Harrington Signal

 HS-3030 

Fire Alarm Control Unit

Operator’s Manual

Revision 

1

Document # LT-2012HAR

HARRINGTON

FIRE ALARM

SIGNAL INC.

Summary of Contents for HS-3030

Page 1: ...Harrington Signal HS 3030 Fire Alarm Control Unit Operator s Manual Revision 1 Document LT 2012HAR HARRINGTON FIRE ALARM SIGNAL INC...

Page 2: ......

Page 3: ...1 2 Types of Inputs 1 1 3 Status Display 2 1 4 Zone LEDs 2 1 5 Buzzer 2 1 6 Operator Keys 3 1 7 Alarm List 6 1 8 LCD and Keypad 7 1 9 Silent Walk Test 10 2 0 Supplementary Information 11 2 1 Diagnost...

Page 4: ......

Page 5: ...st Pull Station This type of input is for pull stations They are required to activate bells and or strobes as well as an LED They can optionally operate relays and control modules in a network as well...

Page 6: ...Checksum Error Database Mismatch FIFO Overflow etc the clock will display 4 dashes instead of the time The buzzer will also beep rapidly to indicate the memory error The clock will also display 4 das...

Page 7: ...2 The default layout is the same as for the HS1 program The panel will beep once when a valid key is pressed and beep three times if an invalid unavailable key is pressed The panel will record every...

Page 8: ...t the system from going to the next stage Second Stage Inhibit has no effect on an EVAC type bell system The green LED will flash when Second Stage Inhibit is available and the yellow LED will flash w...

Page 9: ...e bells are disabled This beeping is suppressed while a privileged level is entered in the panel Press Signal Disconnect again to re enable the bells The yellow LED will flash while the bells are disa...

Page 10: ...screen giving a short description of the event HS2 programs will add device and panel message screens as required To view additional entries in the Alarm List when an entry is showing press the Scroll...

Page 11: ...mal conditions If a privilege level has been entered it will be displayed in the Main Menu as well instead of the time Menus have a or next to the description of each item Use the arrow keys on the ke...

Page 12: ...aded database of the panel to a printer connected to the panel s printer port The printer port is at the bottom of the main assembly and is the one on the right Print Archive This function is restrict...

Page 13: ...by a dot All times are in 24 hour format Press Enter to accept time typed Clear will remove any digits typed If no digits are displayed Clear will return to the Clock Menu The new time entered will b...

Page 14: ...ut circuits only The output circuits are not part of the walk test To activate the walk test first connect the radio to the audio output jack Then activate the walk test by pressing the Test Mode key...

Page 15: ...codes and zone numbering Condition Code Archive Alarm List Description A ALARM Alarm B bypass Bypass C com Comlink D dupl Duplicate Addressable Device E alert Maintenance Alert G ground Ground Fault...

Page 16: ...n 6 Initiating Circuit 6 641 Program Checksum 7 Initiating Circuit 7 651 Database Checksum 8 Initiating Circuit 8 66 AC Power 9 Initiating Circuit 9 67 Low Battery 10 Initiating Circuit 10 691 Program...

Page 17: ...red Zone 94 Unit ID of panel generating the Network Reboot Required trouble Network Reboot Required Why Zone 95 001 network 002 network 003 port 3 006 negative counter 008 memory overflow 009 co proce...

Page 18: ...ch the hardware listed in the panel Correct the database and reload no database loaded The panel does not have a database in memory Load a database into the panel wrong database version or database mi...

Page 19: ...itched on Note This message appears in Test Mode only B Bell Circuit 1 to 8 T Trouble Relay F Function Relay 1 to 4 W Walk Test Relay A Alarm Relay G Ground Fault Relay S Supervisory Relay L LCD Back...

Page 20: ...AL from the LCD menu manual switches One or more switches with timers have been forced either on or off This is not shown for switches that do not have timers To view which switches are forced select...

Page 21: ...uble not enough ram The operating program requires more extend RAM then the panel actually has Certain addressable functions and or the alarm list may not work Basic fire detection will continue to op...

Page 22: ......

Page 23: ......

Page 24: ...Harrington Signal Inc 2519 4th Avenue Moline IL 61265 HARRINGTON FIRE ALARM SIGNAL INC...