background image

EN

8

3. INSTRUCTIONS FOR INSTALLATION

3.1. Prior to Installation

Prior to installing the heater, read all the instructions 

for installation (figure 8), as well as checking the fol

-

lowing points:

• 

The heater volume should be suitable for the 
sauna room volume. Table 2 shows the mini-
mum and maximum volumes for each heater 
output. A precondition for the given values is 
that the sauna room is well heatinsulated. 
Walls and ceiling are covered with wood panel.

• 

Check that supply voltage and amperages are 
available for the heater.

• 

The breakers and the connection cables con-
form with valid regulations and their dimen-
sions are in accordance with table 3.

• 

The location is suitable for the heater 

(

3.2.).

• 

Note! Only one electrical heater may be 

installed in the sauna room. Multiple heaters 

can be installed and used in the sauna room 

only if they share the same control unit 

(Multidrive) 

3.2. Place and Safety Distances

The  minimum  safety  distances  are  described  in 

figure 3 and 5.

 

• 

It is absolutely necessary to install the heater 

according to these values. Neglecting them 

causes a risk of fire.

• 

Hot pieces of stone can damage floor coverings 

and cause a risk of fire. 

The floor coverings of 

the installation place should be heat-resistant.

3.3. Heater fence

It is necessary for safety and should be constructed 

of  softwood  to  match  sauna  interior.  See  figures 

3  and  5  for  clearances  from  sauna  heater.  Fence 
should be attached to wall and should not be placed 
higher than top of heater below rock line.

3.4. Installation of the Control Unit and Sensor

• 

The control unit includes detailed instructions 
for fastening the unit on the wall. 

Install the sensor (WX248), which comes with 

the heater, as shown in figure 6.

Do not place the supply air vent so that the air  

flow cools the temperature sensor. Figure 4.

3.4.1. Suitable control units

• 

Harvia CX30-U1-U3

• 

Harvia CX45-U1-U3

See more detailed information from table 3.

Heater grade setting of the control unit: C1

Please read the instructions of the control unit.

3.5. Electrical Connections

The heater may only be connected to the electrical 

network in accordance with the current regulations 

by an authorised, licensed professional electrician.

The wiring diagrams are included in the control 

unit’s installation instruction.

Further instructions concerning exceptional installa-

tions can be obtained from local electrical authorities.
1.  Remove heater from carton and place in 

proper location in sauna room. Observe proper 

clearances as per figures 3 and 5. After final 

hookup, electrical contractor should secure 

heater to floor with at least two screws or 

bolts.

2.  See applicable wiring diagram for heater model 

(figure 7, see control unit manual for detailed 

instructions how to connect the heater and 
the control unit). Heater must be permanently 
installed by using seal tight conduit between 
the heater and the wall of the sauna room 
(pigtails or plugs are not allowed in the sauna 
room). Wiring must be done by a licensed 
electrician, who must follow wiring diagram 
provided and adhere to local codes. Use proper 
AWG rated wire size and use copper wire 
suitable for 194 °F (90 °C) within sauna walls. 
Use grounding terminals provided in sauna 
heater and control unit to properly ground the 
equipment as per NEC and local codes.

3.  Inside the heater box there are two signs. 

Please place the metal ”CAUTION” sign on 
the interior wall of the sauna room directly 
above the heater in a visible place (screws and 
nails included). Place the metal ”WARNING” 
sign outside, on the door of the sauna room.  
”MAINTENANCE INSTRUCTIONS” are at the 
end of this manual.

Heater

Output

Dimensions

Stones

Sauna room

Width/Depth/
Height

Weight

Cubic vol.

Floor Area

Height

kW

inch

 

mm 

lb/kg

max.  
lb/kg

2.3.!

min.  

CuFt/m³

max.  

CuFt/m³

min
sqft

max
sqft

min.  

inch/mm

HPC(S)7U1H
HPC(S)7U3H

6,8

14/13/40

37,5

17

200 90

141 4

354 10

28

57

75

1900

360/340/1010

HPC(S)9U1H
HPC(S)9U3H

9,0

14/13/40

37,5

17

200 90

141 4

494 14

45

79

75

1900

360/340/1010

HPC(S)11U1H
HPC(S)11U3H

10,5

16/15/45
395/380/1150

46,3

21

265

120

141 4

636 18

22

98

78

1980

Table 2. 

Installation details of the heater

Summary of Contents for HPC(S)11U1H

Page 1: ...kW HPC S 7U3H 6 8 kW HPC S 9U3H 9 0 kW HPC S 11U3H 10 5 kW Instructions d installation de c blage et d utilisation d pannage entretien et garantie du po le de sauna IMPORTANT Ce manuel doit tre remis...

Page 2: ...ARTS 11 GUARANTEE 22 MAINTENANCE INSTRUCTIONS 23 TABLE DES MATI RS Avertissements 12 1 MODE D EMPLOI 13 1 1 Mise en place des pierres du po le 13 1 1 1 Maintenance 13 1 2 Chauffage du sauna 13 1 2 1 U...

