31
10.
Attach the face plate to the back plate (Figure 34, Boxes
B or C).
NOTE: Be careful to correctly align the face plate to avoid
damaging the face plate contact pins.
11.
For the Digital 5-Speed / 5-Mode Control, insert the
instructions card into the control (Figure 34, Box A).
12.
Connect the 3-wire 20 gauge (minimum) 100 feet (30-
1/2 meters) length (maximum to the terminal block
located on ventilator (Red #3, Yellow #4 and Green #5).
Installation and Operation of H/C Ventilation
Wireless Timers (Y8251)
NOTE: Wireless timers can only be used with wall mounted
H/C ERV/HRV Ventilation Push Button Control
(Y8249) or H/C ERV/HRV Deluxe Ventilation
Control (Y8250).
The wireless timers may be installed onto a flush mounted
electrical switch box or it may be surface mounted onto a
wall. Multiple wireless timers (maximum six timers) may be
installed in a ventilation system.
To increase the range of a wireless timer, a H/C Ventilation
Wireless Repeater (Y8252) should be used.
PAIRING
1.
Turn on the main wall control by pressing the ON/OFF
button
and remove the battery from Timer.
2.
Pairing
Wireless 20/40/60 Minute Timer with Digital
5-Speed / 5-Mode Control
: Press the left and right
buttons simultaneously on the main wall control
and RESET buttons). The screen will go blank and the
wireless symbol
appear flashing on the bottom right
of the display. This indicates that the main control is
now in pairing mode (Figure 35, Box D).
3.
Pairing
Wireless 20/40/60 Minute Timer with Wall
Mount Dehumidistat/Ventilation Control:
Press the
left and right buttons simultaneously on the main wall
control
and either
or
buttons, depending on
the main control). The bottom row of three LEDs will
begin flashing. This indicates that the main control is
now in pairing mode (Figure 35, Box E).
4.
Keep the timer within 16” (406 mm) of the main wall
control when pairing.
5.
Install the battery in the wireless timer. All four lights on
the Timer will immediately flash five times, then only
the red battery light will remain on for approximately 12
seconds after which the
40
light flashes the rev code.
20, 40, 60 lights will flash until paired or will stop if not
paired within 12 seconds. If pairing was not successful
you now must return to step 1 to restart the pairing
process.
6.
Press the button on the main wall control to exit pairing
mode when wireless timers have been successfully
paired.
To pair additional wireless timers with the same wall control,
or if pairing was not successful, repeat steps 1-6.
When paired, the wireless timers can be moved and in-
stalled elsewhere.
Estimated range of the wireless timer is 40’ with no obstruc-
tions. A ventilation wireless repeater may be installed to in-
crease the range of the wireless timers.
Test if pairing was successful by pressing the Select but-
ton and listen for the ERV/HRV to initiate HIGH fan speed
ventilation.
UN-PAIRING
1.
Remove the battery from the back of the wireless timer.
2.
Press and hold the Select button on the front of the
Timer.
3.
While holding the Select
Button
, reinsert the battery in
the Timer. Continue holding the select button until the
LED under
40
begins flashing. The wireless timer will
now be unpaired with the main wall control.
INSTALLATION
1.
Separate the face plate from the back plate by firmly
pulling apart (Figure 35, Box A).
2.
For mounting the control without a decorative plate,
break off top and bottom tabs and refer to Figure 35,
Box C for mounting.
BOX A
BOX B
1/8” (3 mm) hole
for screw and
anchor
1/8” (3 mm) hole
for screw and
anchor
BOX C (ALTERNATE WALL MOUNT)
1/8” (3 mm) hole
for screw and anchor
Break off tab
1/8” (3 mm) hole
for screw and anchor
Break off tab
BOX D
BOX E
BOX F
Figure 35. Wireless Timer Installation