GU320a Controller Manual
18
10.3 Central Pick-up Control Unit Communication Protocols
RS485 mechanism is a kind of network form by character signal between the computer and hardware
device. Controller working baud rate is 9600-Baud, communication protocol is
MODBUS-RTU.
When it is
working, the computer will send out a serial orders to the central pick-up controller, and then wait the reflect
data block..
NOTE: max byte (word) of write/read, read is 16, write is 14. Only continuous write order 10(hex)
could be used for write .
Controller Data Cell Address
Address Byte
Content
Unit
$1000
1
L3-N Voltage Ph-c phase voltage
unit
:
V
$1001
1
L2-N Voltage Ph-B phase voltage
unit
:
V
$1002
1
L1-N
Voltage Ph-A phase voltage
unit
:
V
$1003
1
L3-L1 Voltage AC phase and line voltage
unit
:
V
$1004
1
L2-L3 Voltage BC phase and line voltage
unit
:
V
$1005
1
L1-L2 Voltage AB phase and line voltage
unit
:
V
$1006
1
L3 Current
Ph-c phase current
unit
:
A
$1007
1
L2 Current
ph-B phase current
unit
:
A
$1008
1
L1 Current
ph-A phase current
unit
:
A
$1009
1
L3 PF ph-c PF
$100A
1
L2 PF ph-B PF
$100B
1
L1 PF ph-C PF
$100C
1
Frequency
Generator frequency
unit
:
0
.
1HZ
$100D
1
L3 VA Ph-C real power
unit
:
K
VA
$100E
1
L2 VA Ph-B real power
unit
:
K
VA
$100F
1
L1 VA Ph-A real power
unit
:
K
VA
$1010
1
L3 W Ph-C active power
unit
:
K
W
$1011
1
L2 W Ph-B active power
unit
:
K
W
$1012
1
L1 W Ph-A active power
unit
:
K
W
$1013
1
L3 VAr Ph-C reactive power
unit
:
K
VAr
$1014
1
L2 Var Ph-B reactive power
unit
:
K
VAr
$1015
1
L1 VAr Ph-A reactive power
unit
:
K
VAr
$1016
1
T
acho Rotating speed of Speed sensor
unit
:
RPM
$1017
1
OilPress value of oil p-sensor
unit
:
Kpa
$1018
1
Coolant value of T-sensor
unit
:℃
$1019
1
VBAT Battery voltage
unit
:
V
$101A
1
VALT Charge excitation voltage
unit
:
V
$101B
1
AI input voltage standby
unit
:
mV
bit0
—
oil pressure
bit1
—
water temperature
bit2
—
emergency stop
bit3
—
remote control start
$101C
1
Bit4
—
switch signal standby
bit0
—
diesel engine oil
bit1
—
diesel engine start
bit2
—
Gen.set run in normal
bit3
—
Alarm output
bit4
—
Pre-alarm output
$101D
1
bit5
—
Idle speed output
$101E
1
LED
$101F
1
Palarm Pre-alarm code