C. Floor Protection Requirements
Floor Protection Requirements
If the appliance is being installed on a combustible floor, non-
combustible floor protection must be installed.
When installing the four-legged model (#1-90-858000-1), the
included bottom heat shield must be in place when installing
on a protected combustible floor.
Do not block or restrict the airflow under the appliance.
In all installations, the area under and around the stove must
be protected from falling ash and live coals.
The area under a
horizontal run of chimney connector must also be protected,
extending two (2) inches beyond the measurement of the
horizontal connector.
Further guidelines for floor protection are as follows:
In the U.S. the floor protector must be completely under the
stove, and extending 18" in front of the door opening, 8" to
each side of the door opening, and 8" to the back.
In Canada, the floor protection must extend 18" (457mm) in
front of the door opening, and 8" (203mm) to each side of
the appliance, and to the rear.
Minimum Size floor protection (USA) is 49-13/16" Deep by
32-1/2" Wide.
Floor protection touching the wall: 59-9/16" Deep x 32-1/2"
Wide.
The appliance pedestal or legs may not be removed for
installation.
Parallel versus Corner Installations
A parallel installation is one in which the back and sides of
the stove are parallel to the walls behind and to the side of
the stove. A corner installation is one in which the back of the
stove is positioned diagonally across a corner of the room.
Each installation requires its own set of clearances.
For corner installations, the required clearance distances
from the stove are:
1. to the side wall, 14-1/2" (330mm).
2. From the flue connector to the wall, 23" (584mm)
3. Horizontal pipe to the ceiling, 15" (381mm).
NOTE:
For a vertical chimney connector in a parallel
installation the distance of the connector to the side wall
must be 27" (686mm), due to the required side clearance of
the stove itself. Fireplace installations must meet these same
clearance requirements; specifically follow these guidelines
for mantel and trim clearances.
For corner installations, the clearance distances are 14-1/2"
(368mm) from each corner of the stove measured straight
back to the nearest combustible material, and 23" (584mm)
from the chimney connector to the walls. To stay within these
clearances and have the floor protector touch the interior
wall it must be a hearth pad size of 60" x 60" (USA ONLY).
Alternate floor protector dimension may be used as
long as they satisfy the measurement requirements
shown above.
J
J
K
L
Type I or Type II floor protection can be used.
*Floor protection dimensions for the front and sides are
measured from the appliance door opening in The United
States. In Canada, the side dimension is measured from the
widest part of the appliance.
60”
60”
Interior Wall
Interior W
all
Minimum size floor protection for a corner installation hearth
pad is 51-3/16" x 32-1/2" (USA ONLY). NOTE: Floor protector
WILL NOT touch the wall.
Floor Protection
Requirements
US
Canada
J
Sides
8"
203mm
K
Front
18"
457mm
L
Rear
8"
203mm