background image

33

Trouble-Shooting

Cleaning burn Pot

Whenever your stove is not burning, take the oppor-

tunity to scrape the burn pot to remove carbon buildup. 

A vacuum cleaner is handy to remove the residue. Be 

sure the stove is cold if you use a vacuum.

Carbon buildup can be scraped loose with the fire 

burning using the special tool provided with your stove. 

Scrape the floor and sides of the burn pot. The carbon 

will be pushed out by the incoming fuel. Always wear 

gloves to do this.

Removing Ashes

Turn the Temp Dial to number 1 approximately 30 

minutes  before  removing  ashes. This  will  result  in  a 

cooler stove and ash pan.

Maximum  Feed Adjuster  settings  are  not  needed 

in most cases. Operating in the normal range (#4) is 

recommended when maximum heat output is not re-

quired. The ESP probe prevents the stove from being 

over-fired.

Keep the stove free of dust and dirt.

Helpful Hints

Fuel

  STOvE dOES NOT FEEd

1. No fuel in hopper.

2. Firebox draft may be too low for sensing switch in 

feeder circuit to operate. 

Check for closed doors

loose or missing gasket on doors or hopper lid.

3. Hopper lid must contact the lid position switch.

4. Feed motor will not run until the ESP control 

senses a certain temperature. Maybe you did not 

put enough fuel or starting gel in the burn pot before 

manually lighting the fire.

5. Restriction in the hopper or feeder. Remove all 

fuel and examine. Clear the obstruction.

6. Feed motor has failed.

PArTIAllY burNEd PEllETS

1. Feed rate too high.

2. Poor air to fuel mixture. (Check burn pot clean-

out cover and air intake).

3. Burn pot or heat exchanger tubes may need  to 

be cleaned.

4. Combination of all the above.

5. 

#6 status blink

: A 6 blink control board status 

indication is caused by poor or incomplete combus-

tion. The circuit board has the ability to track the 

combustion through feed settings and ESP tem-

peratures. When the control board has calculated 

poor or incomplete combustion, it will shut down 

the unit as a safety feature. (Poor or incomplete 

combustion is a contributor of creosote which may 

cause a chimney fire)

A  6  blink  status  may  be  caused  by  several 

things:

1. Blocked or partially blocked flue.

2. Blocked or partially blocked inlet air.

  a. Backdraft damper on the inlet pipe may be 

stuck closed.

  b. If outside air is installed, the inlet cover may 

be blocked.

3. The air chamber under the burnpot may be filled 

with fines and small bits of ash.

4. The holes in the burnpot may be getting filled 

with ash or carbon buildup.

5.  Combustion  blower  fan  blades  may  need 

cleaned.

6. Fuel restrictions as noted above.

SmOkE SmEll

Seal the vent pipe joints and connection to stove 

with silicone. The exhaust vent is the only part of 

the system that is under positive pressure.

FIRE HAS GONE OUT- Check for status light.

1. No fuel in hopper.

2. Draft is too low, blocked flue.

3. Something is restricting fuel flow.

4. Hopper lid not closed properly.

5. Feed motor or combustion blower has failed.

SmOkE IS vISIblE COmINg OuT OF vENT

1. Air-fuel ratio is too rich.

  A. Feed rate too high.

  B. Draft too low caused by a gasket leak.

 

lOw hEAT OuTPuT

1. Feed rate too low

2. Draft too low because of gasket leak.

3. Poor quality or damp pellets

4. Combination of 1 and 2.

The Accentra is approved for burning any grade 

of pelletized bio-mass fuel. It is also approved for burn-

ing shelled corn in a mixture with wood pellets, up to 

50%.(See Page 46)

It should be noted, however, that higher ash con-

tent will require more frequent ash removal, scraping of 

the burn pot, and may provide less BTU's per pound. 

The moisture content of pellets must not exceed 

8%, and corn must not exceed 15%. Higher moisture 

will rob BTU's and may not burn properly.

Fuel should 

not 

be stored within the stove installa-

tion clearances or within the space required for charg-

ing and ash removal. See Page 14.

Summary of Contents for Harman Accentra Insert

Page 1: ...ALLATION INSPECTION REQUIREMENTS IN YOUR AREA Contact your local authority such as municipal building department fire department fire prevention bureau etc to determine the need for a permit Cette gui...

Page 2: ...SAMPLE HEARTH HOME TECHNOLOGIES 09 3178 FOR USE WITH PELLETIZED WOOD FUEL OR UP TO A 50 CORN AND PELLET MIXTURE ONLY...

Page 3: ...esired temperature and walk away The Accentra insert lights automatically brings the room up to the exact temperature and will turn off if no heat is required No other pellet insert offers such accura...

Page 4: ...gniter element to operate if the view door is open 4 Adjust Feed Rate If this is your first fire or you are trying different pellets set the feed adjuster to 4 Fig 1 This is a conservative number and...

Page 5: ...temperature Therefore as it gets colder more pellets will be burned automati cally The distribution blower speed will vary according to the position of the mode selector pointer and fire size Igniter...

Page 6: ...w the auger motor or the igniter element to operate if the view door or the hopper lid are open 4 Adjust Feed Rate If this is your first fire or you are trying different pellets set the feed adjuster...

Page 7: ...n with the temperature dial set at 4 or less the distribution fan will not operate A 4 on the temperature dial and a 4 on the feed adjuster is ap proximately 80 output It is not necessary to operate t...

Page 8: ...ors at full speed for one minute to check operation After two minutesthestovewill go to minimum burn and the blowers will alternate from high to low every minute to remind you that you are still in Te...

Page 9: ...l the cast top and lid assembly down onto the hopper gasket to seal the hopper They also allow for a small amount of front to back adjustment for alignment of the top into the wing pockets Internal Ca...

Page 10: ...in place Note The heat exchanger covers will tilt to the front when the center medallion is removed l Removing the Heat Exchanger Covers Remove the heat exchanger cover by lifting it upward about 1 2...

Page 11: ...nd right side wings should be standing up aligned with the side of the mounting frame and slid inward towards the center Note The wings mount on the rear side below the notch and on the front side abo...

Page 12: ...lace face 6 You must now decide whether to install the room sensor as a wall sensor or as a return air sensor Harman highly recommends that the room sensor be installed If you are installing the room...

Page 13: ...in fig 24 Wire tie the sensor end so that the sensing tip is in the middle of the front return air opening See Fig 25 Wire tie the sensor wire to the inside of the mounting frame up to the cord groun...

Page 14: ...recommendations Installation Flue Pipe Stub Assembly There are three different flue pipe stubs available 1 The unit comes standard with the largest for use with 4 stainless steel flex pipe 2 Part 1 0...

Page 15: ...is latched into place and the front door is closed Connecting the power cord The white from the mounting frame connects to the white of the insert body The black from the mounting frame connects to t...

Page 16: ...ns that the gasket is not sealing properly Fig 36 19 Inspect the silicone sponge gasket on the top edge of the hopper If it is okay put the cast top hopper lid assembly see Fig 35 into place over the...

Page 17: ...ls open and close freely for control board access 22 Slide the stove body into the mounting frame Note The two spring latches on the bottom right and left side of the body must be in the proper positi...

Page 18: ...n area This is the area that comes closest to the mounting frame as the unit is slid in and out of the frame 11 pin socket on rear of control board 6 amp g l a s s fuse Fig 40 Hopper lid foam gaskets...

Page 19: ...lit check and record the high and low draft readings A simple draft test should be performed after completing the flue pipe installation To record the results for future reference 1 Plug unit into a...

Page 20: ...ile home several requirements must be followed 1 The unit must be bolted to the floor This can be done with 1 4 lag screws through the 5 holes in the base plate shown in Fig 26 2 The unit must also be...

Page 21: ...product warranty and may pose a hazard Do Not Install A Flue Damper In The Exhaust Venting System Of This Appliance DO NOT CONNECT THIS UNIT TO A CHIMNEY FLUE SERVING ANOTHER APPLIANCE Avoiding Smoke...

Page 22: ...e vent pressure we specify that the joints also be sealed with silicone Where passing through an exterior wall or roof be sure to use the appropriate pass through device provid ing an adequate vapor b...

Page 23: ...chimney Fig 49 Height of existing hearth Thechimneytopmustbecapped to prevent rain and or snow from entering the chimney See Page 22 for information on the optional Harman Adjustable Stainless Steel...

Page 24: ...ht of over 30 feet A 3 or 4 PL vent pipe should be used with the needed swivel flue stub NOTE The flue stub insulation wrap must still be used with this method See page 14 Fig 27 29 With a 100 outside...

Page 25: ...itted to remove the floor refractory and or insulation in the bottom of the manufactured fireplace right down to the outer sheet metal which must be left in place for floor protection under the insert...

Page 26: ...Insert Zero Clearance Cabinet Be sure to use ap proved pellet vent pipe wall and ceiling pass through fittings to go through com bustible walls and ceilings Be sure to use a starting collar to attach...

Page 27: ...or siding NOTE Only PL or L vent pipe wall pass throughs and fire stops should be used when venting through combus tible materials NOTE Always take into consideration the effect the prevailing wind di...

Page 28: ...placed in a metal container with a tight fitting lid The closed container of ashes should be placed on a non combustible floor or on the ground well away from all combustible materials pending final...

Page 29: ...Figure 60 The igniter is made to be removable for service by insulated male female wire connectors These connections between the hot leads the wires inside the burn pot and the cold leads the wires f...

Page 30: ...h a vacuum if necessary Note The bottom of the flame guide has 2 notches that match the holes Cleaning the Heat Exchanger tubes Using the cleaning brush provided clean these tubes after every 1 ton of...

Page 31: ...e by pulling it directly away from the blower housing The cord on the motor is long enough to allow the motor to be set down on the black plastic fan cover This allows for easy access to inspect and c...

Page 32: ...sends a status alert and at the same time the unit goes down to minimum feed minimum burn as a safety condition Accentra Insert Motor Component Locations Accentra Pellet Insert Safety Devices Backdra...

Page 33: ...ion through feed settings and ESP tem peratures When the control board has calculated poor or incomplete combustion it will shut down the unit as a safety feature Poor or incomplete combustion is a co...

Page 34: ...side Air Size 3 inches Fuse Rating 6 amp BTU Range 0 to 42 000 Feed Rate 75 lbs hr on minimum on maintenance 5 lbs hr on maximum Vent Size 4 inch Pellet Vent Pipe standard 3 inch Pellet Vent Pipe opti...

Page 35: ...8 3 10 Amp POWER CORD ROOM SENSOR Wire W H I T E N O CONTACTS LOW PRESSURE SWITCH BLUE WHITE WHITE GREEN RED SKY BLUE N O CONTACTS BONDED TO STOVE BODY WHITE BLACK MALE FEMALE CONNECTIONS GREEN WIRE I...

Page 36: ......

Page 37: ......

Page 38: ...674 2 Charcoal 1 90 00674 3 Goldenfire 1 90 00674 4 Metallic Blue 1 90 00674 5 Honey Glo 1 90 00674 10 Mojave Red 1 90 00674 12 Forest Green 20 Hopper 1 90 00676 1 Black 1 90 00676 2 Charcoal 1 90 006...

Page 39: ...order Switch retrofit Kit 1 10 01782A Y 1 00 232108 Y Post 008244667 1 10 01782A Y Feeder Hopper Assembly Height 24 Pre 008240096 1 10 674063A Y 008240096 thru 008244667 Must also order Switch retrofi...

Page 40: ...f 4 1 00 674083 24 Cast Top 4 00 674055A 25 Cast Wing Left 4 00 674056P Y 26 Door Assembly 4 00 674053A Y 27 Cast Bottom Ashlip 3 00 674051P 28 Cast Side Panel Qty 2 Req 4 00 674054P 29 Cast Wing Righ...

Page 41: ...4 Slide Plate Assembly 1 10 08037 Y 37 5 Pusher Arm Assembly 1 10 773890 Y 37 6 Feed Cover and Gasket 2 Sets 1 00 677152 Y 37 7 Auger Assembly 3 50 00465 Y 37 8 Cam Bearing 3 31 3014 Y 37 9 Bearing Fl...

Page 42: ...der Air Intake 1 10 674130 38 7 Gasket Ultra Air Intake Pkg of 10 3 44 677160 10 Y 38 8 Ultra Feeder Weldment 1 10 724132 Y 38 9 UL Feeder Pusher Arm 1 10 677131W Y 38 10 Fines Deflector Pkg of 10 2 0...

Page 43: ...86 Y Combustion Box Insulation Cover 2 00 674038B Combustion Blower Box Insulation Side 3 44 674037 D Shape Knob Shaft 25 Sets 1 00 015605 Y Door Latch 3 00 249119 Y Fan Blade 4 3 4 Single Paddle Comb...

Page 44: ...44 Service Maintenance Log Date Of Service Performed By Description Of Service...

Page 45: ...eration Your appliance will recognize when power is restored What happens depends on ESP temperature and whether it is equipped with automatic ignition x In Automatic setting units equipped with autom...

Page 46: ...Set temperature knob to desired amount Turn mode selector knob onto Room Temp mode After the fire has lit watch that the fuel does not feed too fast that it pushes the red glowing fuel bed off of the...

Page 47: ......

Page 48: ...Proudly Printed On 100 Recycled Paper...

Reviews: