background image

7019-801C

July 10, 2019

15

SANTA FE PELLET INSERT

D. Draft

Draft is the pressure difference needed to vent an 

appliance successfully. When an appliance is drafting 

successfully, all combustion byproducts are exiting the 

home through the chimney.

Install through the warm airspace enclosed by the building 

envelope. This helps to produce more draft, especially 

during lighting and die-down of the fire.

Considerations for successful draft include:

•  Preventing negative pressure

•  Location of appliance and chimney

C. Negative Pressure

Negative pressure results from the imbalance of air 

available for the appliance to operate properly. It can be 

strongest in lower levels of the house.

Causes include:

•  Exhaust fans (kitchen, bath, etc.)

•  Range hoods

•  Combustion air requirements for furnaces, water 

appliances and other combustion appliances

•  Clothes dryers

•  Location of return-air vents to furnace or 

air conditioning

•  Imbalances of the HVAC air handling system

•  Upper level air leaks such as: 

 - Recessed lighting

 - Attic hatch

 - Duct leaks

To minimize the effects of negative air pressure:

•  Install the outside air kit with the intake facing prevailing 

winds during the heating season

•  Ensure adequate outdoor air for all combustion 

appliances and exhaust equipment

•  Ensure furnace and air conditioning return vents are 

not located in the immediate vicinity of the appliance

•  Avoid installing the appliance near doors, walkways or 

small isolated spaces

•  Recessed lighting should be a “sealed can” design

•  Attic hatches weather stripped or sealed

•  Attic mounted duct work and air handler joints and 

seams taped or sealed

E. Chimney and Exhaust Connection

1.  Chimney & Connector:

 Use 3 or 4 inch (76-102mm) 

diameter type “L” or “PL” venting system. It can be 

vented vertically or horizontally.

2.  Mobile Home:

 Approved for all Listed pellet vent. 

A Quadra-Fire Outside Air Kit must be used with 

manufactured home installations.

3. 

Install vent at clearances specified by the 

vent manufacturer.

4.  Secure exhaust venting system to the appliance with 

at least 3 screws. Also secure all connector pipe joints 

with at least 3 screws through each joint.

5. 

DO NOT INSTALL A FLUE DAMPER IN THE 

EXHAUST VENTING SYSTEM OF THIS Appliance.

6. 

DO NOT CONNECT THIS Appliance TO A CHIMNEY 

FLUE SERVING ANOTHER APPLIANCE.

NOTE:

 If burning shelled field corn, you must use 

approved venting specifically designed 

for corn. Follow the instructions from the 

venting manufacturer.

NOTE:

 All pipe must be welded seam pipe whenever 

possible. Seal pipe joints with high temperature 

silicone (500°F [260°C] minimum rated only).

NOTE:

 The appliance exhaust outlet is designed to 

accommodate 3 inch venting. Use of 4 inch 

venting requires the use of a 3-to-4 inch exhaust 

vent increaser in addition to any other venting 

components needed, sold separately.

NOTICE:

 Hearth & Home Technologies assumes no 

responsibility for the improper performance of 

the chimney system caused by:

•  Inadequate draft due to environmental conditions

•  Down drafts

•  Tight sealing construction of the structure

•  Mechanical exhausting devices

WARNING

USE ONLY RECOMMENDED VENTING 

COMPONENTS; OTHERWISE MAKESHIFT PARTS 

MAY RESULT IN PROPERTY DAMAGE, PERSONAL 

INJURY, OR DEATH. 

WARNING

Risk of Asphyxiation! 

Negative pressure can cause spillage of combustion 

fumes and soot.

Summary of Contents for Quadra-Fire SANTA FE SANTAFEI-C

Page 1: ...iquids in the vicinity of this or any other appliance Do not over fire If appliance or chimney connector glows you are over firing Over firing will void your warranty Comply with all minimum clearance...

Page 2: ...and Components 6 E Install Checklist 7 3 Dimensions and Clearances 8 A Appliance Dimensions 8 B Clearance To Combustibles UL and ULC 9 C Masonry Chimney and Fireplace Clearances 10 D Minimum Opening f...

Page 3: ...800 to 22 400 hr BTU Input 9 300 to 30 600 hr Vent Size 3 4 L or PL or 6 inches Hopper Capacity 45 lbs Fuel Premium Wood Pellets Weighted average LHV Low Heating Value efficiency using data collected...

Page 4: ...om size out air must be installed I California Prop65 WARNING This product and the fuels used to operate this product wood and the products of combustion of such fuels can expose you to chemicals incl...

Page 5: ...ior to installation Installation MUST comply with local regional state and national codes and regulations Consult insurance carrier local building inspector fire officials or authorities having jurisd...

Page 6: ...ation to ensure maximum safety and benefit Follow pipe manufacturer instructions for installation and air clearance requirements C Tools And Supplies Needed Tools and building supplies normally requir...

Page 7: ...ation and copying this checklist for your file That this checklist remain visible at all times on the appliance until the installation is complete Electrical 120 VAC unswitched power provided to the a...

Page 8: ...23 5 8 in 600mm 9 5 8 in 246mm 11 1 8 in 283mm 21 1 2 in 546mm 12 3 4 in 325mm 9 1 2 in 243mm 30 in 762mm 40 in 1016mm 14 5 8 in 373mm 9 7 8 in 250mm Figure 8 4 Front View with large basic panel set...

Page 9: ...or protection The size of your floor protector choice must be added to this dimension 25 in 635mm 25 in 635mm 32 7 8 in 835mm 15 1 4 in 387mm NOTE Illustrations reflect typical installations and are F...

Page 10: ...ng dimensions include a 1 4 6mm clearance around unit NOTE If trim measurement is over 3 4 in 19mm in depth use mantle or side clearances to combustibles Location Inches Millimeters A Height 23 1 4 59...

Page 11: ...d 250 2061 WARNING THIS FIREPLACE MAY HAVE BEEN ALTERED TO ACCOMMODATE AN INSERT IT MUST BE RETURNED TO ITS ORIGINAL CONDITION BEFORE USE AS A SOLID FUEL BURNING FIREPLACE 250 2061 Heath Home Technolo...

Page 12: ...uilt zero clearance fireplace system must not be altered The flue liner top support attachment must not reduce the air flow for the existing air cooled chimney system No dilution air is allowed to ent...

Page 13: ...and protruding parts of the structure P 12 in Clearance above roof line for vertical terminations All minimum clearances are listed with an Outside Air Kit OAK installed unless otherwise noted in tabl...

Page 14: ...and House demand may consume the air needed for the appliance It may be necessary to add additional ventilation to the space in which the pellet appliance is located Consult with your local HVAC profe...

Page 15: ...unted duct work and air handler joints and seams taped or sealed E Chimney and Exhaust Connection 1 Chimney Connector Use 3 or 4 inch 76 102mm diameter type L or PL venting system It can be vented ver...

Page 16: ...his installation Figure 16 2 1 Locate the calculated equivalent feet of pipe on the vertical left side of the chart 2 Move to the right horizontally on the chart until you reach your altitude above se...

Page 17: ...any edge to prevent future serviceability Fire Risk Inspection of Chimney Masonry chimney must be in good condition Meets minimum standard of NFPA 211 Factory built chimney must be a minimum 6 inch 15...

Page 18: ...passage through a wall or partition of combustible construction is desired the installation shall conform to CAN CSA B365 NOTE Illustrations reflect typical installations and are FOR DESIGN PURPOSES O...

Page 19: ...N ULC S635 Standard for Lining Systems for Existing Masonry or Factory Built Chimneys and Vents or CAN ULC S640 Standard for Lining Systems for New Masonry Chimneys 12 305mm min below 12 305mm min abo...

Page 20: ...ure 20 2 4 Slide trim ring over flex pipe and run pipe through wall 5 Attach hose to outside termination cap with second hose clamp 6 Secure termination cap to outside surface 7 Secure trim ring to in...

Page 21: ...tape 6 Place cut edge of trim under top lip and into position on scissors Place side pieces on first and then front piece The front piece overlaps side pieces 7 Once you are satisfied with the positio...

Page 22: ...each leg Figure 22 2 3 Open the hopper lid by pulling toward you This will make it easier to set the panels in place Secure the panels to the insert 2 screws per leg as shown in Figure 22 3 4 Connect...

Page 23: ...wall anchors 4 Route the wires through the opening in the base plate and hold the base against the wall while aligning up to the holes Attach base plate using a Phillips head screwdriver and two screw...

Page 24: ...firebox 4 Push the logs to the far left and far right against the sides of the firebox Figure 24 2 5 To clean the logs use a vacuum and a soft brush attachment or a paint brush Figure 24 2 Figure 24 1...

Page 25: ...rd HUD CFR 3280 Part 24 PART NUMBER 811 0872 Spark Arestor Cap Roof Flashing Storm Collar Joist Shield Firestop Double Wall Connector Pipe Figure 25 1 CAUTION THE STRUCTURAL INTEGRITY OF THE MOBILE HO...

Page 26: ...7019 801C July 10 2019 26 SANTA FE PELLET INSERT 8 Reference Materials A Service Maintenance List Date of Service Performed By Description of Service...

Page 27: ...7019 801C July 10 2019 27 SANTA FE PELLET INSERT Date of Service Performed By Description of Service...

Page 28: ...7019 801C July 10 2019 28 SANTA FE PELLET INSERT Date of Service Performed By Description of Service...

Page 29: ...7019 801C July 10 2019 29 SANTA FE PELLET INSERT Date of Service Performed By Description of Service...

Page 30: ...kel SP SFI3040 NB Nickel SP SFI3040 NL Bracket L Trim 832 0840 Logo Quadra Fire Nickel 7000 649 10 Reset Button Assembly SRV7000 040 Smart Batt Il 841 0970 Smart Stat Il 841 0960 Thermostat Programmab...

Page 31: ...4 7000 157 24 Y Nut Wing 1 4 20 Pkg of 12 226 0110 12 Nut Wing 8 32 Pkg of 24 226 0160 24 Y Pin 3 16 X 1 2 7000 229 Rivet Iron 1 4 X 1 1 4 Pkg of 25 229 0090 25 Screw Flat Head 1 4 20 Pkg of 24 7000 1...

Page 32: ...purchased installed _________________________________________________________________________ Serial Number ____________________________________ Location on appliance ___________________________ Deale...

Reviews: