Harman® • P35i-C Installation Manual_R2 • 2019 -___ • 02/20
24
8390-784i
Figure 5.13
Room sensor placed here gives an accurate measure of return
air. Push the pre-cut hole inward, and feed the sensor from the
back side. Allow the bulb of the sensor to extend approximately
1-1/2" into the room. Use a wire tie on the push-in tab to secure
the sensor wire.
H. Flame Guide Extension
Once the flame guide is installed the Flame Guide Extension
should be installed by sliding it in behind the flame guide as
shown below. Notice the bend points away from the Heat
Exchanger.
Burn Pot
Cast Flame Guide
Steel Flame Guide Extension
Heat Exchanger
Bends away from heat Exchanger
Figure 5.14
Once the location has been decided, run the wiring to the
control panel. You'll need to remove the two terminals from
the end of the sensor cable and replace them with the two
smaller terminals from the hardware bag. Plug the terminals
into the control board. These connections are not polarity
specific.
Note:
If the room sensor is located too close to the appliance,
or in a direct path of the distribution air, You may need to
elevate the temperature setting to maintain a comfortable
temperature level throughout the heated space.
See Section "E. Draft Test Procedure" under Operating
Instructions.