Chapter 6 Setting up parameters
-
91
-
22: In-position ready range
(position)
●
Function
When the difference between “command pulse count” and “returned pulse count,” which is “deviation
pulse count,” decreases below the setting value of “in-position ready range,” the signal is outputted to
“CN2 In-position ready output: IN-POS” as completion of positioning.
This value only monitors the state of position deviation and does not directly affect the rotation control of
the servo actuator.
●
Setting
unit
Lower limit
Upper limit
Default
Pulse
0
9999
10
23: Command pulse input factor-numerator
(The power must be turned on again after setting a change.)
24: Command pulse input factor-denominator
(The power must be turned on again after setting a change.)
(position)
●
Function
Use each parameter in conjunction with [Command pulse input factor-Numerator] and [Command pulse
input factor-Denominator] as the electronic gear function. It is used to have integral number for the
relationship of the input pulse number and the amount of moment of the machine that the actuator
drives.
The formula of the relationship of “numerator and denominator” as follows:
For rotary operation:
For linear operation:
* Actuator resolution = Encoder resolution (4 times) x Actuator duty factor
On the basis of this formula, set the parameter value so that both the numerator and denominator will be
integers.
●
Setting
unit
Lower limit
Upper limit
Default
Numerator
-
1
999
1
Denominator
-
1
999
1
Note 1: The power must be turned on again after setting a change. The previous value is effective until
you turn on the power again.
Note2: By default, the internal pulse is performed with the encoder resolution (4 times). The amount of
movement of the actuator will thus be the one corresponding to the encoder resolution (4 times).
Angle of movement per input pulse =
command pulse input factor -numerator
command pulse input factor -denominator
×
360
*Actuator resolution
×
1
Reduction ratio of load mechanism
Amount of feed per input pulse =
command pulse input factor -numerator
command pulse input factor -denominator
×
Load mechanism feed pitch
*Actuator resolution