◆ Output signal: DC4~20mA+HART protocol
◆ Allowable load resistance: 0~600Ω (when DC 24V)
Note: A standard (250 Ω) load resistor is required to communicate with the
handheld communicator.
◆ Power supply:
General purpose
DC10.5~45V
Intrinsically safe explosion-proof
DC10.5~26V
◆ Communication line conditions: Line length: up to 2km (0.75~1.25mm2 control
instrument cable, use twisted pair cable for more than 1km)
Load resistance: 250~600Ω
(DC 24V, including cable resistance)
Load capacitance: below 0.55mF
Load inductance: 3.3mH with power line spacing: 15cm or more
(Please avoid parallel wiring)
◆ Saturation current: upper limit 20.8mA
Lower limit 3.8mA
◆ Alarm current: upper limit 22.8mA
Lower limit 3.6mA
◆ Adjustment function: Zero point and full-scale point can be adjusted on site
from the top three buttons of the outer casing or can be adjusted remotely by
using configuration software.
◆ Zero migration: Can migrate within the range of -20% to +20% of the
maximum range
◆ Output mode: linear output
Square root output
(May achieve remote adjustment via configuration software)
◆ Ambient temperature: -40~+85° C
(When filling with fluorine oil: -10~+60° C)
◆ Storage temperature: -40~+90° C
◆ Weather resistance: DIN40040GPC
◆ EMC applicable standard: EN1326-1:2006