3) SLAB SETTINGS
SETUP MENU
1) SNOW RATE SETUP
2) DESIGN TEMPS
3) SLAB SETUP
4) SYSTEM SETUP
5) TESTING
6) WIFI
SLAB SETUP
1) IDLE TEMP
2) MELT TEMP
3) MELT TIME
4) SENSOR LOC
20
°F
50
°F
3
H
INT
SLAB SETUP
1) IDLE TEMP
2) MELT TEMP
3) MELT TIME
4) SENSOR LOC
20
°F
50
°F
3
H
INT
SLAB SETUP
1) IDLE TEMP
2) MELT TEMP
3) MELT TIME
4) SENSOR LOC
20
°F
50
°F
3
H
INT
SLAB SETUP
1) IDLE TEMP
2) MELT TEMP
3) MELT TIME
4) SENSOR LOC
20
°F
50
°F
3
H
INT
SETUP MENU
1) SNOW RATE SETUP
2) DESIGN TEMPS
3) SLAB SETUP
4) SYSTEM SETUP
5) TESTING
6) WIFI
SLAB SETUP
1) IDLE TEMP
2) MELT TEMP
3) MELT TIME
4) SENSOR LOC
20
°F
50
°F
3
H
INT
SLAB SETUP
1) IDLE TEMP
2) MELT TEMP
3) MELT TIME
4) SENSOR LOC
20
°F
50
°F
3
H
INT
SLAB SETUP
1) IDLE TEMP
2) MELT TEMP
3) MELT TIME
4) SENSOR LOC
20
°F
50
°F
3
H
INT
SLAB SETUP
1) IDLE TEMP
2) MELT TEMP
3) MELT TIME
4) SENSOR LOC
20
°F
50
°F
3
H
INT
SETUP MENU
1) SNOW RATE SETUP
2) DESIGN TEMPS
3) SLAB SETUP
4) SYSTEM SETUP
5) TESTING
6) WIFI
SLAB SETUP
1) IDLE TEMP
2) MELT TEMP
3) MELT TIME
4) SENSOR LOC
20
°F
50
°F
3
H
INT
SLAB SETUP
1) IDLE TEMP
2) MELT TEMP
3) MELT TIME
4) SENSOR LOC
20
°F
50
°F
3
H
INT
SLAB SETUP
1) IDLE TEMP
2) MELT TEMP
3) MELT TIME
4) SENSOR LOC
20
°F
50
°F
3
H
INT
SLAB SETUP
1) IDLE TEMP
2) MELT TEMP
3) MELT TIME
4) SENSOR LOC
20
°F
50
°F
3
H
INT
SETUP MENU
1) SNOW RATE SETUP
2) DESIGN TEMPS
3) SLAB SETUP
4) SYSTEM SETUP
5) TESTING
6) WIFI
SLAB SETUP
1) IDLE TEMP
2) MELT TEMP
3) MELT TIME
4) SENSOR LOC
20
°F
50
°F
3
H
INT
SLAB SETUP
1) IDLE TEMP
2) MELT TEMP
3) MELT TIME
4) SENSOR LOC
20
°F
50
°F
3
H
INT
SLAB SETUP
1) IDLE TEMP
2) MELT TEMP
3) MELT TIME
4) SENSOR LOC
20
°F
50
°F
3
H
INT
SLAB SETUP
1) IDLE TEMP
2) MELT TEMP
3) MELT TIME
4) SENSOR LOC
20
°F
50
°F
3
H
INT
SETUP MENU
1) SNOW RATE SETUP
2) DESIGN TEMPS
3) SLAB SETUP
4) SYSTEM SETUP
5) TESTING
6) WIFI
SLAB SETUP
1) IDLE TEMP
2) MELT TEMP
3) MELT TIME
4) SENSOR LOC
20
°F
50
°F
3
H
INT
SLAB SETUP
1) IDLE TEMP
2) MELT TEMP
3) MELT TIME
4) SENSOR LOC
20
°F
50
°F
3
H
INT
SLAB SETUP
1) IDLE TEMP
2) MELT TEMP
3) MELT TIME
4) SENSOR LOC
20
°F
50
°F
3
H
INT
SLAB SETUP
1) IDLE TEMP
2) MELT TEMP
3) MELT TIME
4) SENSOR LOC
20
°F
50
°F
3
H
INT
SLAB SETUP
Idle Temperature
This is the slab setpoint when there is no snowfall present, and the control is operating
between the WWSD and CWSD parameters.
(
-39°F to 80°F
) Default:
20°F
To turn Idle Temperature OFF, set temperature below -39 °F or above 80 °F.
Melt Temperature
This is the slab setpoint when there is a snowfall detected by the optical sensor, or is
manually put into a Forced Melt.
(
20°F to 100°F
) Default:
50°F
Melt Time
This setting allows for the system to stay on even after no snow is present. This will melt
any residual snow that has accumulated and not melted. This time is also used when
a force melt demand is given. Once a force melt demand is given the control will
stay in
MELT
mode for this amount of time.
(
1H to 99H
) Default:
3H
Sensor Location
Set this to
INT
when the Snow/ Ice Optical Sensor is mounted in-slab, or set to
REM
when mounted remotely.
(
INT or REM
) Default:
INT
Slab Setup
This setting is used to configure your slab options.