Page 33

Healthy Climate

® 

HRV/ERV Ventilators

Table 2. Airflow Balancing Reference HRV4−150

Speed 5 (factory setting)

Speed 4

Speed 3

Pressure Drop

Fresh Air

CFM

Stale Air

CFM

Pressure Drop

Fresh Air

CFM

Stale Air

CFM

Pressure Drop

Fresh Air

CFM

Stale Air

CFM

"w.g.

Pa

"w.g.

Pa

"w.g.

Pa

0.090

22

32

75

0.040

10

39

21

0.040

10

43

29

0.095

24

38

82

0.050

12

47

33

0.045

11

45

32

0.100

25

48

87

0.055

14

51

38

0.050

12

48

36

0.104

26

55

91

0.060

15

55

44

0.055

14

51

41

0.110

27

63

97

0.065

16

58

50

0.060

15

54

45

0.114

28

67

98

0.070

17

61

56

0.065

16

56

51

0.120

30

73

103

0.075

19

64

62

0.070

17

59

57

0.124

31

76

107

0.080

20

67

68

0.075

19

62

63

0.130

32

81

112

0.085

21

69

74

0.080

20

65

71

0.134

33

84

116

0.090

22

72

79

0.085

21

68

79

0.140

35

88

121

0.095

24

74

85

0.090

22

70

89

0.144

36

90

124

0.100

25

77

91

0.095

24

73

94

0.150

37

93

129

0.105

26

79

97

0.100

25

76

98

0.154

38

95

131

0.110

27

81

103

0.105

26

79

101

0.160

40

98

136

0.115

29

83

106

0.110

27

82

105

0.164

41

100

139

0.120

30

86

111

0.115

29

84

109

0.170

42

103

143

0.125

31

88

117

0.120

30

87

112

0.174

43

105

145

0.130

32

90

123

0.125

31

90

116

0.180

45

107

149

0.135

34

92

129

0.130

32

93

120

0.190

47

118

156

0.140

35

94

135

0.135

34

96

123

0.195

49

120

159

0.145

36

96

141

0.140

35

98

127

0.200

50

122

162

0.150

37

97

147

0.145

36

101

131

0.205

51

123

165

0.155

39

99

152

0.150

37

104

134

0.210

52

125

168

0.160

40

101

158

0.155

39

107

138

0.215

54

126

171

0.165

41

103

164

0.160

40

110

142

0.220

55

128

173

0.170

42

105

170

0.165

41

112

145

0.225

56

129

176

0.175

44

111

176

0.170

42

115

149

0.230

57

130

179

0.180

45

113

182

0.175

44

118

152

0.235

58

132

182

0.185

46

115

187

0.180

45

121

156

0.240

60

133

184

0.190

47

116

193

0.185

46

124

160

0.245

61

134

187

0.195

49

118

199

0.190

47

126

163

0.250

62

136

189

0.200

50

119

205

0.195

49

129

167

0.255

63

137

192

0.205

51

121

211

0.200

50

132

171

0.260

65

138

194

0.210

52

123

217

0.205

51

135

174

0.265

66

139

197

0.215

54

124

223

0.210

52

137

178

0.270

67

141

199

0.220

55

126

228

0.215

54

140

182

0.275

68

142

202

0.225

56

127

234

0.220

55

143

185

0.280

70

143

204

0.230

57

129

240

0.225

56

146

189

0.285

71

144

207

0.235

58

130

246

0.230

57

149

193

0.290

72

145

209

0.240

60

131

252

0.235

58

151

196

0.295

73

146

211

0.245

61

133

258

0.240

60

154

200

0.300

75

147

213

0.250

62

134

264

0.245

61

157

204

0.305

76

148

216

0.255

63

136

269

0.250

62

160

207

0.310

77

149

218

0.260

65

137

273

0.255

63

163

211

0.315

78

150

220

0.260

65

165

215

0.320

80

151

222

0.265

66

168

218

0.325

81

152

224

0.270

67

171

222

0.330

82

153

227

0.275

68

174

225

0.335

83

154

229

0.280

70

177

229

0.340

85

155

231

0.285

71

179

233

0.345

86

156

233

0.290

72

182

236

0.350

87

157

235

0.295

73

185

240

0.355

88

158

237

Refer to ˆInstaller Selectable High Speed
Settings˜ in this manual for more informa-
tion.

0.300

75

188

244

0.360

90

159

239

0.305

76

191

247

0.365

91

160

241

0.310

77

193

251

0.370

92

161

243

0.315

78

196

255

0.375

93

162

245

NOTE − Door port balancing on the HRV4−150 requires a Magnehelic Gauge with a scale of
0 to 0.50" w.c.

0.380

95

163

247

Summary of Contents for HEALTHY CLIMATE ERV3-150

Page 1: ...bly containing 2 Drain spout assemblies HRV units only 1 Drain tee HRV units only 4 Hanging straps 1 Installation manual 1 Warranty card 1 Wall mounted remote control General Information These instruc...

Page 2: ...sensible temperature and latent moisture heat from in coming fresh air to the stale air as it is being exhausted thus reducing the air conditioning load The ERV unit is not suitable for use in climate...

Page 3: ...116 CFM 55 L s 69 Sensible Efficiency 13 F 25 C 76 CFM 31 L s 73 65 CFM 30 L s 56 61 CFM 29 L s 68 65 CFM 31 L s 73 64 CFM 30 L s 72 112 CFM 53 L s 72 132 CFM 62 L s 70 N A N A Latent Efficiency 95 F...

Page 4: ...44 0 7 175 40 19 72 34 94 44 80 38 0 8 200 Speed 2 med low 0 1 25 62 29 87 41 127 60 115 54 170 79 73 34 112 53 0 2 50 81 38 81 38 54 25 74 35 116 55 107 50 163 76 67 31 107 50 0 3 75 70 33 70 33 42...

Page 5: ...TS HRV3 300 MODEL HRV3 195 MOTOR IS AT TOP BLOWER DEFROST DAMPER DEFROST AIR FROM INSIDE FILTER CONDENSATE DRAINS FRESH AIR TO INSIDE STALE AIR FROM INSIDE BLOWER FRESH AIR FROM OUT SIDE MOTOR SEE NOT...

Page 6: ...in ventilation for 15 minutes No remote device can override this defrost mode or se lected speed until the cycle is complete After the cycle is completed the HRV defaults to previous settings If the c...

Page 7: ...ed see page 28 or 31 to prevent negative pressure in structure Negative pressure can cause back drafting of combustion gases in other household appliances such as Gas Furnaces Oil Furnaces Hot Water H...

Page 8: ...ating season when outdoor temperatures are less than 59 F 15 C HRV controls include a dehumidistat function which can be set to achieve a dehumidification effect from the HRV dur ing the winter heatin...

Page 9: ...ow voltage wire UNIT ON OFF Control Press and release the ON OFF button ON indicator light illuminates press again to turn OFF Humidity Control Unit will produce a dehumidifying ef fect when outdoor h...

Page 10: ...se the UP DOWN arrows to adjust the Humidity Indi cator on the display screen to the number of degrees difference between your humidity measuring device Minus is indicated by flashing 4 Press MODE Dig...

Page 11: ...o 4 events per day 8 ARRIVE flashes Repeat steps 4 to 6 to program up to 4 events per day 9 SLEEP flashes Repeat steps 4 to 6 to program up to 4 events per day 10 Weekend letters SS flash Press SET Re...

Page 12: ...olding the SELECT button for 5 seconds Connect to 3 wire 20 gauge low voltage wire and is installed in a standard 2 x 4 electrical box 20 Minute Status Lights Select Button Figure 6 20 Minute Timer Y2...

Page 13: ...kept short and have as few bends or elbows as possible to maximize airflow Forty five degree elbows are preferred to 90 elbows Use Y tees instead of straight tees whenever possible All duct joints mu...

Page 14: ...cations S Unit is normally balanced on HIGH speed with the furnace blower ON S A minimum separation of 40 inches 1m is recommended between the two direct connections S The exhaust air connection shoul...

Page 15: ...blower to evenly distribute the fresh air throughout the house S The duct configuration may change depending on the HRV ERV model See specifications for your unit S Check local codes and authority hav...

Page 16: ...locating grilles if the floor is the only option available Areas such as under baseboard heaters will help to temper the air Optional inline duct heaters are available for mounting in the supply air...

Page 17: ...close to the out side wall where the weather hoods will be mounted If a basement area is not convenient or does not exist a utility or laundry room may be used Attic installations are not normally rec...

Page 18: ...ews Note This illustration of the unit may vary from the unit you are installing Step 3 Hook the bottom grommets of the straps through the S hooks Pull down vertically on the hand loops while lifting...

Page 19: ...to the two drain spouts Position the T fitting to point upward and connect the drain line Tape or fasten base to avoid any kinks This creates a trap which will hold some condensate and prevent odors...

Page 20: ...Exhaust Weatherhood Requirements Observe the following when installing the exhaust weatherhood 1 At least 6 2m from the ventilation air intake 2 At least 18 457mm above ground or above the depth of ex...

Page 21: ...cfm See Note Compatible with Dual Hood 0 3 0 4 0 5 HRV3 150 TPD 115 104 95 Yes HRV3 150 TPF 120 107 100 Yes HRV3 095 66 60 n a Yes HRV4 150 90 80 72 Yes HRV4 200 120 107 100 Yes HRV3 195 125 114 107...

Page 22: ...all using the 2 supplied screws and anchors 9 Attach the faceplate to the back plate detail B BE CAREFUL to correctly align the faceplate to avoid damaging the faceplate contact pins 10 Insert the Ope...

Page 23: ...etween 2 ON and 6 HI initiates high speed ventilation Dehumidistat A dry contact for a dehumidistat is connected between 2 ON and 10 BLK 1 2 3 4 5 6 7 8 9 10 LOW ED R YEL GRN HI COM NO NC BLK LOW SPEE...

Page 24: ...andler with a simplified return return installation and should be interlocked with a partially dedicated installation see figure 24 CAUTION Potential equipment malfunction or damage May require repair...

Page 25: ...e 25 Residential Wiring Diagram HRV3 095 HRV4 150 HRV4 200 HRV3 195 HRV3 300 ERV3 150 ERV3 200 THERMISTOR Not on all units TERMINAL BLOCK GROUNDED PLUG SEE DEFROST DETAIL BELOW SEE AUTO TRANS FORMER D...

Page 26: ...Page 26 12 12 Figure 26 Residential Wiring Diagram HRV3 150 TPD...

Page 27: ...Page 27 Healthy Climate HRV ERV Ventilators Figure 27 Residential Wiring Diagram HRV3 150 TPF...

Page 28: ...m the outside must equal the volume of air exhausted by the unit if the airflow is not properly balanced then 1 The HRV ERV unit may not operate at its maximum efficiency 2 A negative or positive air...

Page 29: ...ut of the branch of the Pi tot is connected to the low pressure or reference side of the gauge 4 Insert the Pitot tube into the duct pointing the tip into the airflow 5 For general balancing it is suf...

Page 30: ...itot tube a minimum of 18 from blower or elbows Place Pitot tube a minimum of 18 from blower or elbows Pitot tube Magnehelic Gauge High Pressure Side Low Pressure Side NOTE Duct connections will vary...

Page 31: ...nitiate power and operate the HRV on high speed Operate the forced air system on high speed if the HRV is connected to the forced air system 5 Measure Stale air Insert the 2 rubber fittings from the g...

Page 32: ...700 175 108 0 530 133 139 93 0 490 123 82 64 0 710 178 105 0 540 135 132 91 0 500 125 79 62 0 720 180 176 102 0 550 138 125 88 0 510 128 76 60 0 730 183 165 99 0 560 140 119 85 0 520 130 73 57 0 740 1...

Page 33: ...165 41 103 164 0 160 40 110 142 0 220 55 128 173 0 170 42 105 170 0 165 41 112 145 0 225 56 129 176 0 175 44 111 176 0 170 42 115 149 0 230 57 130 179 0 180 45 113 182 0 175 44 118 152 0 235 58 132 18...

Page 34: ...0 0 195 49 114 170 0 180 45 104 178 0 180 45 106 163 0 200 50 116 173 0 185 46 106 183 0 185 46 108 167 0 205 51 117 176 0 190 47 109 189 0 190 47 110 171 0 210 52 119 178 0 195 49 111 194 0 195 49 11...

Page 35: ...ED ON NO LED SYSTEM POWER ON Press ON OFF fan button Failed wall control LED OFF LED ON NONE Normal operation LOW SPEED FAN OFF FAN ON ON OFF LED status Wall control ON OFF LED flashes to indicate rev...

Page 36: ...Operational Flowchart 2 Failed HRV ERV controller NO YES NO Refer to interface operation instructions Fan may operate based on interface settings Interface control with ON OFF connected Jumper ON to R...

Page 37: ...ode damper closed to outdoor air 3 Recirculation mode is only available on recirculating defrost models HRV3 095 HRV3 150 TPD HRV4 150 HRV4 200 Dehumidistat Disable Four consecutive temperature readin...

Page 38: ...the home from an unvented or unheated crawl space Moisture remaining in washroom and or kitchen areas Condensation seems to form in the spring and fall seasons HRV ERV is set at too low a speed Set d...

Page 39: ...300 Y2144 ERV3 150 Y2138 ERV3 200 Y2139 Motor Capacitor Y5438 Y5438 Y2146 Y5436 Y5437 Y2145 Y2147 Y2145 Y2145 Blower Housing Set N A N A Y2149 Y5439 Y5439 Y2150 Y2150 Y2148 Y2148 Blower Wheel CW red...

Page 40: ...ck and white wire from cir cuit board leading to the motor and pull wires to re move from the electrical box 7 Remove assembly blower motor blower panel by sliding left and down To Assemble Blower Ass...

Page 41: ...ishwasher pressure wash F Install clean filters G Wipe down the inside of the cabinet with a damp cloth to remove dirt bugs and any debris 4 Install clean core as follows A Install the bottom flange o...

Page 42: ...nit Recommended Arid Zone Dry Climate HRV Unit Required ERV unit not recommended where temperatures fall below 25 F 4 C continuously for more than 5 days ERV units are recommended in regions where hig...