background image

Heat & Glo  •  6000TR-OAK, 6000TR-OAK-IPI  •  383-901  Rev. K  •   5/06

34

Step 12.  Before Lighting  the Fireplace

Before

 lighting the fireplace, be sure to do the following:

Remove all paperwork from underneath the fireplace.
Review safety warnings and cautions

• Read the 

Safety and Warning Information

 section at

the beginning of this 

Installers Guide

.

Double-check for gas leaks

• Before lighting the fireplace, double-check the unit for

possible gas leaks.

Double-check vent terminations and front grilles for

obstructions.

• Before lighting the fireplace, double-check the unit for

possible obstructions that could be blocking the vent ter-

minations or the front grilles.

Double-check for faulty components

• Any component that is found to be faulty 

MUST BE

 re-

placed with an approved component. Tampering with the

fireplace components is 

DANGEROUS

 and voids all war-

ranties.

A small amount of air will be in the gas supply lines. When

first lighting the fireplace, it will take a few minutes for the

lines to purge themselves of this air. Once the purging is

complete, the fireplace will light and will operate normally.
Subsequent lightings of the fireplace will not require this

purging of air from the gas supply lines,

 unless the gas

valve has been turned to the OFF position

, in which

case the air would have to be purged.

Air Shutter Setting

This fireplace has an adjustable air shutter (which controls

the primary air) factory set for the minimum vertical vent run

(see  Figure  43).  If  your  installation  has  more  than  the

minimum required vertical vent length, adjustment of the air

shutter  may  be  necessary  to  obtain  optimal  flame

appearance.

This should be adjusted by a qualified

installer at the time of installation.

By pushing the air shutter handle in, you will be closing the

air shutter. To adjust loosen the wing nut. Care should be

taken when adjusting the air shutter so as not to cause the

fireplace to soot. If sooting occurs the air shutter will need

to be opened by pulling the handle out. When finished tighten

wing nut.

Figure 43.

AIR SHUTTER

WING NUT

This statement is in compliance with SPCS 16 CFR Sec-

tion 1201.5 “Certification and labeling requirements” which

refers to 15 USC 2063 stating “…Such certificate shall ac-

company the product or shall otherwise be furnished to any

distributor or retailer to whom the product is delivered.”
Some local building codes require the use of tempered glass

with permanent marking in such locations. Glass meeting

this requirement is available from the factory. Please con-

tact your dealer or distributor to order.

During this break-in period it is recommended that some

windows in the house be opened for air circulation. This will

help avoid setting off smoke detectors, and help eliminate

any odors associated with the fireplace’s initial burning.

NOTE:

 The fireplace should be run 3 to 4 hours on the

initial start-up. Turn it off and let it cool completely. Remove

and clean the glass. Replace the glass and run the fireplace

for an additional 8 hours. This will help to cure the products

used in the paint and logs.

Summary of Contents for 6000TR-OAK

Page 1: ...the rating plate This appliance is not convertible for use with other gases unless a certified kit is used Please contact your Heat Glo dealer with any questions or concerns For the number of your ne...

Page 2: ...fireplace front READ and UNDERSTAND all instructions carefully before starting the installation FAILURE TO FOLLOW these installation instructions may result in a possible fire hazard and will void the...

Page 3: ...tep 3 Installing the Vent System 15 A Vent System Approvals 15 B Installing Vent Components 22 C Vent Termination 25 Step 4 Positioning Leveling and Securing the Fireplace 27 Step 5 Installing the Opt...

Page 4: ...cordance with local codes or in the absence of local codes with the National Electric Code ANSI NFPA No 70 in the United States or to the CSAC22 1 Canadian Electric Code in Canada These models may be...

Page 5: ...read in print size no less than one half 1 2 inch in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF ALL OB STRUCTIONS Inspection The state or local gas inspector of the side wall horizontally vented gas f...

Page 6: ...to ensure maximum safety and benefit Failure to follow these instructions will void the owner s warranty and may present a fire hazard The Heat Glo Warranty will be voided by and Heat Glo disclaims an...

Page 7: ...S LINE ACCESS ELECTRICAL ACCESS GAS CONTROLS RATING PLATE AND LABELS TRIM DOOR HOOD TOP STANDOFFS 41 1040mm 38 965mm 36 1 8 916mm 25 1 4 642mm 34 5 8 879mm 8 203mm VENT COLLARS ELECTRICAL ACCESS 26 7...

Page 8: ...eplace Chase A chase is a vertical box like structure built to enclose the gas fireplace and or its vent system Vertical vents that run on the outside of a building may be but are not required to be i...

Page 9: ...ing reference dimensions CAUTION MEASURE FIREPLACE DIMENSIONS AND VERIFY FRAMING METHODS AND WALL COVERING DETAILS BEFORE FRAMING 1 2 CLEARANCE FROM BACK OF FIREPLACE TO COMBUSTIBLE 0 CLEARANCE TO FRA...

Page 10: ...irect Vent Component Specifications 5 inch inner pipe 8 inch outer pipe NOTE PIPES OVERLAP 1 1 4 INCHESAT EACH JOINT DVP90ST 12 9 16 11 1 4 7 1 4 1 1 4 TYP 1 2 TYP 8 9 16 DVP36 DVP48 48 24 36 4 6 DVP4...

Page 11: ...guration used Identifying Vent Components The vent systems installed on this gas fireplace may in clude one two or three 90 elbow assemblies The rela tionships of vertical rise to horizontal run in ve...

Page 12: ...a 1 4 nut driver by removing the four screws securing it in place see Figure 7 Figure 8 Flue Restrictor BREAK HERE Figure 7 EXHAUST SHIELD FLUE RESTRICTOR 2 Break the Flue Restrictor into two pieces...

Page 13: ...o find the appropriate position to set the Flue Restrictor see Figure 9 1 2 3 4 5 SETTINGS 1 2 3 4 5 Figure 10 4 Center the Flue Restrictor on vent and secure in place by using two self tapping screws...

Page 14: ...rance Figure 12 Venting with One 90 Elbow VENTING WITH ONE 1 90 ELBOW VENTING WITH ONE 1 90 ELBOW V FT H FT 1 MIN 305mm 5 MAX 1 52m 2 MIN 610mm 10 MAX 3 1m 3 MIN 914mm 15 MAX 4 65m 4 MIN 1 22m 20 MAX...

Page 15: ...10 MAX 3 1m 3 MIN 914 mm 6 MAX 1 86 m 15 MAX 4 65m 4 MIN 1 22 m 8 MAX 2 48 m 20 MAX 6 2m V H H1 40 MAX 12 4 m H 8 MAX 2 48 m H H1 20 MAX 6 2m Figure 15 Venting with Two 90 Elbows VENTING WITH TWO 2 90...

Page 16: ...0 MAX 3 1m 3 MIN 914mm 6 MAX 1 86m 15 MAX 4 65m 4 MIN 1 22m 8 MAX 2 48m 20 MAX 6 2m V H H1 H2 40 MAX 12 4 m H 8 MAX 2 48 m H H1 H2 20 MAX 6 2 m V H H H1 H2 1 MIN 305mm 2 MAX 610mm 5 MAX 1 52m 2 MIN 61...

Page 17: ...610mm 10 MAX 3 1m 3 MIN 914mm 15 MAX 4 65m 4 MIN 1 22m 20 MAX 6 2m NOTE H H1 20 MAX 6 2m V V1 H H1 40 MAX 12 4m V V1 FT H H1 FT 1 MIN 305mm 5 MAX 1 52m 2 MIN 610mm 10 MAX 3 1m 3 MIN 914mm 15 MAX 4 65...

Page 18: ...VENT SYSTEM IS AT TACHED TO THE TOP STARTING COLLARS WARNING FAILURE TO REMOVE INSULATION IN THE SET OF COLLARS YOU ARE USING COULD CAUSE A FIRE WARNING YOUMUSTLEAVETHEINSULATION IN PLACE IN THE SET...

Page 19: ...ow and positioned so that it creates a 1 2 inch airspace between the shield and the combustible surface See Figure 21 COMBUSTIBLE SURFACE DIRECTION UP HEAT SHIELD 90 ELBOW 0 Figure 22 If the combustib...

Page 20: ...STOP HEAT SHIELD NOTE There must be NO INSULATION or other combustibles inside the framed firestop opening 10 12 INTERIOR WALL SHIELD For Vertical Runs One ceiling firestop is REQUIRED at the hole in...

Page 21: ...ramed firestop opening Figure 28 Trapezoid Termination Cap C Vent Termination Refer to Cinch Pipe and Termination Cap installation in structions Horizontal Termination The termination kit should pass...

Page 22: ...open only on one side and with an overhang are permitted with the dimensions specified for vinyl or non vinyl siding and soffits 1 There must be 3 feet minimum between termination caps 2 All mechanic...

Page 23: ...ening To seal the roof hole and to divert rain and snow from the vent system Attach a flashing to the roof using nails and use a non hardening mastic around the edges of the flashing base where it mee...

Page 24: ...steps Step 6 The Gas Control Systems WARNING THIS UNIT IS NOT FOR USE WITH SOLID FUEL Two types of gas control systems are used with these models Standing Pilot Ignition and Intermittent Pilot Igniti...

Page 25: ...ustible insulation to pre vent cold air infiltration Open the fireplace lower grille insert the gas supply line throughthegaslinehole andconnectittotheshut offvalve When attaching the pipe support the...

Page 26: ...all Switch Position the wall switch in the desired position on a wall Run a maximum of 25 feet 7 8 m or less length of 18 A W G minimum wire and connect it to the fireplace ON OFF switch pigtails WARN...

Page 27: ...ck to black The fireplace can be used as necessary Once power 110 VAC is re stored disconnect red and black wire leads to extend bat tery life Optional Accessories Optional remote control kits require...

Page 28: ...S ARE SEALED A 300 F MINIMUM SEALANT MATE RIAL MUST BE USED THESE JOINTS ARE NOT RE QUIRED TO BE SEALED ONLY NON COMBUSTIBLE MATERIAL USING 300 F MINIMUM ADHESIVE IF NEEDED CAN BE APPLIED AS FACING TO...

Page 29: ...over ports Care should be taken not to cover the lighting trail of ports from back to front When placing Glowing embers onto the burner care should be taken so that the ports are not covered Place th...

Page 30: ...minimum vertical vent run see Figure 43 If your installation has more than the minimum required vertical vent length adjustment of the air shutter may be necessary to obtain optimal flame appearance...

Page 31: ...al check of your fireplace s flame patterns Make sure the flames are steady not lifting or floating See Figure 44 The flame sensor IPI or thermopile thermocouple standing pilot tips should be covered...

Reviews: