13
2.9.1.2
Mechanical Ventilation to the
Heated Space.
In the event that the heated space has a
design air change of less than 0.5 air
changes per hour and that installer prefers
to mechanically ventilate the heated space
rather than provide ventilation openings then
-
•
The heated space needs to be
mechanically ventilated so that the
design air change is 0.5 air changes or
greater.
•
It is a requirement that the mechanical
ventilation shall be of the ‘input’ type
with either natural or mechanical
extraction.
•
Systems of mechanical extraction with
a natural inlet shall not be used.
•
It is necessary to provide an automatic
means to safely inhibit heater(s)
operation should mechanical air
supply fail for any reason.
2.9.2. Heaters Installed within a Plant
Room or Enclosure.
A plant room means a room housing the
heater plant and probably other items of
building service plant and would generally
have generous space for maintenance.
An enclosure is where the heater is installed
within a compartment or confined area
where space is limited.
Where heaters are installed within a plant
room or enclosure then provision for both
combustion air and air for general ventilation
will be required by means of high
and
low
level ventilation openings (sections 2.3.2.1
refers to plant room applications and
sections 2.3.2.2 refers to enclosure
applications).
Alternatively the plant room or enclosure
may be mechanically ventilated (section
2.3.2.3 refers).
2.9.2.1 Natural Ventilation Openings
to Plant Rooms
For plant room applications the minimum
free area of ventilation opening shall be:
•
At high level 2 cm
2
for each kW of
rated heat input.
•
At low level 4 cm
2
for each kW of rated
heat input.
The high level ventilation opening should be
sited on an external wall and positioned as
high as is practical and always within the top
15% of the wall height.
The low level natural ventilation opening
should be situated on an external wall and
be within 1000 mm of floor level for natural
gas and ideally at floor level for l.p.g gas
installations but in any event no higher than
250 mm.
The table in the next column provides
specific data for each heater model as -
Minimum Free Area of
ventilation opening
High Level
Low Level
cm
2
cm
2
30
None
64
35
None
79
40
None
97
60
None
127
75
None
160
85
None
193
120
None
257
135
None
291
180
None
386
205
None
460
235
None
515
275
None
623
350
None
769
375
None
847
Model
Summary of Contents for HT2000
Page 34: ...34 Wiring Diagram 20 45 605 60 85 ON OFF Riello Burner Integral CP4 230 50 1ph...
Page 35: ...35 Wiring Diagram 20 45 606 120 135 ON OFF Riello Burner Integral CP4 230 50 1ph...
Page 36: ...36 Wiring Diagram 20 45 607 60 275 ON OFF Riello Burner Integral CP4 415 50 3ph...
Page 37: ...37 Wiring Diagram 20 45 620 30 40 ON OFF Riello Burner Remote CP4 230 50 1ph...
Page 38: ...38 Wiring Diagram 20 45 621 60 85 ON OFF Riello Burner Remote CP4 230 50 1ph...
Page 39: ...39 Wiring Diagram 20 45 622 120 135 ON OFF Riello Burner Remote CP4 230 50 1ph...
Page 40: ...40 Wiring Diagram 20 45 623 60 275 ON OFF Riello Burner Remote CP4 415 50 3ph...
Page 41: ...41 Wiring Diagram 20 45 612 30 40 ON OFF Riello Burner No Controls 230 50 1ph...
Page 42: ...42 Wiring Diagram 20 45 613 60 85 ON OFF Riello Burner No Controls 230 50 1ph...
Page 43: ...43 Wiring Diagram 20 45 614 120 135 ON OFF Riello Burner No Controls 230 50 1ph...
Page 44: ...44 Wiring Diagram 20 45 615 60 275 ON OFF Riello Burner No Controls 415 50 3ph...
Page 45: ...45 Wiring Diagram 20 45 292 HI LOW option Riello Burner CP4 Control...
Page 51: ...51 9 0 Parts Lists...
Page 55: ...55 Notes...