HAUTAU LZ 908 Installation And Operating Instructions Manual Download Page 10

10

Diode

Diode

STOP 1

optional

LTB

LTB

RB

RB

LB

LB

- - + +

Motor

L-Zeit

GS 9

1

2

3

4

1

2

3

RESET

0,5

~ 4

1,0

~ 11

1,5

~ 17

2,0

~ 23

2,5

~ 29

3,0

~ 35

3,5

~ 42

4,0

~ 49

4,5

~ 54

5,0

~ 61

The group control module GS 9 is used to contr

ol drives.  

The signals iss

ued by the smoke and heat exhaust  ventilation 

bus 

6

 are given the highest priority. The signals issued by 

the ventilation bus 

5

 are given the second highest priority. 

The signals issued by the ventilation pushbutton bus 

7

 are 

given the lowest priority.
If an SHEV OPEN command is given, the motor output will 

be switched to OPEN again every 2 minutes for a duration of 

30 minutes.
The motors are connected to a 3-pin plug-in terminal 

1

The terminal 3 of this plug-in terminal is intended to monitor for 

cable break and trigger an EMERGENCY STOP.
The motor output is protected by a fuse which is integrated into 

the guard circuit.
Cable break in the area of the motor lines and EMERGENCY 

STOP operation is indicated by a yellow LED 

(which flashes 

during emergency stop operation).
A potentiometer 

3

 can be used to change the operating mode 

of the module:
- When the potentiometer is set to zero, the operating mode of 

the ventilation pushbutton is “OPEN-STOP-CLOSE”,
- A different potentiometer position means operating mode 

“OPEN-CLOSE”.
The set voltage value determines the time during which the 

drives will be moving towards the “OPEN” position. The STOP 

button is without function when the timer is switched on. The 

running period does not interfere with the smoke and heat 

exhaust ventilation functionality.
The running period voltage is measured at the contacts 

9

The voltage values are assigned to the following running 

periods in “ON” direction:

To ensure observance of guideline ZH1/494, install EMERGEN-

CY STOP pushbuttons on windows that are less than 2.5 m in 

height. The design of these EMERGENCY STOP pushbuttons 

must comply with standard DIN EN 60204.
The devices used to protect against crushing hazards and the 

EMERGENCY STOP button used as an “opener” are connect-

ed in series and integrated into the motor guard circuit (see 

drawing). When combined with the GS 9 module, they provide 

the following functions:
- If the direction in the module is switched to “OPEN”, the 

disruption of line 3 is only defined as a “malfunction” in the 

central control unit.

- If the direction “CLOSE” is switched as a ventilation function 

(includes ventilation pushbutton, superordinate ventilation, 

wind/rain sensor, delayed smoke and heat exhaust venti-

lation reset) and wire 3 is interrupted (equal to actuation of 

EMERGENCY STOP pushbutton), the GS 9 module will trigger 

an internal malfunction. The drives in this group will be stopped, 

while the internal malfunction remains active and is indicated 

in the fire pushbutton as well as on the module. Actuating 

the module in “OPEN” direction will reset the error message 

mentioned above and allow the drive to move again during the 

next “CLOSE” operation.
Pressing and holding the “Reset” button in the fire pushbutton 

will disable the EMERGENCY STOP functi

on.  

Releasing the reset button will enable the EMERGENCY 

FUNCTION again.

If a connected timer is switched on, the ventilation function 

will be blocked after an emergency stop has been triggered. 

Pressing the reset button in the fire pushbutton or on the RWA 

9 module of the central control unit will enable the ventilation 

function again.
An additional reset button is installed on the smoke and heat 

exhaust ventilation bus of the group module in the central 

ventilation units LZ 9 to reset the EMERGENCY STOP function 

manually (see drawing below). In the event of an EMERGENCY 

STOP, the control unit must be reset by issuing an “OPEN” or a 

reset command (in combination with a timer).

Overview of the major components and modules (cont.)

Voltage [V]

Time [s]

L-pushbutton

Malfunction

Reset button in an LZ9 .. 

Central ventilation unit

Drive

Summary of Contents for LZ 908

Page 1: ...stage of the groups is identified by the designation RAZ 908 Its basic configuration consists of a housing with screw plate as well as a top hat rail a transformer a rectifier module with filter capa...

Page 2: ...e live During service maintenance work at the unit the supply voltage has to be disconnected via isolating link at all poles Protect the system against unintentional re starting The isolating link mus...

Page 3: ...electric power lines follow VDE regu lations In any case the wiring type must be coordinated with the responsible authority fire department T V fire protection authority etc All maximum wire lengths...

Page 4: ...functions for SHEV and ventilation 4 Wind transmitter WG H 10 rain sensor REM H 10 WREM H 10 for automatic closing of windows top hung windows and light domes in case of rain and or wind 5 Conduit box...

Page 5: ...000 1000 300 1196 2 7 956 3 56 7 3 1000 1000 300 1118 3 7 956 4 56 7 4 1000 1000 300 1040 4 7 956 5 56 7 5 1000 1000 300 962 5 7 956 6 56 7 6 1000 1000 300 884 6 7 956 7 56 7 7 1000 1000 300 806 7 7 9...

Page 6: ...ety equipment for smoke removal or smoke control perform wiring in accor dance with the functional integrity classes E30 or E90 of the Model Wiring Guideline MLAR Security systems need line monitoring...

Page 7: ...l diagram The transformer connector is slipped on via cable lugs The central unit is overload and reverse battery protected A short circuit at the and terminals of the 24 V DC feed lines in the contro...

Page 8: ...age supply to the ventilation control system in case of a mains voltage failure The sensor at the end of the PTC cable is positioned close to the battery back see image while the other end is connecte...

Page 9: ...The group control module is used to control the motors monitor the motor lines for cable break and include an EMERGENCY STOP function for power controlled windows in the event of an emergency Technic...

Page 10: ...ese EMERGENCY STOP pushbuttons must comply with standard DIN EN 60204 The devices used to protect against crushing hazards and the EMERGENCY STOP button used as an opener are connect ed in series and...

Page 11: ...in the area of the fire pushbutton In case of emergency power operation the yellow ERROR LED 8 will flash The red ALARM LED 9 will be lit when the OPEN signal is active on the smoke and heat exhaust v...

Page 12: ...nitored for disruptions and short circuits Another option is to connect a central fire alarm system which however requires that only smoke detectors or only one central fire alarm system be connected...

Page 13: ...wind rain alarm is reset after a certain switch off delay The signal issued by the rain sensor is transferred to the internal bus To adjust the set point of the wind rain module slip on the jumper 3 a...

Page 14: ...r external devices The fuse 4 is used to protect the voltage supply circuit which is switched off in the event of a mains failure The module output is connected via 3 pin connectors 5 6 Jumpers 2 can...

Page 15: ...ange over module PFW 9 Works in the same way as PFA 9 but its output contacts are designed for 230 V AC Technical specifications Overview of the major components and modules cont Description The poten...

Page 16: ...TA 3 1 24 V DC Synchronous drives with exter nal synchronisation SYN 2K Sync drives Sync drives Sync drives Sync drives Synchronous drives with additional locking and external synchronous sequence SF...

Page 17: ...g Follow the terminal diagram to connect the battery pack wire To prevent dangerous gases from developing and to ensure the central control unit remains operational for 72 hrs in case of a mains failu...

Page 18: ...of the motor lines EMERGENCY STOP button pressed Fuse on module defective Display in wind rain module red LED is lit Error source The wind sensor has triggered a wind alarm The rain sensor was trigger...

Page 19: ...reversal of polarity yes approx 2 s Pulsing according to prEN 12101 9 yes every 2 min Automatic clearing no Line monitoring yes up to the last conduit box by monitoring diodes with 3rd line Connection...

Page 20: ...HAUTAU GmbH Wilhelm Hautau Str 2 31689 Helpsen Germany Tel 49 5724 393 0 info hautau de www hautau de...

Reviews: