Hearth & Home IntelliFire IFT-RC150 Installation Instructions Manual Download Page 6

Hearth & Home Technologies  •  RC150 IntelliFire

 Touch Installation Instructions  •  2326-980  •  9/16

6

5.  IntelliFire™ Touch Electronic Control Module (IFT-ECM)

1.  The Electronic Control Module (IFT-ECM) has a 

three-position ON/OFF/REMOTE selector switch 

that must be set for proper operation. See figure 7. 

When changing switch positions,it is important to 

pause in each position for 1-2 seconds. 

 

OFF Position:   

 

The appliance will not respond to any commands 

from a wired wall switch, IFT-RC150  or IFT-RC400 

remote controls.  The unit should be in the OFF 

position during installation, service, backup battery 

installation, fuel conversion and to reset the IFT-

ECM in the event the system goes into a LOCK-

OUT mode as the result of a system error.  When 

switched to the OFF position while the appliance is 

operating, the system will shut down. 

 

ON  Position:   

 

The  appliance  will  ignite  and  run continuously at 

the HI flame setting.  No adjustment in flame height 

is possible. The IFT-ECM has a safety feature that 

will automatically shut down the fireplace after 9 

hours of continuous operation in the ON position.   

 

Remote Position:   

 

The remote position allows operation of the 

appliance from a wired wall switch, IFT-RC400 or 

IFT-RC150 remote controls.  The IFT-ECM switch 

must be in this position to pair the IFT-ECM with the 

IFT-ACM (if installed), and/or IFT-RC400 and IFT-

RC150 remote controls.  See the IFT-RC400 or IFT-

RC150 installation manual for detailed instructions 

on pairing the IFT-ECM with the remote controls. 

After successfully pairing a IFT-RC400, all installed 

accessories can be controlled by the IFT-RC400 

(see IFT-RC400 user manual).  The  RC150 allows 

the user to turn ON/OFF the flame in the appliance 

and activate the Cold Climate mode if desired.  The 

IFT-ECM has a safety feature that will automatically 

shut down the fireplace after 9 hours of continuous 

operation without receiving a command from the 

IFT-RC400 or IFT-RC150. 

2.  If multiple control options are installed, the IFT-ECM 

will respond to the last command from the wired wall 

switch, IFT-RC400 or IFT-RC150.  The wired wall 

switch is NOT available if a Power Vent is used.

3.  The Pilot button on the IFT-ECM activates the Cold 

Climate function of the fireplace.  This function lights 

the pilot flame ONLY to provide enough heat in the 

firebox to reduce condensation in cool, high humidity 

ambient conditions.  To activate the Cold Climate 

function, press and hold the Pilot button for one second 

and release.  The IFT-ECM will flash two green LED 

IFT-ECM Detailed Operating Instruction

DANGER

1. 

beep twice and light and rectify the pilot flame when 

pressed to activate.  To turn off Cold Climate, press 

and hold the Pilot button for one second and release.  

The IFT-ECM will flash one green LED blink, beep 

once and shut down the pilot flame.  If remote controls 

are paired with the IFT-ECM, this feature can also 

be activated with the IFT-RC400 and/or IFT-RC150. 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2.  An IFT-ECM reset is required if the module is in a 

lock-out condition.  When this occurs, the appliance 

is shut down and the IFT-ECM status indicator LED 

will be blinking a RED/GREEN error code along with 

a one-time audible double- beep.  If the IFT-ECM is 

in a lock-out condition, refer to the troubleshooting 

chart to interpret the error code and take corrective 

action as required.  To reset the IFT-ECM after a 

lock-out error: 

Figure 7.  IFT-ECM

CAUTION!  Risk of burns! Appliance surfaces are hot 

when operating and during cool down. Use care and wear 

gloves when opening the front and accessing compo-

nents inside the appliance.

 

       -  Be aware the appliance may be HOT, use  

          care in accessing the IFT-ECM. 

 

       -  Set the IFT-ECM 3-position selector switch to        

          OFF position. 

 

       

-  Wait five (5) minutes to allow possible     

 

          accumulated gas to clear. 

 

       -  Set the IFT-ECM 3-position selector switch to ON  

          or IFT-REM position.  Module will beep once and  

          flash a three GREEN LED code on successful 

 

          startup. 

 

       -  If placed in ON position, the appliance will ignite  

          normally if the error condition was corrected. 

 

       -  If placed in IFT-REM position, use the paired IFT-   

          RC400, IFT-RC150 or wired wall switch to start  

          the appliance; appliance will ignite normally if the 

          error condition was corrected.
      -  If the IFT-ECM re-enters the lock-out condition  

         after these steps, call your dealer for service.

Summary of Contents for IntelliFire IFT-RC150

Page 1: ...nd or use of any component part not approved by Hearth Home Technologies Any such action may cause a fire hazard Read understand and follow these instructions for safe installation and operation B Determine Location Determine the location for the IFT RC150 The selected location should be in the same space as the gas appli ance with visual sight of the appliance The device must be placed within 30 ...

Page 2: ...3 2 On the IFT ECM move the ON OFF REMOTE switch to the REMOTE position The green LED will blink three times A few seconds later an audible beep will occur to indicate that the system is ready Note If the green LED continues to blink slowly system is searching for a clear channel wait until it stops before proceeding to step 3 3 Locate the pairing hole on the IFT ECM See Figure 4 Using a paper cli...

Page 3: ...GNITER ADAPTER I S 6 PIN 6V DC BATTERY PACK RED BLK BRN ORANGE PILOT GREEN MAIN BLK RED IFT RC150 WIRELESS WALL SWITCH RF MODULE ELECTRONIC CONTROL MODULE VALVE OPTIONAL WIRE ASSEMBLY MODULE RESET SWITCH APPLIANCE ON OFF CONTROL BRN BLK OPTIONAL ON SOME MODELS ONLY SPLITTER BLK RED F Wiring Diagram IntelliFire Touch System Wiring Diagram ...

Page 4: ...wer source in the event of a power outage Batteries should not be used as a primary long term power source A Turn Flame ON OFF To turn the flame ON press the top of the rocker switch To turn the flame OFF press the bottom of the rocker switch The IFT ECM on the appliance has a safety feature that automatically shuts down the appliance after 9 hours of continuous operation without receiving a comma...

Page 5: ...ve IFT ECM or RF module Manually turn OFF the appliance following steps listed under 3E and contact your dealer The IFT RC150 LED blinks randomly even though no command is given Communicating with IFT ECM This is normal operation The IFT RC150 com municates periodically with the IFT ECM to send or receive information The IFT RC150 LED blinks in a pattern of every 3 seconds continuously for longer ...

Page 6: ...wired wall switch IFT RC400 or IFT RC150 The wired wall switch is NOT available if a Power Vent is used 3 The Pilot button on the IFT ECM activates the Cold Climate function of the fireplace This function lights the pilot flame ONLY to provide enough heat in the firebox to reduce condensation in cool high humidity ambient conditions To activate the Cold Climate function press and hold the Pilot bu...

Page 7: ...or or no system ground Verify black gound wire in valve harness is connected to metal chassis of fireplace Pilot won t light there is no noise or spark 2 Red 1 Green Lockout Pilot solenoid not detected Check if valve harness orange wire is connected to pilot so lenoid valve Check pilot solenoid resistance nominal is 40 ohms If open or shorted replace valve Check valve harness wire continuity if op...

Page 8: ... Check main valve solenoid resistance nominal is 60 ohms If open or shorted replace valve Verify valve inlet pressure is correct for gas type Pilot and main do not light ECM goes into 5 Red 1 Green Lockout Power Vent PV Failure Power Vent blower defective check wiring to IFT ACM check if blower is working Check if PV pressure switch is connected to brown and black wire in 6 pin valve wire harness ...

Page 9: ...ever there is no guarantee that in terference will not occur in a particular installation If this equipment does cause harmful interference to radio or television reception which can be determined by turning the equipment off and on the user is encouraged to try to correct the interference by one or more of the following measures Reorient or relocate the receiving antenna Increase the separation b...

Reviews: