Heat & Glo • 6000GL-IPI-R, 6000GL-IPI-S • 2102-900 Rev. B • 5/06
13
Figure 5.3
Figure 5.4
D. Vent Diagrams
WARNING
1. Top Vent - Horizontal Termination
One Elbow
Two Elbows
NOTE:
For corner installations: A 6 inch
(152mm) section of straight pipe may need
to be attached to the appliance before a
90
o
elbow, to allow the vent pipe to clear
the top standoffs.
NOTE:
For corner installations: A
6 inch (152mm) section of straight
pipe may need to be attached to
the appliance before a 90
o
elbow, to
allow the vent pipe to clear the top
standoffs.
V
1
Minimum
H
1
Maximum
Elbow only
2 ft
610 mm
1 ft.
305 mm
3 ft.
914 mm
2 ft.
610 mm
6 ft.
1.8 m
3 ft.
914 mm
11 ft.
3.4 m
4 ft.
1.2 m
20 ft.
6.1 m
V
1
+ H
1
= 40 ft. (12.2 m) Maximum
H
1
= 20 ft. (6.1 m) Maximum
V
1
Minimum
H
1
+ H
2
Maximum
0 in.
0 mm
1 ft.
305 mm
6 in.
152 mm
2 ft.
610 mm
1 ft.
305 mm
2 ft.
610 mm
2 ft.
610 mm
4 ft.
1.2 m
3 ft.
914 mm
9 ft.
2.7 m
4 ft.
1.2 m
18 ft.
5.5 m
5 ft.
1.5 m
20 ft.
6.1 m
V
1
+ H
1
+ H
2
= 40 ft. (12.2 m) Maximum
H
1
+ H
2
= 20 ft. (6.1 m) Maximum
Fire Risk. Explosion Risk.
Do NOT pack insulation or other combustibles
between ceiling fi restops.
• ALWAYS maintain specified clearances
around venting and fi restop systems.
• Install wall shield and ceiling fi restops as
specifi ed.
Failure to keep insulation or other material
away from vent pipe may cause fi re.
NOTE:
The 6000 series fi replaces can adapt to SL
series vent pipe, if desired.
When venting off the top of the unit, use a DVP-826
adapter and a minimum 48 inch vertical section of SL
series vent pipe.
After
the 48 inch vertical section, the venting table
rules must be followed. The fi rst 48 inch vertical section
is NOT counted as part of the
vertical
components
in the table. It is still counted as part of the overall
maximum run. All venting table rules for the vent run
must still be followed.
Example:
DVP pipe 3 ft. min. vertical = 11 ft. max. horizontal
SL pipe 7 ft. min. vertical = 11 ft. max. horizontal