Adjusting Alarm Set Points
Purpose: When the CWS/CGS is in Auto mode, it will automatically switchover to city water backup
on high temperature and low flow. The high temperature alarm set point is the supply temperature
threshold at which switchover to city water backup is triggered. On units with a flow transducer, the
low flow alarm set point is the threshold at which switchover to city water backup is triggered.
1.
Press
on the controller
2.
Press
or
to highlight Setpoints
3.
Press
to go into that menu section
4.
To change an alarm set point value, press
to move the blinking cursor to the value
5.
Press
or
to adjust the value
6.
Press
to move the blinking cursor to the top left corner
7.
With the blinking cursor in the top left corner, press
or
to navigate to additional alarm
set point screens (if applicable)