Heat & Glo  •  6000TR-OAK, 6000TR-OAK-IPI  •  383-901  Rev. K  •   5/06

26

V

= VENT  TERMINAL

X

= AIR SUPPLY INLET

= AREA WHERE TERMINAL IS NOT PERMITTED

     Figure 29.  Minimum Clearances for Terminations

A

= 12" ....................... clearances above grade, veran-

da, porch, deck or balcony

B

= 12" ....................... clearances  to  window  or  door

that may be opened, or to per-

manently  closed  window.

D*

= 18" ....................... vertical clearance to unventilat-

ed soffit or to ventilated soffit lo-

cated above the terminal

 *30” ...................... for  vinyl  clad  soffits  and  below

electrical  service

F

=  9" ........................ clearance to outside corner

G

= 6" ......................... clearance to inside corner

H

= 3 ft. (Canada) ...... not  to  be  installed  above  a  gas

meter/regulator  assembly  within

3 feet (90cm) horizontally from the

center-line of the regulator

I

= 3 ft. (U.S.A.)

6 ft. (Canada) ...... clearance  to  gas  service  regu-

lator vent outlet

J

= 9" (U.S.A.)

12"  (Canada) ........ clearance to non-mechanical air

supply  inlet  to  building  or  the

combustion air inlet to any other

appliance

K

= 3 ft. (U.S.A.)

6 ft. (Canada) ......... clearance  to  a  mechanical

air supply inlet

L** = 7 ft. ......................... clearance  above  paved

sidewalk or a paved driveway

located on 

public

 property

M*** = 18" ......................... clearance  under  veranda,

porch, deck, balcony or over-

hang

42” ......................... vinyl

N

= 6” ........................... non-vinyl  sidewalls

12” ......................... vinyl  sidewalls

P

= 8 ft.

CAUTION:

IF EXTERIOR WALLS ARE FINISHED WITH VINYL SIDING, IT IS SUGGESTED THAT A VINYL PROTECTOR KIT BE

INSTALLED.

  ** a  vent  shall  not  terminate  directly  above  a  sidewalk  or  paved

driveway  which  is  located  between  two  single  family  dwellings

and  serves  both  dwellings.

 *** only permitted if veranda, porch, deck or balcony is fully open on

a minimum of 2 sides beneath the floor, or meets Note 2.

NOTE 1

:  On  private  property  where  termination  is  less  than  7  feet

above a sidewalk, driveway, deck, porch, veranda or balcony, use of

a listed cap shield is suggested.

NOTE 2

: Termination in an alcove space (spaces open only on one side

and with an overhang) are permitted with the dimensions specified for

vinyl or non-vinyl siding and soffits. 

1

. There must be 3 feet minimum

between termination caps. 

2.

 All mechanical air intakes within 10 feet

of a termination cap must be a minimum of 3 feet below the termination

cap.

3.

 All gravity air intakes within 3 feet of a termination cap must be

a minimum of 1 foot below the termination cap.

M

N

P

R

Q

(See Note 1)

(See Note 1)

(See Note 2)

S =  6" .......................... clearance from sides of elec-

trical service

T = 12" ......................... clearance  above  electrical

service

______________________________________________________________________

______________________________________________________________________

______________________________________________________________________

______________________________________________________________________

Q

MIN

     R

MAX

  1 cap

  3 feet

   2 x Q 

ACTUAL

  2 caps

  6 feet

   1 x Q 

ACTUAL

  3 caps

  9 feet

2/3 x Q 

ACTUAL

  4 caps

12 feet

1/2 x Q 

ACTUAL

Q

MIN

 = # termination caps x 3        R

MAX

 = (2 / # termination caps) x Q

ACTUAL

(See Note 5)

(See Note 5)

Electrical

Service

V

S

V

S

V

T

D*

V

NOTE 3

:  Local  codes  or  regulations  may  require  different

clearances.

NOTE 4: 

Termination caps may be hot. Consider their proximity to

doors  or  other  traffic  areas.

NOTE 5: 

Location of the vent termination must not interfere with

access  to  the  electrical  service.

WARNING: In the U.S:

 Vent system termination is 

NOT

 permitted

in  screened  porches. You  must  follow  side  wall,  overhang  and

ground clearances as stated in the instructions.

