background image

27

Save  These  Instructions                                                                                                                             

TL2.6 Woodburning Stove

Dry Seasoned Wood Only!

Harman®  •  TL2.6 Owner's Manual_R25  •  2011 -___  •  09/15

Avoid overfiring your stove. Overfiring is a potentially 

hazardous situation which can lead to overheating of 

combustible materials nearby, damage to the stove, and 

in extreme cases, cause a fire. Overfiring is caused by: 1. 

Too much air flowing through the stove too quickly. 2. You 

may have positioned the primary air control lever too far to 

the right. 3. Inadvertently leaving the damper open or 4. Not 

keeping up with routine maintenance, such as checking door 

gaskets for wear.

Overfiring results in excessive fuel consumption, and may 

cause parts of the stove or chimney connector to glow red. 

If you notice signs of overfiring, reduce the air supply to the 

fire, and review the Maintenance section in this manual.
In the event of a chimney fire, call your local fire department; 

make sure everyone is safely out of the house. Reduce the 

air intake of the stove as much as possible using the air 

control lever; close the bypass damper to further restrict air 

flow. Do not throw water on the fire; this can cause stove 

damage and create an even more dangerous situation. Have 

your chimney professionally cleaned and inspected before 

resuming burning in your stove.
As you begin to operate your stove at higher temperatures, 

you will notice a “hot” or unpleasant smell; this is just the 

paint going through the curing process, and will disappear 

after a few fires.

Providing you have the charcoal bed described, close the 

bypass damper by pulling the handle toward the front of the 

stove. This will begin the highly efficient mode of operation 

where the exhaust gases get re-burned in the secondary 

combustion package. If you cannot achieve a charcoal bed 

within the first 15 to 20 minutes, your wood is likely too wet, 

and you may need to burn the fire longer and/or hotter to 

compensate for the extra energy needed to drive out the 

moisture. If, after five minutes of burning with the damper 

closed, smoke is visible coming from the chimney, you 

probably do not have the proper coal bed. Open the bypass 

damper and continue with the process until a significant coal 

bed is formed.
Install a magnetic probe stack thermometer 24" above the 

flue collar of the unit. With the thermometer at this location, 

the following guidelines can be helpful if followed; however, 

remember these are only rough guidelines and a myriad of 

other factors contribute to the operation of the Harman

®

 TL2.6 

wood stove. While establishing a coal bed, prior to engaging 

the Firedome, a 2-3” coal bed and a stack temperature of 

900°F - 1100°F indicate that the stove is normally ready for 

Firedome mode. With the Firedome engaged, temperatures 

of 500°F – 800°F indicate the unit is burning properly and 

no adjustment is necessary. Temperatures below 400°F with 

wood remaining in the firebox indicate the Firedome system 

is not working and the stove is likely smoking. Open the 

damper, and allow the unit to burn with the damper open for 

10-15 minutes to reheat before attempting to reengage the 

Firedome system. Lastly, temperatures above 1000°F with 

the Firedome engaged indicate the unit is being over-fired. 

Unit damage may occur from operating the unit at stack 

temperatures above 1000°F.
Always remember to open the bypass damper when you are 

loading, this allows the exhaust gases to pass directly into 

the flue outlet and reduces the chance of smoke spillage 

into the room. 

Reloading: 

Once you have prepared and maintained a thick 

charcoal bed, and the secondary combustion is established, 

you should be able to reload the stove at any time by simply 

opening the bypass damper, then the load door, adding fuel 

and closing the door then the damper. This depends on coal 

bed size, load size and moisture content of fuel.

Removing Ashes:

 Before reloading, empty the ash pan 

(remember to close the ash door while emptying the pan). 

The ashes should be the coolest at this time. Remove ashes 

from the fire chamber periodically by raking a poker across 

the bottom grates.
Excessive ash buildup can prevent proper venting of exhaust 

gases. D

o  not  allow  the  ash  pan  to  over-fill. Ash  buildup 

between the ash pan and the bottom of the grate can cause 

the grate to overheat and wear out prematurely.

The TL2.6 is designed to provide access to the ash pan 

without the need for opening the main door. Before opening 

the ash door and removing the ash pan, open the bypass 

damper. Wearing heavy protective gloves, open the ash door 

and remove the ash pan by pulling it forward by the handle. 

Close the ash door and damper bypass before taking the 

ashes outside for safe disposal.

DISPOSAL OF ASHES;

Ashes should be placed in a steel container with a 

tight fitting lid. The closed container of ashes should 

be moved outdoors immediately, and placed on a 

noncombustible  floor  or  the  ground,  well  away  from 

all combustible materials, pending final disposal. If the 

ashes are disposed of by burial in soil or otherwise 

locally dispersed, they should be retained in the closed 

container until all cinders have completely cooled. Other 

waste shall not be placed in this container.

 

HOT WHILE IN OPERATION. KEEP CHILDREN, 

CLOTHING AND FURNITURE AWAY. CONTACT MAY 

CAUSE SKIN BURNS.

RISK OF EXCESSIVE TEMPERATURES. KEEP ASH 

DOOR CLOSED DURING FIRING OF THE HEATER.

NEVER LEAVE THE STOVE UNATTENDED IF EITHER 

THE ASH OR LOAD DOOR IS OPEN. OVERFIRING 

MAY RESULT.

CAUTION

!

Summary of Contents for TL 2.6

Page 1: ...PERMITS HOT WILL CAUSE BURNS DO NOT TOUCH GLASS UNTIL IT IS COOLED NEVER ALLOW CHILDREN TO TOUCH GLASS KEEP CHILDREN AWAY CAREFULLY SUPERVISE CHILDREN IN SAME ROOM AS FIREPLACE ALERT CHILDREN AND ADUL...

Page 2: ...le ou d autres liquides inflammables AVERTISSEMENT Risque d incendie ne pas fonctionner avec chargement de combustible ou d enl vement de cendres portes ouvertes Ne pas stocker carburants ou de combus...

Page 3: ...le Home Installation 21 Section 7 Appliance Set Up A Outside Air Attachment 22 B Leveling the Appliance 22 C Optional Cooking Grill 22 D Optional Blower Kit 23 E Brushed Stainless Trim Option 23 Secti...

Page 4: ...Certified to comply with 2015 particulate emission standards Not approved for sale after May 15 2020 MODEL TL2 6 Woodburning Stove LABORATORY OMNI Test Laboratories Inc REPORT NO 135 S 30b 6 2 TYPE S...

Page 5: ...dows or doors 2 Make sure the stove doors and lid are closed and latched 3 Check stove for smoking or puffing condition Open by pass and increase air flow to firebox if needed 4 Check chimney for poss...

Page 6: ...appliance Certain conditions can create negative pressure within the dwelling When this occurs you may have trouble operating the wood stove Worse yet it may be strong enough to allow smoke leakage fr...

Page 7: ...ff the rear shield by removing the four bolts near each corner of the safety label The flue cover plate and the flue collar have the same 2 bolt pattern Switch the two of them by removing the nuts fro...

Page 8: ...ey meets the minimum height requirements 10 All labels and hang tags have been removed from the glass 11 All plated surfaces have been wiped clean if applicable 12 The optional air distribution blower...

Page 9: ...nce Dimensions Section 4 Dimensions and Clearances 23 15 16 607mm 34 7 8 885mm 36 11 16 935mm 25 7 8 657mm 34 9 16 888mm 32 3 4 832mm 25 7 8 657mm Outside Air Kit 9 5 16 236mm 29 1 2 749mm C L Outside...

Page 10: ...d Fuel Burning Appliances Vertical Venting Configuration Location Single Wall Pipe Double Wall Pipe A Unit to Side Wall 17 432mm 15 381mm B Unit to Back Wall 17 432mm 15 381mm C Vent Pipe to Side Wall...

Page 11: ...rances for Solid Fuel Burning Appliances for clearance from the top of the unit to ceiling This unit was not tested for installation into an Alcove Follow NFPA 211 Table 13 6 1 Clearances for Solid Fu...

Page 12: ...of the stove A corner installation is one in which the back of the stove is positioned diagonally across a corner of the room Each installation requires its own set of clearances For corner installat...

Page 13: ...e collar opening which is 6 inches Do not use makeshift compromises No part of the chimney connector may pass through an attic or roof The Chimney Connector Shall Not Pass Through an Attic or Roof Spa...

Page 14: ...olid fuel chimneys extend 3 ft 0 9m above the highest point at which they exit from the roof Then the chimney must extend 2 ft 0 6m above the highest point within a 10ft 3m radius Thus the 3 foot 2 fo...

Page 15: ...Protection in this section Since many fireplaces have exposed wooden mantels and trim pay special attention to the clearances necessary to these materials If your fireplace chimney is behind a combus...

Page 16: ...led Space a Floor or Ceiling Chimney Connector Minimum air space with chimney listing Chimney support Attic radiation shield Chimney sections Chimney cap Storm collar Roof flashing Roof radiation shie...

Page 17: ...ce Closet or Similar Concealed Space a Floor or Ceiling Minimum clearance to unprotected ceiling 15 Chimney connector sealed at thimble Flue liner with required air space Minimum of three sheet metal...

Page 18: ...of Space Closet or Similar Concealed Space a Floor or Ceiling Combustible Floor Airtight insulated clean out Flue liner with required air space Floor Protection Stainlesssteel chimney connector must e...

Page 19: ...Concealed Space a Floor or Ceiling Combustible Floor UL1777 Stainless steel liner system or other approved lining system Floor Protection Follow liner manufacture s instructions on insulation and supp...

Page 20: ...y connector to uprotected ceiling 15 Flue liner with required air space Listed or approved thimble assembly 1 Clearance for exterior chimney or 2 clearance for interior chimney and 2 clearance for NFP...

Page 21: ...inal cap with spark arrestor 7 Use silicone to create an effective vapor barrier at the location where the chimney or other component penetrates to the exterior 8 Installation shall be in accordance w...

Page 22: ...ide the other end of the metal intake flex pipe into the stub on the rear of the stove and secure it with aluminum tape This air intake will supply outside air for the secondary combustion 7 Secure th...

Page 23: ...eces Load door trim Ash lip trim and the Ash door frame To install the load door trim it is best to remove the door by lifting from the hinges Lay the door down flat on it s face Drill the dimpled hol...

Page 24: ...open the ash door lift up the handle and pull out Close the door by pushing in and pushing the handle all the way down Top Load Door To open the top load door open the bypass damper and then lift to...

Page 25: ...bustion air enters at the bottom front of the stove where it travels upward through channels at either side of the front door From the manifold located above the front door it is directed into the fir...

Page 26: ...e loading door s Allow this start up fire to burn for a few minutes keeping the bypass damper open Add about five more pieces of wood in the 2 to 3 inch 50 80mm size range making sure that the fuel be...

Page 27: ...of 900 F 1100 F indicate that the stove is normally ready for Firedome mode With the Firedome engaged temperatures of 500 F 800 F indicate the unit is burning properly and no adjustment is necessary...

Page 28: ...years of trouble free service Contact your dealer to answer questions regarding proper operation trouble shooting and service for your appliance Visit www harmanstoves com to find a dealer We recommen...

Page 29: ...lass should be obtained only through your Harman dealer To replace a broken glass first be sure to carefully remove the broken glass and any remaining shards or pieces With the door laying on a flat s...

Page 30: ...ousing Alternately with some minor disassembly you can use a vacuum and or brush to clean the blower wheel Reinstall the blower and tighten the four bolts securely 5 Chimney Connector Frequency As nec...

Page 31: ...d Wood Only Harman TL2 6 Owner s Manual_R25 2011 ___ 09 15 Variable Speed Switch Power Cord Blower Thermostat Grounded to housing Black Wire White Wire 2 1 TL2 0 TL2 6 Optional Blower Kit 1 00 856002...

Page 32: ...9 15 Service Parts TL2 6 W Pedestal Beginning Manufacturing Date Sept 2011 Ending Manufacturing Date Active Part number list on following page Wood Stove 1 90 857000 1 2 3 1 4 5 6 7 8 9 10 11 13 12 14...

Page 33: ...Damper gasket 30 ft 1 00 00888 Y Damper Shaft Retainers Hardware Set of 2 1 00 249145 Y Damper Only 1 10 249107 Gasket 1 Single Ply Tape 10 Ft 1 00 88100 Y 5 Firedome Plus Combustion Package with Gask...

Page 34: ...an 1 10 857002A Y 22 Combustion shoe brick 3 40 00100 Y Shoe brick gasket 3 44 06951 Y 23 Side brick insulation Qty 2 req 3 40 857054 Y 24 Right side panel painted 2 00 857021B Y 25 Heat shield mounti...

Page 35: ...30 1110 100 Y Cap Screw 5 16 18 x 1 2 Grade 5 Zinc Plated Hex Pkg of 50 3 30 1122 50 Y Cap Screw 1 4 20 x 3 8 Grade 5 Zinc Hex Pkg of 25 3 30 1106 25 Y Cap Screw 5 16 18 x 3 4 Grade 8 Plain Finish Hex...

Page 36: ...Service Parts TL2 6 w Legs Beginning Manufacturing Date Sept 2011 Ending Manufacturing Date Active Part number list on following page Wood Stove 1 90 858000 1 08 15 1 2 3 7 6 5 4 8 9 10 11 12 13 14 1...

Page 37: ...Wooden handle for damper w hardware Pkg of 2 1 00 00249 Y 6 Damper Elbow painted 3 50 00500S Y 7 Damper shaft bushing plates w hardware Inner outer 1 00 856061 Y 8 Damper rod weldment 1 10 856011W Y...

Page 38: ...ntrol weldment 1 10 856004W Y 22 Air slide 1 10 856003W Y 23 Shoe brick gasket 3 44 06951 Y 24 Bottom Heat Shield 1 00 857056 25 Queen Ann Leg painted w Hardware Qty 4 req 1 00 7000551 Y 26 Right side...

Page 39: ...1110 100 Y Cap Screw 5 16 18 x 1 2 Grade 5 Zinc Plated Hex Pkg of 50 3 30 1122 50 Y Cap Screw 1 4 20 x 3 8 Grade 5 Zinc Hex Pkg of 25 3 30 1106 25 Y Cap Screw 5 16 18 x 3 4 Grade 8 Plain Finish Hex P...

Page 40: ...In the case of new home construction warranty coverage begins on the date of first occupancy of the dwelling or six months after the sale of the product by an independent authorized HHT dealer distrib...

Page 41: ...ED ABOVE WARRANTY EXCLUSIONS This warranty does not cover the following Changes in surface finishes as a result of normal use As a heating appliance some changes in color of interior and exterior surf...

Page 42: ...Save These Instructions 3 90 08570 Harman TL2 6 Owner s Manual_R25 2011 ___ 09 15 Service Maintenance Log Date Of Service Performed By Description Of Service...

Page 43: ......

Page 44: ...________________________________________________________________________________ ________________________________________________________________________________ _____________________________________...

Reviews: