background image

Page 20

506746−01 05/12

Troubleshooting

Problem

Causes

Solutions

The humidifier does not turn on

1. No electrical power.
2. On/off switch of the humidifier in position O"

(OFF).

3. Control connectors improperly connected.
4. Power source failure; blown fuse; tripped

breaker.

5. Transformer failure.

1. Check the safety devices upstream from the humidifier and

the presence of power.

2. Close the switch on the panel: position I" (ON).
3. Check that connectors are properly inserted in terminal

block.

4. Check the power source; check condition of fuses; check

for tripped breaker.

5. Check for proper voltage across 24VAC and GND on

control. If no voltage present, replace controller.

The humidifier does not start
operation

1. Remote ON/OFF contact open.
2. The humidistat has not been connected

correctly.

3. Humidistat failure.
4. Control signal not compatible with the type set.
5. Value measured by the humidistat sensor(s)

higher than the corresponding RH set point.

6. Low conductivity water.

1. Close ON/OFF contacts.
2. Check the external connection.
3. Replace the humidistat.
4. Confirm for correct signal type for connected humidistat

using 

Selecting the signal type

 procedure on Page 17.

5. Using RH meter, confirm accuracy of RH sensor(s).
6. If 220−240 VAC humidifier, consider installing the Low

Conductivity cylinder (Y3484) listed on Page 23.

The humidifier fills with water
without producing steam

1. High steam back pressure.
2. Fill valve strainer clogged.
3. Mineral buildup in the fill cup.

1. Check that the steam hose is not kinked or sagging,

trapping condensate.

2. Clean the fill valve strainer.
3. Clean the fill cup.

The humidifier wets the duct

1. The steam nozzle is not installed correctly (too

near the top of the duct or the condensate return
is blocked).

2. Air flow rate is too low.
3. Humidifier active when the fan in the duct is off.

1. Check that the steam nozzle is installed correctly.
2. Increase air flow in duct or decrease maximum steam

production setting (see Page 17).

3. Check the connection of the device (flow switch or

differential pressure switch) controlling the humidifier to the
ventilation in the duct.

The humidifier wets the floor below 1. The humidifier drain is blocked.

2. The supply water or overflow circuit has leaks.
3. The condensate drain pipe does not bring the

water back to the drain pan.

4. The steam hose is not properly fastened to the

cylinder.

1. Clean the drain assembly and pan.
2. Check the entire water circuit.
3. Check the correct position of the condensate drain hose in

the drain pan.

4. Check the fastening of the hose clamps on the steam

outlet.

Water in the cylinder turns black

1. Minerals in the cylinder have over concentrated

and are deteriorating the electrodes.

1. Check for sags & kinks that could trap condensate in the

steam hoses that could cause a back pressure on the
cylinder.

2. Check the duct static pressure.
3. Check the fill valve and inlet strainer.
4. Check the drain pump operation.
5. Correct installation problems and replace cylinder.

Heavy arcing occurs within hours
of startup

1. The feed water contains large amounts of Iron,

Copper or other conductive contaminants.

1. If you are using a softener, discontinue use.
2. Check the electrodes in the cylinder to be sure they were

not damaged in shipping. Use a ohm−meter to check
whether they are short−circuited. Look through the steam
outlet to see whether the electrodes are loose.

Humidifier continuously fills and
drains without producing steam

1. Mineral has bridged between the electrodes.
2. There is back pressure from the steam hoses or

duct.

3. The flow regulator in the fill valve is broken or

out of place.

4. Water conductivity is very high.
5. Water is foaming excessively.

1. Perform cleaning cycles or replace the cylinder.
2. Check the steam hoses for kinks or gullies that might be

trapping condensate.

3. Replace the fill valve (stuck open).
4. Consider using a mix of demineralized water with raw

water.

5. Check cylinder − replace if exhausted.

Summary of Contents for HCSteam?16

Page 1: ...pping damage or missing components if found immediately report any discrepancies to the last carrier INSTALLATION INSTRUCTIONS HCSteam 16 35 Residential Healthy Climate Steam Humidifier INDOOR AIR QUA...

Page 2: ...through an electric fill valve Periodically based on the water quality the unit will also drain some water to di lute the build up of minerals in the steam generator This humidifier has been designed...

Page 3: ...cylinder A flow restrictor 4 prevents the unit from filling too quickly or with too much pressure The water flows up the fill tube 2 and into the fill cup 3 Water then flows over the dam in the fill c...

Page 4: ...hole mounting pattern and for connections to the humidifier and to the condensate drain Also see figure 6 for a typical installation diagram Drill a 2 1 4 57 mm hole in the ductwork at the selected lo...

Page 5: ...5 128 10 1 8 257 2 1 2 65 Dimensions in inches mm 1 7 8 48 2 3 4 70 2 1 8 54 3 8 9 17 5 8 448 3 7 8 98 1 1 2 38 2 3 8 60 2 3 8 60 23 5 8 600 3 5 8 92 5 8 16 3 1 4 82 1 3 8 35 2 dia 51 7 8 dia 23 1 5...

Page 6: ...rt to the negative pressure tap Check for closure of the switch when blower is turned on Plumbing Water characteristic requirements The humidifier must be supplied with water with the following charac...

Page 7: ...ILTER Recommended SUPPLY WATER EXTENSION TUBE SHUTOFF VALVE AND FILTER Recommended OPEN DRAIN DRAIN LINE Water inlet with filtering screen 3 4 hose con nection 1 1 4 Water drain STEAM HOSE ADAPTER FIL...

Page 8: ...jection The maximum allowed duct static pressure is 2 w c The HCSteam 16 35 humidifier include a plastic injection nozzle figure 7 CONDENSATE CONNECTION 2 1 2 63m 2 1 2 63m STEAM INLET O D 2 2 56mm dr...

Page 9: ...0 3 m TYPICAL INSTALLATION WHEN UNIT IS ABOVE THE STEAM NOZZLE 5 ft 1 5 M MAX 5 ft 1 5 M MAX IF NO SLOPE 3 9M MAX 20 5 10 ft 3M MAX 5ft 1 5 M MAX 20 5 GENTLE BEND OBSTRUCTION SUPPORTED STEAM HOSE AND...

Page 10: ...ct the ground wire to the unit s chassis ground lo cated just behind the power wiring terminal block see fig ure 11 C L1 L2 A B C SERVICE DISCONNECT STRAIN RELIEF L1 L2 GND GND WIRE NUT POWER CONTROL...

Page 11: ...a heating demand or thermostat blower demand When the indoor blower stops the air proving switch contacts will open SLP98 Furnace CBX40 Air Handler C NO Note 1 Do not connect H on CS7000 to H on furna...

Page 12: ...he thermo stat s humidity RH set point a demand message for humidification is sent to the HVAC unit control board S The demand message starts the indoor blower and sends a 24 volt signal from the H te...

Page 13: ...sent to the furnace control board S The demand message starts the indoor blower and closes the HUM contacts on the furnace control 24 VAC passes through a field installed jumper from the R terminal on...

Page 14: ...EXT FAN contacts open de energizing the blower interlock coil and stopping the indoor blower if not running due to a heating demand or thermostat blower demand When the indoor blower stops the air pr...

Page 15: ...rogramming port Connecting to Programming port or supervisor factory use only AB AB Remote enabling input Imposes an external NO contact Rmax 300 Ohm Vmax 33 Vdc Imax 6mAdc humidifier enabled contact...

Page 16: ...wired to close when air flow is proved S Hi limit humidistat if used is wired to open on humid ity rise above setpoint S Unit wires have been checked to make sure they and all connectors are tight fr...

Page 17: ...f 03 or higher not applicable for these models If value is higher than 02 press reset sel until the display goes back to the normal operating mode and re start from step 1 4 Press and hold drain mini...

Page 18: ...humidifier back on DO NOT release reset sel and drain buttons until the wrench icon blinks then re lease both buttons 3 Press reset sel until the display shows 03 DO NOT confirm any value higher than...

Page 19: ...y used for 2000 hrs Press reset sel key for 1 seconds to reset Off Change cylinder not urgent E4 Fill alarm unable or slow fill current does not increase within timeout Press reset sel key for 1 secon...

Page 20: ...rrectly 2 Increase air flow in duct or decrease maximum steam production setting see Page 17 3 Check the connection of the device flow switch or differential pressure switch controlling the humidifier...

Page 21: ...nd the general condition of the cylinder Check that during operation there is no arcing between the electrodes S Every three months or no more than 1000 operating hours Check operation that there are...

Page 22: ...the electrical connections from the top of the cylinder 7 Carefully remove cylinder from the pump manifold Make sure the O ring remains in the manifold see fig ure 26 8 Verify cylinder model voltage f...

Page 23: ...5 S Steam Nozzle Y3781 Table 6 Technical Specifications Steam flows VAC kW 5 5 lbs hr 2 5 kg h 110 120 VAC 1 phase 50 60 Hz 1 86 kW 12 lbs hr 5 4 kg h 220 240 VAC 1 phase 50 60 Hz 4 05 kW Notes Steam...

Page 24: ...Page 24 506746 01 05 12 070222075 rel 1 2 dated 25 05 2012...

Reviews: