Hearth & Home Heatilator Eco Choice PS50-C Installation Manual Download Page 15

15

June 18, 2019

7059-800B

HEATILATOR ECO-CHOICE PS50

F. Equivalent Feet of Pipe 

The table below can help you calculate the equivalent feet 

of pipe which is a method used to determine pellet vent 

size

 (Figure 15.1)

.

2 ft. 

2 ft. 

3 ft. 

2 ft. 

Example of 3 Elbow-Rear Vent Termination Calculation

NOTE

: This is a generic example and is not intended to represent any 

specific fuel type.

Figure 15.2

3 in. or 4 in. (76mm or 

102mm)  Diameter   Pipe 

3 in. or 4 in. (76mm or 

102mm)  Diameter   Pipe 

Equivalent Pipe 

Length In Feet

Equivalent Pipe 

Length In Feet

ALTITUDE IN THOUSANDS OF FEET

ALTITUDE IN THOUSANDS OF FEET

0

20

30

   

1        2       3       4       5       6        7       8        9     10

4 in. (102mm) Diameter Pipe Only

4 in. (102mm) Diameter Pipe Only

10

Example 1

Example 1

Example 2

Example 2

•  Example 1

: If the equivalent length of pipe is 23 feet 

(7m) with altitude of 8,000 feet (2438m) you must use 4 

inch (102mm) diameter type “L” or “PL” vent.

•  Example 2

: If the equivalent length of pipe is 12 feet 

(3.7m) with altitude of 6,000 feet (1829m) you may 

use 3 or 4 inch (76 to 102mm) diameter type “L” or 

“PL” vent.

G. Pipe Selection Chart

The chart will help you in determining proper venting 

size according to the equivalent feet of pipe calculated 

previously and the altitude above sea level of this 

installation

 (Figure 15.2)

.

1.  Locate the calculated equivalent feet of pipe on the 

vertical left side of the chart.

2.  Move to the right horizontally on the chart until you 

reach your altitude above sea level.

3. 

If you fall below the diagonal line, 3 or 4 inch (76 to 

102mm) pipe may be used.

4.  If it is anywhere above the diagonal line, a 4 inch 

(102mm) diameter pipe is required.

Figure 15.1

Vent surfaces get HOT, can cause burns 

if touched. Non-combustible shielding or 

guards may be required.

WARNING

Pellet 

Venting 

Component

# of 

Elbows

Feet of 

Pipe

Multiplied 

By

Equivalent 

Feet

Components 

Equivalent 

Feet

90° Elbow 

or Tee

3

X

5

15

45° Elbow

X

3

Horizontal 

Pipe

7

X

1

7

Vertical 

Pipe

2

X

0.5

1

Total Equivalent Feet

23

NOTICE!

• 

A 90° elbow is 5 times as restrictive to the flow of 

exhaust gases under positive pressure as 1 foot 

(305mm) of horizontal pipe.

•  A foot of horizontal pipe is twice as restrictive as a 

foot of vertical pipe.

Risk of Injury or Property Damage.

•  Improper installation, adjustment, 

alteration, service or maintenance can 

cause injury or property damage. 

•  Refer to the owner’s information manual 

provided with this appliance. 

• 

For assistance or additional information 

consult a qualified installer, service 

agency or your dealer.

WARNING

 

Risk of Fire! 

• 

Only LISTED venting components may be 

used.

• 

NO OTHER vent components may be 

used.

• 

Substitute or damaged vent components 

may impair safe operation.

WARNING

Summary of Contents for Heatilator Eco Choice PS50-C

Page 1: ...ay cause house fire HOT SURFACES Glass and other surfaces are hot during operation AND cool down WARNING Hot glass will cause burns Do not touch glass until it is cooled NEVER allow children to touch...

Page 2: ...haust Connection 14 F Equivalent Feet of Pipe 15 G Pipe Selection Chart 15 5 Venting Systems 16 A Through The Wall 16 B Vertical into Existing Class A Chimney 17 C Vertical Interior Typical Installati...

Page 3: ...put 7 500 to 36 600 per hr BTU Input 13 100 to 49 900 per hr Vent Size 3 or 4 inches L or PL Hopper Capacity 83 lbs Fuel Premium Wood Pellets Weighted average LHV Low Heating Value efficiency using da...

Page 4: ...gnite and burn composed of any combination of the following Steel Plaster Brick Iron Concrete Tile Glass Slate Materials reported as passing ASTM E 136 Standard Test Method for Behavior of Metals in a...

