbon Monoxide Detectors

At the time of installation of the side wall horizontal vented

gas fueled equipment, the installing plumber or gasfitter

shall observe that a hard wired carbon monoxide detector

with an alarm and battery back-up is installed on the floor

level where the gas equipment is to be installed. In addi-

tion, the installing plumber or gasfitter shall observe that a

battery operated or hard wired carbon monoxide detector

with an alarm is installed on each additional level of the

dwelling, building or structure served by the side wall hori-

zontal vented gas fueled equipment. It shall be the respon-

sibility of the property owner to secure the services of qual-

ified licensed professionals for the installation of hard wired

carbon monoxide detectors.

In the event that the side wall horizontally vented gas fu-

eled equipment is installed in a crawl space or an attic, the

hard wired carbon monoxide detector with alarm and bat-

tery back-up may be installed on the next adjacent floor

level.

In the event that the requirements of this subdivision can

not be met at the time of completion of installation, the

owner shall have a period of thirty (30) days to comply with

the above requirements; provided, however, that during said

thirty (30) day period, a battery operated carbon monoxide

detector with an alarm shall be installed.

Approved Carbon Monoxide Detectors

Each carbon monoxide detector as required in accordance

with the above provisions shall comply with NFPA 720 and

be ANSI/UL 2034 listed and IAS certified.

Signage

A metal or plastic identification plate shall be permanently

mounted to the exterior of the building at a minimum height

of eight (8) feet above grade directly in line with the ex-

haust vent terminal for the horizontally vented gas fueled

heating appliance or equipment. The sign shall read, in

print size no less than one-half (1/2) inch in size, 

“GAS

VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OB-

STRUCTIONS”.

Inspection

The state or local gas inspector of the side wall horizontally

vented gas fueled equipment shall not approve the installa-

tion unless, upon inspection, the inspector observes carbon

monoxide detectors and signage installed in accordance with

the provisions of 248 CMR 5.08(2)(a)1 through 4.

Exemptions

The following equipment is exempt from 248 CMR 5.08(2)(a)1

through 4:
• The equipment listed in Chapter 10 entitled “Equipment

Not Required To Be Vented” in the most current edition

of NFPA 54 as adopted by the Board; and

• Product Approved side wall horizontally vented gas fu-

eled equipment installed in a room or structure sepa-

rate from the dwelling, building or structure used in whole

or in part for residential purposes.

MANUFACTURER REQUIREMENTS
Gas Equipment Venting System Provided

When the manufacturer of Product Approved side wall hor-

izontally vented gas equipment provides a venting system

design or venting system components with the equipment,

the instructions provided by the manufacturer for installa-

tion of the equipment and the venting system shall include:
• Detailed instructions for the installation of the venting

system design or the venting system components; and

• A complete parts list for the venting system design or

venting system.

Gas Equipment Venting System NOT Provided

When the manufacturer of a Product Approved side wall

horizontally vented gas fueled equipment does not provide

the parts for venting the flue gases, but identifies “special

venting systems”, the following requirements shall be sat-

isfied by the manufacturer:
• The referenced “special venting system” instructions shall

be included with the appliance or equipment installation

instructions; and

• The “special venting systems” shall be Product Approved

by the Board, and the instructions for that system shall

include a parts list and detailed installation instructions.

A copy of all installation instructions for all Product Ap-

proved side wall horizontally vented gas fueled equipment,

all venting instructions, all parts lists for venting instruc-

tions, and/or all venting design instructions shall remain

with the appliance or equipment at the completion of the

installation.

See Gas Connection section for additional Common-

wealth of Massachusetts requirements.

NOTE:

The following requirements reference various

Massachusetts and national codes not contained in

this document.

Requirements for the Commonwealth of

Massachusetts

Summary of Contents for 6000TR-OAK

Page 1: ...the rating plate This appliance is not convertible for use with other gases unless a certified kit is used Please contact your Heat Glo dealer with any questions or concerns For the number of your ne...

Page 2: ...fireplace front READ and UNDERSTAND all instructions carefully before starting the installation FAILURE TO FOLLOW these installation instructions may result in a possible fire hazard and will void the...

Page 3: ...tep 3 Installing the Vent System 15 A Vent System Approvals 15 B Installing Vent Components 22 C Vent Termination 25 Step 4 Positioning Leveling and Securing the Fireplace 27 Step 5 Installing the Opt...

Page 4: ...cordance with local codes or in the absence of local codes with the National Electric Code ANSI NFPA No 70 in the United States or to the CSAC22 1 Canadian Electric Code in Canada These models may be...

Page 5: ...read in print size no less than one half 1 2 inch in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF ALL OB STRUCTIONS Inspection The state or local gas inspector of the side wall horizontally vented gas f...

Page 6: ...to ensure maximum safety and benefit Failure to follow these instructions will void the owner s warranty and may present a fire hazard The Heat Glo Warranty will be voided by and Heat Glo disclaims an...

Page 7: ...S LINE ACCESS ELECTRICAL ACCESS GAS CONTROLS RATING PLATE AND LABELS TRIM DOOR HOOD TOP STANDOFFS 41 1040mm 38 965mm 36 1 8 916mm 25 1 4 642mm 34 5 8 879mm 8 203mm VENT COLLARS ELECTRICAL ACCESS 26 7...

Page 8: ...eplace Chase A chase is a vertical box like structure built to enclose the gas fireplace and or its vent system Vertical vents that run on the outside of a building may be but are not required to be i...

Page 9: ...ing reference dimensions CAUTION MEASURE FIREPLACE DIMENSIONS AND VERIFY FRAMING METHODS AND WALL COVERING DETAILS BEFORE FRAMING 1 2 CLEARANCE FROM BACK OF FIREPLACE TO COMBUSTIBLE 0 CLEARANCE TO FRA...

Page 10: ...irect Vent Component Specifications 5 inch inner pipe 8 inch outer pipe NOTE PIPES OVERLAP 1 1 4 INCHESAT EACH JOINT DVP90ST 12 9 16 11 1 4 7 1 4 1 1 4 TYP 1 2 TYP 8 9 16 DVP36 DVP48 48 24 36 4 6 DVP4...

Page 11: ...guration used Identifying Vent Components The vent systems installed on this gas fireplace may in clude one two or three 90 elbow assemblies The rela tionships of vertical rise to horizontal run in ve...

Page 12: ...a 1 4 nut driver by removing the four screws securing it in place see Figure 7 Figure 8 Flue Restrictor BREAK HERE Figure 7 EXHAUST SHIELD FLUE RESTRICTOR 2 Break the Flue Restrictor into two pieces...

Page 13: ...o find the appropriate position to set the Flue Restrictor see Figure 9 1 2 3 4 5 SETTINGS 1 2 3 4 5 Figure 10 4 Center the Flue Restrictor on vent and secure in place by using two self tapping screws...

Page 14: ...rance Figure 12 Venting with One 90 Elbow VENTING WITH ONE 1 90 ELBOW VENTING WITH ONE 1 90 ELBOW V FT H FT 1 MIN 305mm 5 MAX 1 52m 2 MIN 610mm 10 MAX 3 1m 3 MIN 914mm 15 MAX 4 65m 4 MIN 1 22m 20 MAX...

Page 15: ...10 MAX 3 1m 3 MIN 914 mm 6 MAX 1 86 m 15 MAX 4 65m 4 MIN 1 22 m 8 MAX 2 48 m 20 MAX 6 2m V H H1 40 MAX 12 4 m H 8 MAX 2 48 m H H1 20 MAX 6 2m Figure 15 Venting with Two 90 Elbows VENTING WITH TWO 2 90...

Page 16: ...0 MAX 3 1m 3 MIN 914mm 6 MAX 1 86m 15 MAX 4 65m 4 MIN 1 22m 8 MAX 2 48m 20 MAX 6 2m V H H1 H2 40 MAX 12 4 m H 8 MAX 2 48 m H H1 H2 20 MAX 6 2 m V H H H1 H2 1 MIN 305mm 2 MAX 610mm 5 MAX 1 52m 2 MIN 61...

Page 17: ...610mm 10 MAX 3 1m 3 MIN 914mm 15 MAX 4 65m 4 MIN 1 22m 20 MAX 6 2m NOTE H H1 20 MAX 6 2m V V1 H H1 40 MAX 12 4m V V1 FT H H1 FT 1 MIN 305mm 5 MAX 1 52m 2 MIN 610mm 10 MAX 3 1m 3 MIN 914mm 15 MAX 4 65...

Page 18: ...VENT SYSTEM IS AT TACHED TO THE TOP STARTING COLLARS WARNING FAILURE TO REMOVE INSULATION IN THE SET OF COLLARS YOU ARE USING COULD CAUSE A FIRE WARNING YOUMUSTLEAVETHEINSULATION IN PLACE IN THE SET...

Page 19: ...ow and positioned so that it creates a 1 2 inch airspace between the shield and the combustible surface See Figure 21 COMBUSTIBLE SURFACE DIRECTION UP HEAT SHIELD 90 ELBOW 0 Figure 22 If the combustib...

Page 20: ...STOP HEAT SHIELD NOTE There must be NO INSULATION or other combustibles inside the framed firestop opening 10 12 INTERIOR WALL SHIELD For Vertical Runs One ceiling firestop is REQUIRED at the hole in...

Page 21: ...ramed firestop opening Figure 28 Trapezoid Termination Cap C Vent Termination Refer to Cinch Pipe and Termination Cap installation in structions Horizontal Termination The termination kit should pass...

Page 22: ...open only on one side and with an overhang are permitted with the dimensions specified for vinyl or non vinyl siding and soffits 1 There must be 3 feet minimum between termination caps 2 All mechanic...

Page 23: ...ening To seal the roof hole and to divert rain and snow from the vent system Attach a flashing to the roof using nails and use a non hardening mastic around the edges of the flashing base where it mee...

Page 24: ...steps Step 6 The Gas Control Systems WARNING THIS UNIT IS NOT FOR USE WITH SOLID FUEL Two types of gas control systems are used with these models Standing Pilot Ignition and Intermittent Pilot Igniti...

Page 25: ...ustible insulation to pre vent cold air infiltration Open the fireplace lower grille insert the gas supply line throughthegaslinehole andconnectittotheshut offvalve When attaching the pipe support the...

Page 26: ...all Switch Position the wall switch in the desired position on a wall Run a maximum of 25 feet 7 8 m or less length of 18 A W G minimum wire and connect it to the fireplace ON OFF switch pigtails WARN...

Page 27: ...ck to black The fireplace can be used as necessary Once power 110 VAC is re stored disconnect red and black wire leads to extend bat tery life Optional Accessories Optional remote control kits require...

Page 28: ...S ARE SEALED A 300 F MINIMUM SEALANT MATE RIAL MUST BE USED THESE JOINTS ARE NOT RE QUIRED TO BE SEALED ONLY NON COMBUSTIBLE MATERIAL USING 300 F MINIMUM ADHESIVE IF NEEDED CAN BE APPLIED AS FACING TO...

Page 29: ...over ports Care should be taken not to cover the lighting trail of ports from back to front When placing Glowing embers onto the burner care should be taken so that the ports are not covered Place th...

Page 30: ...minimum vertical vent run see Figure 43 If your installation has more than the minimum required vertical vent length adjustment of the air shutter may be necessary to obtain optimal flame appearance...

Page 31: ...al check of your fireplace s flame patterns Make sure the flames are steady not lifting or floating See Figure 44 The flame sensor IPI or thermopile thermocouple standing pilot tips should be covered...

Reviews: