HAUTAU LZ 908 Installation And Operating Instructions Manual Download Page 18

18

Function test

Check if the central unit functions properly after successfully 

installing all components (fire pushbuttons, smoke or heat 

detector, drives, ventilation pushbuttons, etc).
-  Switch the 230 V AC power supply on and slip on the 

battery packs.

- The green LED on LAD 9 is lit.
- All other modules must show only green LEDs.
-  Push the alarm button (red) on the fire pushbuttons to turn 

the system on. The red LEDs in the fire pushbutton and on 

the RWA 9 are lit.

-  Check if all windows of the corresponding fire group are 

opened all the way. Afterwards, close the windows by 

pressing the RESET button (black) in the fire pushbutton. 

-  Use a smoke detector test control unit to trigger the 

smoke detector; the (red) LED on the RM 9 will be lit, and 

the windows will open.

-  When using test gas for checking the smoke detectors, 

you must press and hold the RESET button on the RWA 9 

module or the fire pushbutton for 10 seconds in order to 

set the RM 523 smoke detector to revision mode.

-  Check the ventilation pushbuttons by pressing the OPEN, 

STOP, and CLOSE buttons.

-  Switch off the 230 V AC mains supply; the green LEDs will 

turn off, and the yellow malfunction LEDs will start flashing 

in the event of a malfunction.

Elimination of fault

functions

Green display LEDs on the load module are not lit

Error source: 

- 230 V AC mains supply not connected 

- Mains fuse switched off 

- Connection to battery packs is not established

Error message “Mains / battery fault“ does not appear

- monitoring takes place cyclically approx. every 25 minutes

- it is necessary to wait for the appropriate time

Displays on SHEV module - yellow LED is lit/flashes –

Error source:

- Malfunction in the area of the fire pushbutton 

-  Break or short circuit in wire SHEV “OPEN” or “CLOSE”; 

red LED is lit

- Alarm was triggered

Displays on smoke detector module – red LED is lit

Error source:

-  A smoke detector in this group was triggered, green LED 

is not lit

- 10K terminal resistor not installed in smoke detector 

- Break or short circuit in smoke detector wire
- System runs on emergency power

Display in group control module – yellow LED is 

lit or flashing

Error source:

- Cable break in the area of the motor lines  

- EMERGENCY STOP button pressed 

- Fuse on module defective

Display in wind/rain module – red LED is lit

Error source:

- The wind sensor has triggered a wind alarm 

- The rain sensor was triggered

Displays in potential-free output module – green LEDs 

are lit

Error source:

-  The relays have been actuated by the signals issued by 

the smoke and heat exhaust ventilation or ventilation bus

Displays in potential-free input module – green LEDs 

are lit

Error source:

-  The relays on the module have been actuated by the 

signals issued by external devices

Care

Check all devices and cable connections for external 

damage and dirt. The operability of smoke outlets, central 

control units, fire pushbuttons, ventilation pushbuttons, etc. 

must not be affected by, for example, structural measures 

or stored goods.

Maintenance

Smoke and heat exhaust ventilation systems must be 

serviced at least once a year by a company specialised in 

smoke and heat exhaust ventilation and in accordance with 

all statutory regulations (building code and state building 

regulations).
To guarantee a reliable emergency power supply, have the 

used battery packs checked and, if necessary, replaced on 

a regular basis. The battery packs must be replaced no later 

than every 4 years. Dispose of the battery packs properly as 

required by all applicable legal regulations.
The inspection plate on the central unit must be renewed, 

and a control book must be kept.
We recommend that you conclude a service contract.

Maintenance

If components have to be checked, repaired or replaced, 

please contact the manufacturer. Use only original spare parts. 

Modifications of connections are permitted only within the limits 

of the connection options.

Disposal

Dispose of this product, when it has reached  

the end of its service life, in accordance with  

the provisions of the Electrical and Electronic 

Equipment Act.

Before working on electrically powered windows and dome 

lights, make sure to set them to the desired  position. They 

must be disconnected via isolating link at all poles and 

safeguarded against unintentional re-starting. The  isolating 

link must be clearly marked. This step allows you to 

 disable the ventilation function while performing work on 

the windows.Observe the maintenance and operating 

 regulations for power-controlled windows, doors, and gates.

CAUTION:

Summary of Contents for LZ 908

Page 1: ...stage of the groups is identified by the designation RAZ 908 Its basic configuration consists of a housing with screw plate as well as a top hat rail a transformer a rectifier module with filter capa...

Page 2: ...e live During service maintenance work at the unit the supply voltage has to be disconnected via isolating link at all poles Protect the system against unintentional re starting The isolating link mus...

Page 3: ...electric power lines follow VDE regu lations In any case the wiring type must be coordinated with the responsible authority fire department T V fire protection authority etc All maximum wire lengths...

Page 4: ...functions for SHEV and ventilation 4 Wind transmitter WG H 10 rain sensor REM H 10 WREM H 10 for automatic closing of windows top hung windows and light domes in case of rain and or wind 5 Conduit box...

Page 5: ...000 1000 300 1196 2 7 956 3 56 7 3 1000 1000 300 1118 3 7 956 4 56 7 4 1000 1000 300 1040 4 7 956 5 56 7 5 1000 1000 300 962 5 7 956 6 56 7 6 1000 1000 300 884 6 7 956 7 56 7 7 1000 1000 300 806 7 7 9...

Page 6: ...ety equipment for smoke removal or smoke control perform wiring in accor dance with the functional integrity classes E30 or E90 of the Model Wiring Guideline MLAR Security systems need line monitoring...

Page 7: ...l diagram The transformer connector is slipped on via cable lugs The central unit is overload and reverse battery protected A short circuit at the and terminals of the 24 V DC feed lines in the contro...

Page 8: ...age supply to the ventilation control system in case of a mains voltage failure The sensor at the end of the PTC cable is positioned close to the battery back see image while the other end is connecte...

Page 9: ...The group control module is used to control the motors monitor the motor lines for cable break and include an EMERGENCY STOP function for power controlled windows in the event of an emergency Technic...

Page 10: ...ese EMERGENCY STOP pushbuttons must comply with standard DIN EN 60204 The devices used to protect against crushing hazards and the EMERGENCY STOP button used as an opener are connect ed in series and...

Page 11: ...in the area of the fire pushbutton In case of emergency power operation the yellow ERROR LED 8 will flash The red ALARM LED 9 will be lit when the OPEN signal is active on the smoke and heat exhaust v...

Page 12: ...nitored for disruptions and short circuits Another option is to connect a central fire alarm system which however requires that only smoke detectors or only one central fire alarm system be connected...

Page 13: ...wind rain alarm is reset after a certain switch off delay The signal issued by the rain sensor is transferred to the internal bus To adjust the set point of the wind rain module slip on the jumper 3 a...

Page 14: ...r external devices The fuse 4 is used to protect the voltage supply circuit which is switched off in the event of a mains failure The module output is connected via 3 pin connectors 5 6 Jumpers 2 can...

Page 15: ...ange over module PFW 9 Works in the same way as PFA 9 but its output contacts are designed for 230 V AC Technical specifications Overview of the major components and modules cont Description The poten...

Page 16: ...TA 3 1 24 V DC Synchronous drives with exter nal synchronisation SYN 2K Sync drives Sync drives Sync drives Sync drives Synchronous drives with additional locking and external synchronous sequence SF...

Page 17: ...g Follow the terminal diagram to connect the battery pack wire To prevent dangerous gases from developing and to ensure the central control unit remains operational for 72 hrs in case of a mains failu...

Page 18: ...of the motor lines EMERGENCY STOP button pressed Fuse on module defective Display in wind rain module red LED is lit Error source The wind sensor has triggered a wind alarm The rain sensor was trigger...

Page 19: ...reversal of polarity yes approx 2 s Pulsing according to prEN 12101 9 yes every 2 min Automatic clearing no Line monitoring yes up to the last conduit box by monitoring diodes with 3rd line Connection...

Page 20: ...HAUTAU GmbH Wilhelm Hautau Str 2 31689 Helpsen Germany Tel 49 5724 393 0 info hautau de www hautau de...

Reviews: