Harman® • Allure50 Installation Manual_R2 • 2016 - ___ • 09/16
9
3-90-888000i
Floor Protection
Requirements
US
Canada
J
Sides
6"
152mm
K
Front
6”
152mm
L
Rear
1”
25mm
E. Floor Protection
Parallel Installation:
Place the stove on a noncombustible floor or floor protector
that extends a minimum of 6” (152mm) to the front of the load
door opening, 6” (152mm) to the sides of the door opening,
and 1” (25mm) to the rear. Floor protection must also extend
2” (51mm) beyond each side of any horizontal flue pipe. The
minimum floor protector material is 20 gauge sheet metal.
Other floor protector materials are ceramic tile, stone, brick,
etc. Figure 3.3
Minimum Size floor protection is 25-5/8” wide By 25-3/8”
deep (651mm X 645mm).
*Floor protection dimensions for the front and sides are
measured from the appliance door opening in The United
States. In Canada, the side dimension is measured from the
widest part of the appliance.
F. Mobile Home Installation
When installing this unit in a mobile home, several
requirements must be followed:
1. The unit must be bolted to the floor. This can be done
using an appropriate fastener for the application.
2. The unit must be connected to an outside combustion
air inlet
. Proper supports and spark arresters must be
considered when installing venting. See “Termination
Location and Vent Information” Section D.
3. Floor protection and clearances must be followed as
shown.
4. Unit must be grounded to the metal frame of the mobile
home.
Note:
Use silicone or other sealant to create an effective vapor
barrier when the venting system or outside air duct passes
through to the exterior of the structure.
Figure 3.3
J
K
L
F
loor
protector
L
Install lag bolts here.
F
loor
protector
Figure 3.4
Corner Installation:
Minimum size floor protection for a corner installation hearth
pad is 25-5/8” wide By 25-3/8” deep (651mm X 645mm)
.
Note: Floor protector WILL NOT touch the wall using
minimum clearances.
If corner floor protection is desired to touch the wall, the
floor protection will need to be at least 40” x 40” (1016mm
x 1016mm).
Note: This will allow the floor protection to
touch the wall as shown. Figure 3.4
.
Alternate floor protector dimension may be used as long as
they satisfy the measurement requirements.