background image

Page 13

HCSTEAM−16/−35 SERIES

SL280 ONLY

Note 1. Humidification must be added in icomfort Touch

®

thermostat during commissioning. Refer to icomfort
Touch

®

 Installer Guide for details.

Note 2. 48G96 relay field supplied.
Note 3. Remove factory jumper between AB−AB.

C
NO

48G96
Relay

Alarm
terminals
(if used)

(not
used)

(not
used)

(not
used)

Required Air Proving
Switch (provided)

NO

C

NC

C

NO

GND

24VAC

N2

GND

N1
AB
AB

GND

IN

Humidifier
low voltage
wiring panel

icomfort

t

 enabled 

outdoor unit

icomfort
Touch

®

thermostat

Figure 16. Humidifier with icomfort Touch

®

 thermostat used as humidistat with an icomfort

t

 en-

abled SL280 gas furnace

S

Humidification is controlled by the humidity sensor in the thermostat.

 When the humidity in the space falls below the thermo-

stat’s humidity RH set point, a demand message for humidification is sent to the furnace control board.

S

The demand message starts the indoor blower and closes the "HUM" contacts on the furnace control. 24 VAC passes through
a field−installed jumper from the "R" terminal on the control board, through the closed "HUM" terminals, and to the humidifier
isolation relay coil. The isolation relay contacts close to complete the circuit from "GND" and "IN" terminals on the humidifier
controller.

S

When the indoor blower achieves sufficient speed, the air proving switch contacts close completing the circuit from "AB" to
"AB" on the humidifier controller. Steam production will now start and continue until the humidity demand is satisfied.

S

When the RH set point is reached, the thermostat removes the demand to the furnace board which opens the HUM contacts,
opens the isolation relay circuit and, in turn, opens the circuit between "GND" and "IN" on the humidifier controller, stopping
steam production. The indoor blower will be turned off (if not running due to a heating demand or thermostat blower demand).

Summary of Contents for HCSteam?16

Page 1: ...pping damage or missing components if found immediately report any discrepancies to the last carrier INSTALLATION INSTRUCTIONS HCSteam 16 35 Residential Healthy Climate Steam Humidifier INDOOR AIR QUA...

Page 2: ...through an electric fill valve Periodically based on the water quality the unit will also drain some water to di lute the build up of minerals in the steam generator This humidifier has been designed...

Page 3: ...cylinder A flow restrictor 4 prevents the unit from filling too quickly or with too much pressure The water flows up the fill tube 2 and into the fill cup 3 Water then flows over the dam in the fill c...

Page 4: ...hole mounting pattern and for connections to the humidifier and to the condensate drain Also see figure 6 for a typical installation diagram Drill a 2 1 4 57 mm hole in the ductwork at the selected lo...

Page 5: ...5 128 10 1 8 257 2 1 2 65 Dimensions in inches mm 1 7 8 48 2 3 4 70 2 1 8 54 3 8 9 17 5 8 448 3 7 8 98 1 1 2 38 2 3 8 60 2 3 8 60 23 5 8 600 3 5 8 92 5 8 16 3 1 4 82 1 3 8 35 2 dia 51 7 8 dia 23 1 5...

Page 6: ...rt to the negative pressure tap Check for closure of the switch when blower is turned on Plumbing Water characteristic requirements The humidifier must be supplied with water with the following charac...

Page 7: ...ILTER Recommended SUPPLY WATER EXTENSION TUBE SHUTOFF VALVE AND FILTER Recommended OPEN DRAIN DRAIN LINE Water inlet with filtering screen 3 4 hose con nection 1 1 4 Water drain STEAM HOSE ADAPTER FIL...

Page 8: ...jection The maximum allowed duct static pressure is 2 w c The HCSteam 16 35 humidifier include a plastic injection nozzle figure 7 CONDENSATE CONNECTION 2 1 2 63m 2 1 2 63m STEAM INLET O D 2 2 56mm dr...

Page 9: ...0 3 m TYPICAL INSTALLATION WHEN UNIT IS ABOVE THE STEAM NOZZLE 5 ft 1 5 M MAX 5 ft 1 5 M MAX IF NO SLOPE 3 9M MAX 20 5 10 ft 3M MAX 5ft 1 5 M MAX 20 5 GENTLE BEND OBSTRUCTION SUPPORTED STEAM HOSE AND...

Page 10: ...ct the ground wire to the unit s chassis ground lo cated just behind the power wiring terminal block see fig ure 11 C L1 L2 A B C SERVICE DISCONNECT STRAIN RELIEF L1 L2 GND GND WIRE NUT POWER CONTROL...

Page 11: ...a heating demand or thermostat blower demand When the indoor blower stops the air proving switch contacts will open SLP98 Furnace CBX40 Air Handler C NO Note 1 Do not connect H on CS7000 to H on furna...

Page 12: ...he thermo stat s humidity RH set point a demand message for humidification is sent to the HVAC unit control board S The demand message starts the indoor blower and sends a 24 volt signal from the H te...

Page 13: ...sent to the furnace control board S The demand message starts the indoor blower and closes the HUM contacts on the furnace control 24 VAC passes through a field installed jumper from the R terminal on...

Page 14: ...EXT FAN contacts open de energizing the blower interlock coil and stopping the indoor blower if not running due to a heating demand or thermostat blower demand When the indoor blower stops the air pr...

Page 15: ...rogramming port Connecting to Programming port or supervisor factory use only AB AB Remote enabling input Imposes an external NO contact Rmax 300 Ohm Vmax 33 Vdc Imax 6mAdc humidifier enabled contact...

Page 16: ...wired to close when air flow is proved S Hi limit humidistat if used is wired to open on humid ity rise above setpoint S Unit wires have been checked to make sure they and all connectors are tight fr...

Page 17: ...f 03 or higher not applicable for these models If value is higher than 02 press reset sel until the display goes back to the normal operating mode and re start from step 1 4 Press and hold drain mini...

Page 18: ...humidifier back on DO NOT release reset sel and drain buttons until the wrench icon blinks then re lease both buttons 3 Press reset sel until the display shows 03 DO NOT confirm any value higher than...

Page 19: ...y used for 2000 hrs Press reset sel key for 1 seconds to reset Off Change cylinder not urgent E4 Fill alarm unable or slow fill current does not increase within timeout Press reset sel key for 1 secon...

Page 20: ...rrectly 2 Increase air flow in duct or decrease maximum steam production setting see Page 17 3 Check the connection of the device flow switch or differential pressure switch controlling the humidifier...

Page 21: ...nd the general condition of the cylinder Check that during operation there is no arcing between the electrodes S Every three months or no more than 1000 operating hours Check operation that there are...

Page 22: ...the electrical connections from the top of the cylinder 7 Carefully remove cylinder from the pump manifold Make sure the O ring remains in the manifold see fig ure 26 8 Verify cylinder model voltage f...

Page 23: ...5 S Steam Nozzle Y3781 Table 6 Technical Specifications Steam flows VAC kW 5 5 lbs hr 2 5 kg h 110 120 VAC 1 phase 50 60 Hz 1 86 kW 12 lbs hr 5 4 kg h 220 240 VAC 1 phase 50 60 Hz 4 05 kW Notes Steam...

Page 24: ...Page 24 506746 01 05 12 070222075 rel 1 2 dated 25 05 2012...

Reviews: