10.1 Commissioning and hand over
Warning
As part of the commissioning programme,
the commissioning engineer must go
through the following with the operator.
(i) Lighting, shutdown, and operational
information.
(ii) Safety features, data plate, and labelling.
(iii) The requirement for regular inspection -
especially if the heater is within a more
demanding environment - and the need for
regular servicing, carried out by competent
and qualified engineers.
Caution
After approximately 100 hours of running,
the tension on the fan belts must be
checked to ensure that it is correct, and that
the belts have not stretched.
It is strongly advised that this is undertaken
by the commissioning engineer, and not the
operator
10.2 Servicing
Warning
Servicing must be carried out on a regular
basis, the maximum interval between
services being one year.
It is a requirement that only suitably qualified
and competent persons are allowed to
undertake the servicing.
Harry Taylor advise that the planned service
schedule as detailed in section 5.1 of the
Installation, Commissioning and Servicing
Manual is adopted by the user.
Further details are available from either
Harry Taylor or from the commissioning
engineer.
10.3 Start Up Procedure
(a) Enable burner via controller by selecting
‘Heat’ (Relay 2); ‘Heat On’; ‘Heat/Auto’.*
(* dependent on control type supplied. Refer
to individual controller operating manual.)
(b) Burner will fire and establish within
60seconds.
(c) As temperature of heater increases, fan
will operate.
10.4 Stop procedure
(a) Disable burner by selecting ‘Heat OFF’;
‘Standby’.* (* dependent on control type
supplied. Refer to individual controller
operating manual.)
(b) The burner will turn off.
(c) The fan motor will continue to run until
heat dissipation allows the fan and limit stat
to shut down the fan.
Caution
Do not use the main electrical isolator to
turn off the heater, to do so can cause
damage to the heat exchanger and
combustion chamber and thereby invalidate
the warranty.
10.5 Shut down procedure
(a) Follow steps 10.4 (a), (b) and (c), when
main fan stops turn main electrical isolator
off, and shut oil valves
10.6 Ventilation only
(a) Enable fan on via controller by selecting
‘Fan only’; ‘Vent only’; ‘Vent/Manual’.*
(*dependent on control type supplied. Refer
to individual controller operating manual.)
(b) Fan will operate without the burner for
the set period of the controller.
10.7 Lockout situations
If either the burner or the fan and limit stat
go to lockout, the lockout must be cleared
manually before the ignition sequence can
be re-initiated.
Caution
Repeated or frequent lockouts must be
investigated and their cause determined by
a qualified and competent engineer.
10 User Instructions
Document re
feren
c
e number
20
-45-
494
March 20
14 i
s
sue
15
Replace
s
20
-45-494
M
a
y 2013
i
ssu
e 1
4
Summary of Contents for HT2000
Page 34: ...34 Wiring Diagram 20 45 605 60 85 ON OFF Riello Burner Integral CP4 230 50 1ph...
Page 35: ...35 Wiring Diagram 20 45 606 120 135 ON OFF Riello Burner Integral CP4 230 50 1ph...
Page 36: ...36 Wiring Diagram 20 45 607 60 275 ON OFF Riello Burner Integral CP4 415 50 3ph...
Page 37: ...37 Wiring Diagram 20 45 620 30 40 ON OFF Riello Burner Remote CP4 230 50 1ph...
Page 38: ...38 Wiring Diagram 20 45 621 60 85 ON OFF Riello Burner Remote CP4 230 50 1ph...
Page 39: ...39 Wiring Diagram 20 45 622 120 135 ON OFF Riello Burner Remote CP4 230 50 1ph...
Page 40: ...40 Wiring Diagram 20 45 623 60 275 ON OFF Riello Burner Remote CP4 415 50 3ph...
Page 41: ...41 Wiring Diagram 20 45 612 30 40 ON OFF Riello Burner No Controls 230 50 1ph...
Page 42: ...42 Wiring Diagram 20 45 613 60 85 ON OFF Riello Burner No Controls 230 50 1ph...
Page 43: ...43 Wiring Diagram 20 45 614 120 135 ON OFF Riello Burner No Controls 230 50 1ph...
Page 44: ...44 Wiring Diagram 20 45 615 60 275 ON OFF Riello Burner No Controls 415 50 3ph...
Page 45: ...45 Wiring Diagram 20 45 292 HI LOW option Riello Burner CP4 Control...
Page 51: ...51 9 0 Parts Lists...
Page 55: ...55 Notes...