GU320a Controller Manual
12
2.1
V Low Alarm
0V
AC45~20000V
0 (no setting)
2.2
V Low preALM
198V
AC45~20000V
0 (no setting)
2.3
V High preALM
253V
AC45~20000V
29999 (no setting)
2.4
V High Alarm
29999
AC45~20000V
29999 (no setting)
2.5
I High preALM
9999A
0~9999A
9999 (no setting)
2.6
I High Alarm
9999A
0~9999A
9999 (no setting)
2.7
Alarm delay
10s 0~600s
8.3
ENGINE
NO. Item
Preset
Range
3.0
QUIT
3.1
Nominal speed
1500
99-9999 RPM
3.2
Pickup frequency
3000
1-9999 Hz
3.3
Set pickup now
3.4
Fuel mode
0
0~1
0(NC) 1 (NO)
3.5
T-sensor mode
0
0~8
0 (no use)
3.6
P-sensor mode
0
0~9
0 (no use)
3.7
H-sensor mode
0
0~1
0 (no use) 1 (use)
3.8
Start delay
10s
0~300 s
3.9
Crank attempt
3
1~10s
3.10
Crank time
8s
0~30 s
3.11
Crank reset
15s
0~300 s
3.12
Crank disconnect
300RPM
1-9999 RPM
3.13
Idle delay
0
秒
0~9999s
3.14
Safety-on delay
60s
0~600s
3.15
Cooling delay
300s
0~600 s
3.16
Stop delay
20s
0~60s
3.17
Under SP Alarm
0 RPM
0-9999 RPM
0 (no setting)
3.18
Under SP preALM
1440 RPM
0-9999 RPM
0 (no setting)
3.19
Over SP preALM
1600 RPM
0-9999 RPM
9999 (no setting)
3.20
Over SP Alarm
1710 RPM
0-9999 RPM
9999 (no setting)
3.21
Oil-P low Alarm
140KPa
50~300Kpa
0 (no setting)
3.22
Oil-P low preALM
220KPa
50~300Kpa
0 (no setting)
3.23
Coolant preALM
95
℃
70~160
℃
9999 (no setting)
3.24
Coolant Alarm
105
℃
70~160
℃
9999 (no setting)
3.25
Batt low preALM
8.0V
1~25V
0 (no setting)
3.26
External. Alarm
0
3.27
External analog
2
0 unit V, 1 unit %, measuring 0-5v signal.
2 unit %, self determine the input according to the
resistance type and sensor data.
8.4 Note for pressure and temperature sensor
Different type of P-sensor and T-sensor according to the table followed, if the sensor available is not in the table, then
write the sensor parameter into the controller through the software, and the sensor setting in the parameter setting should be
the last type “user define”
Pressure sensor
NO. Type
0
NOT USE
1
VDO 10 bar
2
VDO 5 bar
3
Datcon 10 bar
4
Datcon 7 bar