Page 5: ...CAUTION If burning shelled field corn you must use approved venting specifically designed for corn to prevent corrosion or degradation Follow the instructions from the venting manufacturer NOTICE Chec...

Page 6: ...carefully during the installation to ensure maximum safety and benefit Follow pipe manufacturer instructions for installation and air clearance requirements Reciprocating Saw Channel Locks Hammer Phi...

Page 7: ...llation and copying this checklist for your file That this checklist remain visible at all times on the appliance until the installation is complete Electrical 120 VAC unswitched power provided to the...

Page 8: ...Top View Figure 8 3 Side View Figure 8 4 Side View with Top Vent Adapter 24 1 4 616 24 1 4 616 26 7 16 672 28 5 16 719 9 3 4 248 2 3 8 60 20 1 4 514 32 813 35 3 4 908 10 11 16 272 23 1 4 591 3 1 8 79...

Page 9: ...Installation Inches Millimeters D Back Wall to Adapter 1 25 E Side Wall to Appliance 14 356 F Back Wall to Appliance 6 1 4 159 Corner Installation Inches Millimeters G Walls to Appliance 2 51 Vertical...

Page 10: ...end 51mm beyond each side of pipe shaded area to the wall thimble 152mm Front of glass 348mm USA INSTALLATIONS A non combustible floor protection is recommended extending beneath the flue pipe when in...

Page 11: ...53 1346 n a n a C Depth n a n a 48 1219 D Side Wall 14 356 n a n a E Top 16 533 n a n a F Mantel Depth n a n a 36 914 Installations Into Alcove All minimums listed are to a combustible surface NOTE Il...

Page 12: ...pi ces d passant de la structure P 305 mm 12 po D gagements au dessus du toit pour les abat vents verticaux Tous les d gagements minimum correspondent une installation avec un ensemble de prise d air...

Page 13: ...emand House demand may consume the air needed for the appliance It may be necessary to add additional ventilation to the space in which the pellet appliance is located Consult with your local HVAC pro...

Page 14: ...combustion byproducts are exiting the home through the chimney Install through the warm airspace enclosed by the building envelope This helps to produce more draft especially during lighting and die...

Page 15: ...this installation Figure 15 2 1 Locate the calculated equivalent feet of pipe on the vertical left side of the chart 2 Move to the right horizontally on the chart until you reach your altitude above...

Page 16: ...oose which one is best for your installation 2 in 51mm Minimum 2 in 51mm Minimum 6 in 152mm Minimum 6 in 152mm Minimum Figure 16 2 5 Venting Systems NOTE In Canada where passage through a wall or part...

Page 17: ...installation instructions for all reduced air clearances installations B Vertical into Existing Class A Chimney Firestop Flashing Rain Cap 6 in 152mm Minimum Non combustible Hearth Pad 3 in 76mm Mini...

Page 18: ...Minimum Fireclay Flue Liner with Airspace Concrete Cap Non combustible Hearth Pad Airtight Clean Out Door Clean Out cover Sheathing 3 in 76mm Minimum 1 in 25mm Clearance Flashing Fireclay flue Liner...

Page 19: ...ters and hole saw or jig saw 1 Measure distance from floor to air vent opening in appliance and mark location on wall 2 Use a saw to cut opening in wall 2 inch kit Cut a 2 1 2 to 3 inch opening on ins...

Page 20: ...iate position 3 Install the vent pipe into the adapter be sure to silicone all joints Clean Out Cover Clean Out Cover Figure 20 2 Rear Vent Adapter Figure 20 3 Rear to Top Vent Adapter 90 D Thermostat...

Page 21: ...24 Spark Arestor Cap Roof Flashing Storm Collar Joist Shield Firestop Double Wall Connector Pipe Figure 21 1 CAUTION THE STRUCTURAL INTEGRITY OF THE MOBILE HOME FLOOR WALL AND CEILING ROOF MUST BE MAI...

Page 22: ...22 June 18 2019 7059 800B HEATILATOR ECO CHOICE PS50 A Service Maintenance Log 8 Reference Materials Date of Service Performed By Description of Service...

Page 23: ...Wire 230 0810 Power Cord 812 1180 Y Thermostat Mechanical 812 3760 Y Paint Touch Up 3 42 19905 Hose Vacuum 5 32 Id 3 Ft SRV240 0450 Y Reset Button Assembly SRV7000 040 Baffle Center Back SRV7058 166...

Page 24: ...ate purchased installed _________________________________________________________________________ Serial Number ____________________________________ Location on appliance ___________________________ D...

Reviews: