4.5 Water flow setting
While the heat pump is running and the water inlet and outlet valves are open,
adjust the by-pass valve to obtain a difference of 2°C between the water
inflow and outflow temperature (see functional diagram
§3.1
).
You can check the setting by viewing the inflow and outflow temperatures
directly on the control panel by following the procedure below.
Then adjust the by-pass to obtain a difference of 2°C between the inflow and
the outflow.
Press
once to exit the menu.
• Opening the bypass valve results in a lower flow in the heat pump’s
exchanger, leading to an increase in the inflow/outflow temperature
difference.
• Closing the bypass valve results in a higher flow in the heat pump’s
exchanger, leading to a decrease in the inflow/outflow temperature
difference.
You can check the setting by viewing the inflow/outflow
temperatures (1-2) directly in the “
EyesPool Inverter
Connect
” app (see
§4.6
).
1
2
Inflow
temperature
Outflow
temperature
4. USER INTERFACE (continued)
10 s
5 s
Summary of Contents for AccessLine HP3051DT3HM
Page 2: ......
Page 3: ...POMPE A CHALEUR POUR PISCINE Manuel d instructions et d installation ISHP3XX1DT3HM RevB ...
Page 34: ...Page laissée blanche intentionnellement ...
Page 35: ...SWIMMING POOL HEAT PUMP UNIT Installation Instruction Manual ISHP3XX1DT3HM RevB ...
Page 66: ...Page left intentionally blank ...
Page 98: ...Página en blanco intencionalmente ...
Page 99: ...BOMBA DE AQUECIMENTO PARA PISCINAS Manual de instalação e de instruções ISHP3XX1DT3HM RevB ...
Page 130: ...Página deixada em branco intencionalmente ...
Page 131: ...HEIZPUMPENANLAGE FÜR EIN SCHWIMMBECKEN Einbau Anleitungshandbuch ISHP3XX1DT3HM RevB ...
Page 162: ...Seite bewusst leer gelassen ...
Page 163: ...ZWEMBAD WARMTEPOMP Installatie en bedieningshandleiding ISHP3XX1DT3HM RevB ...
Page 194: ...Opzettelijk leeg gelaten pagina ...