![Hardy Instruments A Series Operation And Installation Manual Download Page 44](http://html.mh-extra.com/html/hardy-instruments/a-series/a-series_operation-and-installation-manual_597396044.webp)
HI 1756-WS WEIGH SCALE MODULE
4-16
Structure
(ITECHTEST)
Structure
Item
Description
DINT
command*
0x66
DINT
channel*
0 or 1
DINT
status*
N/A
DINT
nSensors*
Number of load sensors.
REAL
BaseR
Load cell impedance measured during Calibration
REAL
ReadR
Impedance measured at test time
DINT
TestR
Test Result: Good = True, Bad = False
REAL
Vsense
Sense Voltage from the load cells
REAL
loadcell current
Load Cell Current
DINT
RTZ_R_combined
Test result, return to zero, all load cells
DINT
RTZ_R_1**
Test result, return to zero, load cell 1
DINT
RTZ_R_2**
Test result, return to zero, load cell 2
DINT
RTZ_R_3**
Test result, return to zero, load cell 3
DINT
RTZ_R_4**
Test result, return to zero, load cell 4
REAL
DVM_combined
Millivolts/Volt, all load cells
REAL
DVM_1**
Millivolts/Volt, load cell 1
REAL
DVM_2**
Millivolts/Volt, load cell 2
REAL
DVM_3**
Millivolts/Volt, load cell 3
REAL
DVM_4**
Millivolts/Volt, load cell 4
REAL
IREF_weight
Internal reference counts, converted into a weight
REAL
JBOXREF_weight
JBOX reference counts, converted into a weight
REAL
grossweight
Combined Gross Weight, all load cells
REAL
weight_1**
Gross Weight, load cell 1
REAL
weight_2**
Gross Weight, load cell 2
REAL
weight_3**
Gross Weight, load cell 3
Summary of Contents for A Series
Page 14: ...HI 1756 WS WEIGH SCALE MODULE 1 6 ...
Page 28: ...HI 1756 WS WEIGH SCALE MODULE 3 10 ...
Page 52: ...HI 1756 WS WEIGH SCALE MODULE 4 24 ...
Page 62: ...HI 1756 WS WEIGH SCALE MODULE 6 2 FIG 6 2 DISCRETE DATA ...
Page 72: ...HI 1756 WS MANUAL 7 10 ...
Page 80: ...HI 1756 WS MANUAL Write Parameters WRITEPARAM 4 18 Z Zero Command ZEROCMD 4 12 ...