5.2.1 Wiring diagram
Grounding
Power positive
Power negative
Testing positive
5.2.2 Cable specifications
◆ The company recommends to use shielded, double-core double-twisted cable
◆ Wire core cross-section of block terminal: 0.5...2.5mm2
◆ Cable outer diameter: 5...9mm
5.2.3 Shielding / potential balance
◆ When both ends of the shielding layer are grounded (connected to the control
and equipment respectively), it is possible to obtain the best shielding effect
to prevent interference impact on the measurement. When there is strong
equalizing current in the factory, the shielding layer is only connected at one
end. It is recommended to ground the transmitter end.
◆ When using in a hazardous area, comply with applicable regulatory
requirements.
Additional technical data and operating manuals in the separate explosion-proof
manual are standard documents for all explosion-proof (Ex) systems.