In Canada:

 Vent system termination is 

NOT

 permitted in screened

porches.  Vent  system  termination  is  permitted  in  porch  areas

with  two  or  more  sides  open.  You  must  follow  all  side  walls,

overhang and ground clearances as stated in the instructions.
Heat  &  Glo  assumes  no  responsibility  for  the  improper  perfor-

mance of the fireplace when the venting system does not meet

these  requirements.

D

E

B

L

v

v

v

v

v

v

v

v

B

B

A

H

M

X

J or K

I

A

G

F

U.S.

(3 FT)

B

Summary of Contents for 6000TR-OAK

Page 1: ...the rating plate This appliance is not convertible for use with other gases unless a certified kit is used Please contact your Heat Glo dealer with any questions or concerns For the number of your ne...

Page 2: ...fireplace front READ and UNDERSTAND all instructions carefully before starting the installation FAILURE TO FOLLOW these installation instructions may result in a possible fire hazard and will void the...

Page 3: ...tep 3 Installing the Vent System 15 A Vent System Approvals 15 B Installing Vent Components 22 C Vent Termination 25 Step 4 Positioning Leveling and Securing the Fireplace 27 Step 5 Installing the Opt...

Page 4: ...cordance with local codes or in the absence of local codes with the National Electric Code ANSI NFPA No 70 in the United States or to the CSAC22 1 Canadian Electric Code in Canada These models may be...

Page 5: ...read in print size no less than one half 1 2 inch in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF ALL OB STRUCTIONS Inspection The state or local gas inspector of the side wall horizontally vented gas f...

Page 6: ...to ensure maximum safety and benefit Failure to follow these instructions will void the owner s warranty and may present a fire hazard The Heat Glo Warranty will be voided by and Heat Glo disclaims an...

Page 7: ...S LINE ACCESS ELECTRICAL ACCESS GAS CONTROLS RATING PLATE AND LABELS TRIM DOOR HOOD TOP STANDOFFS 41 1040mm 38 965mm 36 1 8 916mm 25 1 4 642mm 34 5 8 879mm 8 203mm VENT COLLARS ELECTRICAL ACCESS 26 7...

Page 8: ...eplace Chase A chase is a vertical box like structure built to enclose the gas fireplace and or its vent system Vertical vents that run on the outside of a building may be but are not required to be i...

Page 9: ...ing reference dimensions CAUTION MEASURE FIREPLACE DIMENSIONS AND VERIFY FRAMING METHODS AND WALL COVERING DETAILS BEFORE FRAMING 1 2 CLEARANCE FROM BACK OF FIREPLACE TO COMBUSTIBLE 0 CLEARANCE TO FRA...

Page 10: ...irect Vent Component Specifications 5 inch inner pipe 8 inch outer pipe NOTE PIPES OVERLAP 1 1 4 INCHESAT EACH JOINT DVP90ST 12 9 16 11 1 4 7 1 4 1 1 4 TYP 1 2 TYP 8 9 16 DVP36 DVP48 48 24 36 4 6 DVP4...

Page 11: ...guration used Identifying Vent Components The vent systems installed on this gas fireplace may in clude one two or three 90 elbow assemblies The rela tionships of vertical rise to horizontal run in ve...

Page 12: ...a 1 4 nut driver by removing the four screws securing it in place see Figure 7 Figure 8 Flue Restrictor BREAK HERE Figure 7 EXHAUST SHIELD FLUE RESTRICTOR 2 Break the Flue Restrictor into two pieces...

Page 13: ...o find the appropriate position to set the Flue Restrictor see Figure 9 1 2 3 4 5 SETTINGS 1 2 3 4 5 Figure 10 4 Center the Flue Restrictor on vent and secure in place by using two self tapping screws...

Page 14: ...rance Figure 12 Venting with One 90 Elbow VENTING WITH ONE 1 90 ELBOW VENTING WITH ONE 1 90 ELBOW V FT H FT 1 MIN 305mm 5 MAX 1 52m 2 MIN 610mm 10 MAX 3 1m 3 MIN 914mm 15 MAX 4 65m 4 MIN 1 22m 20 MAX...

Page 15: ...10 MAX 3 1m 3 MIN 914 mm 6 MAX 1 86 m 15 MAX 4 65m 4 MIN 1 22 m 8 MAX 2 48 m 20 MAX 6 2m V H H1 40 MAX 12 4 m H 8 MAX 2 48 m H H1 20 MAX 6 2m Figure 15 Venting with Two 90 Elbows VENTING WITH TWO 2 90...

Page 16: ...0 MAX 3 1m 3 MIN 914mm 6 MAX 1 86m 15 MAX 4 65m 4 MIN 1 22m 8 MAX 2 48m 20 MAX 6 2m V H H1 H2 40 MAX 12 4 m H 8 MAX 2 48 m H H1 H2 20 MAX 6 2 m V H H H1 H2 1 MIN 305mm 2 MAX 610mm 5 MAX 1 52m 2 MIN 61...

Page 17: ...610mm 10 MAX 3 1m 3 MIN 914mm 15 MAX 4 65m 4 MIN 1 22m 20 MAX 6 2m NOTE H H1 20 MAX 6 2m V V1 H H1 40 MAX 12 4m V V1 FT H H1 FT 1 MIN 305mm 5 MAX 1 52m 2 MIN 610mm 10 MAX 3 1m 3 MIN 914mm 15 MAX 4 65...

Page 18: ...VENT SYSTEM IS AT TACHED TO THE TOP STARTING COLLARS WARNING FAILURE TO REMOVE INSULATION IN THE SET OF COLLARS YOU ARE USING COULD CAUSE A FIRE WARNING YOUMUSTLEAVETHEINSULATION IN PLACE IN THE SET...

Page 19: ...ow and positioned so that it creates a 1 2 inch airspace between the shield and the combustible surface See Figure 21 COMBUSTIBLE SURFACE DIRECTION UP HEAT SHIELD 90 ELBOW 0 Figure 22 If the combustib...

Page 20: ...STOP HEAT SHIELD NOTE There must be NO INSULATION or other combustibles inside the framed firestop opening 10 12 INTERIOR WALL SHIELD For Vertical Runs One ceiling firestop is REQUIRED at the hole in...

Page 21: ...ramed firestop opening Figure 28 Trapezoid Termination Cap C Vent Termination Refer to Cinch Pipe and Termination Cap installation in structions Horizontal Termination The termination kit should pass...

Page 22: ...open only on one side and with an overhang are permitted with the dimensions specified for vinyl or non vinyl siding and soffits 1 There must be 3 feet minimum between termination caps 2 All mechanic...

Page 23: ...ening To seal the roof hole and to divert rain and snow from the vent system Attach a flashing to the roof using nails and use a non hardening mastic around the edges of the flashing base where it mee...

Page 24: ...steps Step 6 The Gas Control Systems WARNING THIS UNIT IS NOT FOR USE WITH SOLID FUEL Two types of gas control systems are used with these models Standing Pilot Ignition and Intermittent Pilot Igniti...

Page 25: ...ustible insulation to pre vent cold air infiltration Open the fireplace lower grille insert the gas supply line throughthegaslinehole andconnectittotheshut offvalve When attaching the pipe support the...

Page 26: ...all Switch Position the wall switch in the desired position on a wall Run a maximum of 25 feet 7 8 m or less length of 18 A W G minimum wire and connect it to the fireplace ON OFF switch pigtails WARN...

Page 27: ...ck to black The fireplace can be used as necessary Once power 110 VAC is re stored disconnect red and black wire leads to extend bat tery life Optional Accessories Optional remote control kits require...

Page 28: ...S ARE SEALED A 300 F MINIMUM SEALANT MATE RIAL MUST BE USED THESE JOINTS ARE NOT RE QUIRED TO BE SEALED ONLY NON COMBUSTIBLE MATERIAL USING 300 F MINIMUM ADHESIVE IF NEEDED CAN BE APPLIED AS FACING TO...

Page 29: ...over ports Care should be taken not to cover the lighting trail of ports from back to front When placing Glowing embers onto the burner care should be taken so that the ports are not covered Place th...

Page 30: ...minimum vertical vent run see Figure 43 If your installation has more than the minimum required vertical vent length adjustment of the air shutter may be necessary to obtain optimal flame appearance...

Page 31: ...al check of your fireplace s flame patterns Make sure the flames are steady not lifting or floating See Figure 44 The flame sensor IPI or thermopile thermocouple standing pilot tips should be covered...

Reviews: