NOTE:
A Class A ground-fault circuit interrupter
(GFCI) shall be installed in the branch-circuit
supplying power to this unit.
CAUTION!
Prior to making any electrical
connections, verify with a voltmeter that power
from the service panel is
off.
SHOULD YOU EXPERIENCE DIFFICULTY WITH THE INSTALLATION OF THIS
MODEL, OR REQUIRE REPLACEMENT PARTS, PLEASE CALL:
TECHNICAL SUPPORT:
1-800-766-5612
HOURS OF OPERATION: MON-THURS 7:00a.m. - 4:30p.m PT, FRI 7:00a.m.- 11:00a.m. PT
PARTS LIST:
1 Bottle Filler, 1 filter cartridge, 1 plastic drain basin, 1 hex key, 1 grommet.
RECOMMENDED TOOLS:
Phillips screwdrivers, level.
REQUIRED PARTS (NOT SUPPLIED):
1/2” screwdriver stop, 3/8” tubing (to be used for water
supply inlet), 6 1/8” x 3” zinc-plated steel toggle bolts, 6 zinc-plated steel 1/8” fender washers.
PRODUCT INSTALLATION:
When installing this product, local, state or federal codes should be
adhered to. This unit is certified for indoor use only.
SUPPLY LINE:
Minimum recommended line size is 1/2" IPS with 30-90 PSI (2-6 ATM) flowing
pressure; supply water is to be cold water supply. Intended for municipal water only.
PLUMBING CONNECTIONS:
Inlet is 3/8” O.D. push-in type fitting. If a waste is desired, the Haws
6470 retrofit 1-1/4” O.D. waste kit may be used.
ELECTRICAL CONNECTIONS:
115VAC, 60HZ, approx. 0.14A. Unit is equipped with a standard
115VAC plug.
RATED SERVICE FLOW:
0.5 GPM (2725L/day)
OPERATING TEMPERATURE:
35–100
°
F (1.7–37.8
°
C)
OPERATING PRESSURE:
30-90 PSI
FILTER CAPACITY:
2500 gallons (9460L) or 1 year
REPLACEMENT FILTER CARTRIDGE
: Electronic Lifecycle Control Filter Model 6423