Hearth & Home Heatilator Eco Choice PS50-C Installation Manual Download Page 14

14

June 18, 2019

7059-800B

HEATILATOR ECO-CHOICE PS50

C. Negative Pressure

Negative pressure results from the imbalance of air 

available for the appliance to operate properly. It can be 

strongest in lower levels of the house.

Causes include:

•  Exhaust fans (kitchen, bath, etc.)

•  Range hoods

•  Combustion air requirements for furnaces, water 

appliances and other combustion appliances

•  Clothes dryers

•  Location of return-air vents to furnace or air 

conditioning

•  Imbalances of the HVAC air handling system

• 

Upper level air leaks such as: 

 - Recessed lighting

 - Attic hatch

 - Duct leaks

To minimize the effects of negative air pressure:

•  Install the outside air kit with the intake facing prevailing 

winds during the heating season

•  Ensure adequate outdoor air for all combustion 

appliances and exhaust equipment

•  Ensure furnace and air conditioning return vents are 

not located in the immediate vicinity of the appliance

•  Avoid installing the appliance near doors, walkways or 

small isolated spaces

•  Recessed lighting should be a “sealed can” design

•  Attic hatches weather stripped or sealed

•  Attic mounted duct work and air handler joints and 

seams taped or sealed

WARNING

Risk of Asphyxiation! 

Negative pressure can cause spillage of combustion 

fumes and soot.

Hearth & Home Technologies assumes no responsibility 

for the improper performance of the chimney system 

caused by:

•  Inadequate draft due to environmental conditions

•  Down drafts

• 

Tight sealing construction of the structure

•  Mechanical exhausting devices

NOTICE

D. Draft 

Draft is the pressure difference needed to vent an 

appliance successfully. When an appliance is drafting 

successfully, all combustion byproducts are exiting the 

home through the chimney.

Install through the warm airspace enclosed by the building 

envelope. This helps to produce more draft, especially 

during lighting and die-down of the fire.

Considerations for successful draft include:

• 

Preventing negative pressure

•  Location of appliance and chimney

E. Chimney and Exhaust Connection 

1.  Chimney & Connector

:

  Use 3 or 4 inch (76-102mm)  

diameter type “L” or “PL” venting system.  It can be 

vented vertically or horizontally.

2.  Mobile Home: 

Approved for all Listed pellet vent.  If 

using the 3 inch (76mm) vertical Top Vent Adapter Kit 

or the 3 to 6 inch (76-152mm) Top Vent Offset Adapter, 

use Listed double wall flue connector.  A Quadra-Fire 

Outside Air Kit must be used with manufactured home 

installations.

3.  Residential: 

 The 3 inch (76mm) vertical Top Vent 

Adapter Kit and the 3 to 6 inch (76-152mm) Top Vent 

Offset Adapter are tested to use 24 gauge single wall 

flue connector or Listed double wall flue connector to 

Class A Listed metal chimneys, or masonry chimneys 

meeting International Residential Code standards for 

solid fuel appliances.

4.  INSTALL VENT AT CLEARANCES SPECIFIED BY THE 

VENT MANUFACTURER.

5.  Secure exhaust venting system to the appliance with 

at least 3 screws.  Also secure all connector pipe joints 

with at least 3 screws through each joint.

6.  DO NOT INSTALL A FLUE DAMPER IN THE 

EXHAUST VENTING SYSTEM OF THIS Appliance.

7. 

DO NOT CONNECT THIS Appliance TO A CHIMNEY 

FLUE SERVING ANOTHER APPLIANCE.

NOTE:

 If burning shelled field corn, you must use 

approved venting specifically designed for 

corn. Follow the instructions from the venting 

manufacturer.

NOTE:

 All pipe must be welded seam pipe whenever 

possible. Seal pipe joints with high temperature 

silicone (500°F [260°C] minimum rated only).

.075 inches W.C.

Minimum Vacuum Requirements per Appliance

Summary of Contents for Heatilator Eco Choice PS50-C

Page 1: ...ay cause house fire HOT SURFACES Glass and other surfaces are hot during operation AND cool down WARNING Hot glass will cause burns Do not touch glass until it is cooled NEVER allow children to touch...

Page 2: ...haust Connection 14 F Equivalent Feet of Pipe 15 G Pipe Selection Chart 15 5 Venting Systems 16 A Through The Wall 16 B Vertical into Existing Class A Chimney 17 C Vertical Interior Typical Installati...

Page 3: ...put 7 500 to 36 600 per hr BTU Input 13 100 to 49 900 per hr Vent Size 3 or 4 inches L or PL Hopper Capacity 83 lbs Fuel Premium Wood Pellets Weighted average LHV Low Heating Value efficiency using da...

Page 4: ...gnite and burn composed of any combination of the following Steel Plaster Brick Iron Concrete Tile Glass Slate Materials reported as passing ASTM E 136 Standard Test Method for Behavior of Metals in a...

Page 5: ...CAUTION If burning shelled field corn you must use approved venting specifically designed for corn to prevent corrosion or degradation Follow the instructions from the venting manufacturer NOTICE Chec...

Page 6: ...carefully during the installation to ensure maximum safety and benefit Follow pipe manufacturer instructions for installation and air clearance requirements Reciprocating Saw Channel Locks Hammer Phi...

Page 7: ...llation and copying this checklist for your file That this checklist remain visible at all times on the appliance until the installation is complete Electrical 120 VAC unswitched power provided to the...

Page 8: ...Top View Figure 8 3 Side View Figure 8 4 Side View with Top Vent Adapter 24 1 4 616 24 1 4 616 26 7 16 672 28 5 16 719 9 3 4 248 2 3 8 60 20 1 4 514 32 813 35 3 4 908 10 11 16 272 23 1 4 591 3 1 8 79...

Page 9: ...Installation Inches Millimeters D Back Wall to Adapter 1 25 E Side Wall to Appliance 14 356 F Back Wall to Appliance 6 1 4 159 Corner Installation Inches Millimeters G Walls to Appliance 2 51 Vertical...

Page 10: ...end 51mm beyond each side of pipe shaded area to the wall thimble 152mm Front of glass 348mm USA INSTALLATIONS A non combustible floor protection is recommended extending beneath the flue pipe when in...

Page 11: ...53 1346 n a n a C Depth n a n a 48 1219 D Side Wall 14 356 n a n a E Top 16 533 n a n a F Mantel Depth n a n a 36 914 Installations Into Alcove All minimums listed are to a combustible surface NOTE Il...

Page 12: ...pi ces d passant de la structure P 305 mm 12 po D gagements au dessus du toit pour les abat vents verticaux Tous les d gagements minimum correspondent une installation avec un ensemble de prise d air...

Page 13: ...emand House demand may consume the air needed for the appliance It may be necessary to add additional ventilation to the space in which the pellet appliance is located Consult with your local HVAC pro...

Page 14: ...combustion byproducts are exiting the home through the chimney Install through the warm airspace enclosed by the building envelope This helps to produce more draft especially during lighting and die...

Page 15: ...this installation Figure 15 2 1 Locate the calculated equivalent feet of pipe on the vertical left side of the chart 2 Move to the right horizontally on the chart until you reach your altitude above...

Page 16: ...oose which one is best for your installation 2 in 51mm Minimum 2 in 51mm Minimum 6 in 152mm Minimum 6 in 152mm Minimum Figure 16 2 5 Venting Systems NOTE In Canada where passage through a wall or part...

Page 17: ...installation instructions for all reduced air clearances installations B Vertical into Existing Class A Chimney Firestop Flashing Rain Cap 6 in 152mm Minimum Non combustible Hearth Pad 3 in 76mm Mini...

Page 18: ...Minimum Fireclay Flue Liner with Airspace Concrete Cap Non combustible Hearth Pad Airtight Clean Out Door Clean Out cover Sheathing 3 in 76mm Minimum 1 in 25mm Clearance Flashing Fireclay flue Liner...

Page 19: ...ters and hole saw or jig saw 1 Measure distance from floor to air vent opening in appliance and mark location on wall 2 Use a saw to cut opening in wall 2 inch kit Cut a 2 1 2 to 3 inch opening on ins...

Page 20: ...iate position 3 Install the vent pipe into the adapter be sure to silicone all joints Clean Out Cover Clean Out Cover Figure 20 2 Rear Vent Adapter Figure 20 3 Rear to Top Vent Adapter 90 D Thermostat...

Page 21: ...24 Spark Arestor Cap Roof Flashing Storm Collar Joist Shield Firestop Double Wall Connector Pipe Figure 21 1 CAUTION THE STRUCTURAL INTEGRITY OF THE MOBILE HOME FLOOR WALL AND CEILING ROOF MUST BE MAI...

Page 22: ...22 June 18 2019 7059 800B HEATILATOR ECO CHOICE PS50 A Service Maintenance Log 8 Reference Materials Date of Service Performed By Description of Service...

Page 23: ...Wire 230 0810 Power Cord 812 1180 Y Thermostat Mechanical 812 3760 Y Paint Touch Up 3 42 19905 Hose Vacuum 5 32 Id 3 Ft SRV240 0450 Y Reset Button Assembly SRV7000 040 Baffle Center Back SRV7058 166...

Page 24: ...ate purchased installed _________________________________________________________________________ Serial Number ____________________________________ Location on appliance ___________________________ D...

Reviews: