![Hawk Intelligent 2000 Series Instruction Manual Download Page 18](http://html1.mh-extra.com/html/hawk/intelligent-2000-series/intelligent-2000-series_instruction-manual_2109377018.webp)
18
Overview
Linearisation Vertical Tank With Cone
1. Push [PROG] till “100” appears on the display.
2. Push
h
/ SPAN 11 times until “111” appears. (Confirm with [PROG])
3. Push
h
twice. (Confirm with [PROG])
4. Enter height (H1) of the tank (= actual level).
(Confirm with [PROG]).
5. Enter diameter (D) of tank. (Confirm with [PROG])
6. Enter height (H2) of cone. (Confirm with [PROG])
7. Enter the height (H3) from the bottom of the tank to the topside
of the diaphragm (or weld-on nipple). (Confirm with [PROG]).
8. Enter the percentage of the actual “full” level (for example 80%).
(Confirm with [PROG]).
Linearisation Vertical Tank With Spherical Cone
(From Software Revision 3)
1. Push [PROG] till “100” appears on the display.
2. Push
h
/ SPAN 11 times until “111” appears. (Confirm with [PROG])
3. Push
h
three times. (Confirm with [PROG])
4. Enter height (H1) of the tank (= actual level).
(Confirm with [PROG]).
5. Enter diameter (D) of tank. (Confirm with [PROG])
6. Enter height (H2) of cone. (Confirm with [PROG])
7. Enter the height (H3) from the bottom of the tank to the topside
of the diaphragm (or weld-on nipple). (Confirm with [PROG]).
8. Enter the percentage of the actual “full” level (for example 80%).
(Confirm with [PROG]).
Note
When the specific gravity of the fluid is unequal to 1 and you do not want to use option 4, you must take care of it by defining the
calibration of the transmitter.
Calibration (see P102) = Height of the level x Specific Gravity.
Series 2000 HART
Linearization horizontal tank (Elliptical)
1. Push [PROG] until “100” is shown on the display.
2. Push
h
/ SPAN 11 times until “111” appears. (Confirm with [PROG])
3. Push
h
once. (Confirm with [PROG])
4. Enter the height (H1) of the tank in meters. (Confirm with [PROG])
5. Enter the height (H2) of the tank in meters. (Confirm with [PROG])
6. Enter the length (L) of the tank. For a “ball” or cone shaped tank,
take the cylindrical length plus the length of 1 “ball” cone. (Confirm
with [PROG])
7. Enter H3 in meters if the transmitter is installed like in the
left picture. Enter 0m when the transmitter is installed like
in the right picture.
8. Enter the percentage of the actual “full” level (for example
80%). (Confirm with [PROG]).