Page 3: ...egrees above the normal body temperature of 98 6 F The symptoms of hyperthermia include an increase in the internal temperature of the body dizziness lethargy drowsiness and fainting The effects of hy...

Page 4: ...r near the heater that could change the amount or direction of the air flowing through the heater A bare heating element can endanger combustible materials even outside the safety distances Check that...

Page 5: ...higher figure than the temperature of the sauna Check that the overheat protectors have not gone off See figure 9 Check that the breaker is switched on Also breaker should be correct size The sauna ro...

Page 6: ...d with moisture content not exceeding 11 BENCHES Use matching softwood Fasten from bottom to prevent burning of bathers DOOR Must open out and should not have a lock Types of door fastenings that may...

Page 7: ...l and fence Figure 4 Sensor s minimum distance from an air vent 360 180 40 1000 mm 20 500 mm TILE CARRELAGE AIR IN ARRIV E D AIR CONCRETE B TON AIR OUT VACUATION D AIR 6 4 FENCE CEINTURE DE PROTECTION...

Page 8: ...unit C1 Please read the instructions of the control unit 3 5 Electrical Connections The heater may only be connected to the electrical network in accordance with the current regulations by an authoris...

Page 9: ...n this diagram Main Electrical Panel Figure 6 Installing the temperature sensor 3 80mm 3 80mm 4 100mm 4 100mm HPC S 7U1H HPC S 7U3H HPC S 9U1H HPC S 9U3H HPC S 11U1H HPC S 11U3H Table 3 Supply wires f...

Page 10: ...S 9U3H HPC S 11U3H L11 L21 A1 A2 L22 L12 140 C T L11 L21 A1 A2 L22 L12 R3 R2 R1 208V 3 Phase heater 240V 1 Phase heater 1 Group connection 2 Group connection A Connection box B Connection cable 3 7 E...

Page 11: ...PC S 9U1H HPC S 11U1H HPC S 7U3H HPC S 9U3H HPC S 11U3H 3 3 3 3 3 3 2 Overheat protector ZSK 764 1 3 Temperature sensor WX248 1 3 8 Resetting the Overheat Protectors If the temperature of the sauna ro...

Page 12: ...usieurs degr s la temp rature normale du corps 98 6 F Les sympt mes d hyperthermie incluent une hausse de la temp rature interne du corps des vertiges la l thargie la somnolence et l vanouissement Les...

Page 13: ...raverse le po le ne doit tre plac l int rieur du com partiment pierres du po le ni proximit de ce dernier Recouvrir enti rement les r sistances de pierres Une r sistance non couverte risque d endommag...

Page 14: ...e du sauna S assurer que les s curit s surchauffe soient toujours en place Figure 9 V rifier que le circuit lectrique est ferm au niveau du coupe circuit Le coupe circuit doit aussi tre de la bonne ta...

Page 15: ...de faciliter la fixation des planches des murs et du plafond REV TEMENT MURAL Utilisez du bois s ch au s choir avec une teneur en humidit inf rieure 11 BANCS Utilisez du bois assorti Placez les fixat...

Page 16: ...rs du m nage hebdomadaire il est bon d aspirer de balayer le sol du sauna Il est aussi recommand de le laver avec un chiffon humide Au moins tous les six mois le sauna doit tre nettoy fond Les murs le...

Page 17: ...ture Figure 3 3 4 1 Centres de contr le adapt s Harvia CX30 U1 U3 Harvia CX45 U1 U3 Pour en savoir plus voir le tableau 3 R glages de classe du centre de contr le C1 Veuillez lire les instructions du...

Page 18: ...s des picines et des douches Aucun r cepteur ne doit tre install dans le sauna Tableau de commande Capteur Conduite herm tique 90 C WIRE Un panneau de distribution Cutler Hammer mod le CH4F doit tre i...

Page 19: ...fournies Figure 7 Connexions lectriques de po le HPC S 7U1H HPC S 9U1H HPC S 11U1H 140 C T L1 L2 A2 A1 L3 R1 R2 R3 HPC S 7U3H HPC S 9U3H HPC S 11U3H L11 L21 A1 A2 L22 L12 140 C T L11 L21 A1 A2 L22 L1...

Page 20: ...nitialisation de la s curit surchauffe Si la temp rature de la cabine de sauna devient dangereusement lev e la s curit surchauffe coupe d finitivement l alimentation du po le Il est possible de remett...

Page 21: ...tance 3000 W 240 V R sistance 3500 W 240 V R sistance 2250 W 208 V R sistance 3000 W 208 V R sistance 3500 W 208 V Y10 0005 Y10 0004 Y10 0002 Y10 0004 Y10 0003 Y10 0001 HPC S 7U1H HPC S 9U1H HPC S 11U...

Page 22: ...The manufacturer gives a one year guarantee for this heater The guarantee starts from the date of purchase and includes all the parts of the heater heating elements controls contactors etc The guaran...

Page 23: ...ne ar elle endommagerait grave ment le po le 2 Utilisez toujours de l eau propre dans les seaux du sauna et jetez l eau apr s chaque utilisa tion Frottez les seaux et les louches de temps en temps lor...

Page 24: ......

Reviews: