The evc/epc can be controlled by messages received over the SAE J1939 Bus.
The EEC1 (PGN: 61444 SA: 0) engine RPM (SPN: 190) can be monitored for use in anti-stall and closed
loop operations.
The proprietary J1939 Command Message (PGN: 65281 through 65407 SA: 34) can be monitored for
Coil A, Coil B and RPM Setpoints for various operation modes. This address is adjusted based on the
Module ID. The relationship of the Module ID and the Command Message address is defined in a chart at
the end of this section.
The evc/epc can transmit its status over the SAE J1939 Bus.
The proprietary J1939 Status Message (PGN: 65409 through 65535 SA: 34) is a multiplexed message
with the first data byte indicating message 1 Status or message 2 Analog Values. This address is
adjusted based on the Module ID. The relationship of the Module ID and the Status Message address is
defined in a chart at the end of this section. When the J1939 Command Message is enabled, the Status
Message will be transmitted. If Report Analog Values is enabled on the J1939 tab, the Analog Values will
be transmitted. The content of the Status and Analog Values messages are detailed below.
Command Message Format
Transmission Repetition
40mS
Data Length
8
Data Page
1
PDU Format
255
PDU Specific
Module ID #
Priority N/A
Parameter Group Number
65281 Through 65407
(FF01 Through FF7F)
Start Position
Length
Parameter Name
1
1 Byte
Always = 1
2-3
2 Bytes
Coil A Set point
4-5
2 Bytes
Coil B Set point
6-7
2 Bytes
RPM Set point