Calculating Total Wattage of Devices Used with the Generator

Before using the Generator, check that the products 

you want to plug into the unit are below the rated and 

maximum wattage ratings of the Generator.  Use the 

Wattage Calculation Table below, and the watts listed on 

your products, to help calculate multiple wattage totals.

To use the table:

1.  Add up the Running Watts for all items you 

would like to use at any given time.

2.  Make sure that this total is under the 7,250 

running wattage of the Generator.

3.  Find the single highest starting watts for 

the selected items and add to the total. 

4.  Make sure that this total is under the 9,000 

max. starting wattage of the Generator.

5.  Plug in and turn on products from 

largest wattage to smallest.

Wattage Calculation Table

Equipment

Running

Watts

Total Running Watts  

(must be less than 7,250)

Largest Additional Start-up Watts

Total Startup Watts needed for all loads 

(must be less than 9,000)

Example

Equipment

Running

Watts

Electric Water Heater (2,000 + 0)

2,000

Television (400 + 0)

400

Lawn Mower (1,200 + 1,200)

1,200

Hand Drill (600 + 600)

600

Total Running Watts  

(must be less than 7,250)

4,200

Largest Additional Start-up Watts

1,200

Total Startup Watts needed for all loads 

(must be less than 9,000)

5,400

A generator that is rated more than the minimum 

required max. starting watts will last much longer than 

a generator that only supplies the exact watts needed.

To Calculate Wattage: 

Volts and amps can be multiplied together 

to get watts (volts x amps = watts).

To Calculate Additional Start-Up Watts  

(If They Are Not Listed) 

For equipment with a motor:  Use the rated watts 

amount as an estimate of additional Start-up Watts.

For most lights or heaters: 

there are no additional start-up watts.

Wattage Estimate Charts

Note:

 Wattages listed below are estimates for that 

type of equipment only. Check nameplate wattages 

on all loads before connecting to Generator.

EMERGENCY

Device

Running 

Watts

Additional 

Start-up 

Watts

Refrigerator/Freezer

700

1500

Radio

100

0

JOB SITE

Device

Running 

Watts

Additional 

Start-up 

Watts

Air Compressor - 1/2 HP

1000

1000

Table Saw - 10″

1700

1300

Belt Sander - 3″

1200

1200

Hand Drill - 1/2″

600

600

Halogen Work Light

1000

0

Recipricating Saw

900

900

RECREATION

Device

Running 

Watts

Additional 

Start-up 

Watts

AM/FM Radio

100

0

Electric Grill

1700

0

Inflator Pump

50

100

CD/DVD Player

100

0

Box Fan - 20″

200

200

Coffee Maker

600

0

HOUSEHOLD

Device

Running 

Watts

Additional 

Start-up 

Watts

Computer w/ Monitor

800

0

Electric Clothes Dryer

5500

500

Electric Range

2100

0

Electric Water Heater

2000

0

Light Bulb - 100 watts

100

0

Microwave - 1000 watts

1000

200

Sump Pump - 1/2 HP

1000

1100

Television

400

0

Washing Machine

1100

1100

Well Pump - 1/2 HP

1000

1000

LAWN & GARDEN

Device

Running 

Watts

Additional 

Start-up 

Watts

Hedge Trimmer

400

400

Pressure Washer

1200

1200

Lawn Mower

1200

1200

Edger

1000

1000

HEATING & COOLING

Device

Running 

Watts

Additional 

Start-up 

Watts

Central AC - 10,000 BTU

1500

1500

Furnace Fan - 1/2 HP

900

1400

Space Heater

1800

0

Window AC - 10,000 BTU

1200

600

Summary of Contents for PREDATOR 59134

Page 1: ...nce 22g Using a generator indoors CAN KILL YOU IN MINUTES Generator exhaust contains carbon monoxide This is a poison you cannot see or smell NEVER use inside a home or garage EVEN IF doors and window...

Page 2: ...ken Access shall be through the use of a special tool or lock and key or other means of security and shall be controlled by the authority responsible for the location 2 Gasoline fuel and fumes are fla...

Page 3: ...llow carbon monoxide to accumulate FLASHING RED LIGHT Dangerous levels of carbon monoxide gas have built up and generator will shutoff Leave immediately until area has aired out Move Generator to well...

Page 4: ...placed f Press Reset button in for use The Generator must be grounded before use An ungrounded Generator has an increased risk of electric shock Refer to Grounding on page 9 19 Insulate all connection...

Page 5: ...moving parts breakage of parts and any other condition that may affect the Generator s operation If damaged have the Generator serviced before using Many accidents are caused by poorly maintained equ...

Page 6: ...rrectly 9 Store equipment out of the reach of children 10 Follow scheduled engine and equipment maintenance GFCI Protection This Generator is equipped with two 3 Prong duplex 120V ground fault circuit...

Page 7: ...line Capacity 7 79 Gallon 29 50 Liter Engine Oil Type SAE 10W 30 above 32 F 5W 30 at 32 F or below Capacity 1 Quart Spark Plug Type NHSP Torch F6TC Gap 0 028 0 031 Valve Clearance Intake 0 004 0 006 E...

Page 8: ...ptacle 120 volt or 240 volt that is compatible with the electrical characteristics and rated capacities of the tools and equipment being used ON OFF 3 Circuit Breakers The circuit breaker protects the...

Page 9: ...intended to power sensitive electronic equipment without the addition of an appropriate line conditioner and surge protector both not included Sensitive electronic equipment includes but is not limite...

Page 10: ...ns are as follows Use one of the following as the grounding electrode Pipe or conduit minimum in diameter minimum 8 ft long If steel it must have anti corrosion coating Rod stainless steel or copper o...

Page 11: ...wl under the fuel cup to catch any spilled fuel 5 Unthread the screws holding the solenoid in place CAUTION Carburetor bowl may have gas in it which will leak upon removing the solenoid bolt 6 Disconn...

Page 12: ...out threading it in and remove it to check the oil level The oil level should be up to the full level as shown above 5 If the oil level is at or below the low mark add the appropriate type of oil unti...

Page 13: ...If above test fails do not use receptacle until it is repaired or replaced d Press Reset button in for use RESET TEST RESET TEST Reset Button Test Button 120 Volt GFCI Receptacle 4 Plug in products 5...

Page 14: ...t the engine can stabilize For MANUAL START A Turn the Engine Switch to ON B Grip the Starter Handle of the Engine loosely and pull it slowly several times to allow the gasoline to flow into the Engin...

Page 15: ...rated capacity for this Generator as serious damage to the Generator and or appliances tools and equipment could result from an overload Starting and running wattage requirements should always be cal...

Page 16: ...r that only supplies the exact watts needed To Calculate Wattage Volts and amps can be multiplied together to get watts volts x amps watts To Calculate Additional Start Up Watts If They Are Not Listed...

Page 17: ...gine in an emergency turn the Engine Switch off NOTICE Generator shut off under load may damage the Generator and attached equipment Stopping the Engine Under Normal Conditions 1 Before turning off th...

Page 18: ...qualified technician service the equipment instead Cleaning Maintenance and Lubrication Note This maintenance schedule is intended solely as a general guide If performance decreases or if equipment o...

Page 19: ...Remove the drain plug and if possible tilt the crankcase slightly to help drain the oil out Recycle used oil 5 Replace the drain plug and tighten it 6 Clean the top of the Dipstick and the area around...

Page 20: ...r back in place immediately after cleaning and before further operation Long Term Storage When the equipment is to remain idle for longer than 20 days prepare the Engine for storage as follows 1 CLEAN...

Page 21: ...xposure to rain and sunlight NOTICE During extended storage periods the Engine must be started every 3 months and allowed to run for 15 20 minutes or the Warranty is VOID 6 AFTER STORAGE Before starti...

Page 22: ...ilter IGNITION SPARK RELATED 1 Power Switch at OFF position 2 Spark plug cap not connected securely 3 Spark plug electrode wet or dirty 4 Incorrect spark plug gap 5 Spark plug cap broken 6 Circuit bre...

Page 23: ...y operate generator outside 2 Carbon monoxide sensor malfunction Sensor needs service Call 1 888 866 5797 as soon as possible Do not use the Generator until the sensor is working properly 3 Make sure...

Page 24: ...er Plug in product and turn on 3 Turn off and unplug product Test GFCI receptacle If functioning properly reset GFCI plug in product and turn on 4 Have product repaired Product begins to operate abnor...

Page 25: ...TS LIST AND ASSEMBLY DIAGRAM IN THIS MANUAL AS A REFERENCE TOOL ONLY NEITHER THE MANUFACTURER OR DISTRIBUTOR MAKES ANY REPRESENTATION OR WARRANTY OF ANY KIND TO THE BUYER THAT HE OR SHE IS QUALIFIED T...

Page 26: ...52 Muffler Vent Shield 1 53 Muffler Gasket 1 54 Flanged Hex Bolt 2 55 Tank Vibration Dampeners 4 56 Bushing 4 57 Flat Washer 4 Part Description Qty 58 Flanged Hex Bolt 4 59 Fuel Level Gauge 1 60 Phil...

Page 27: ...ng Rod 1 137 Steel Cable Baffle Ring 2 138 Piston 1 139 Piston Pin 1 140 Piston Ring Assembly 1 141 Camshaft Assembly 1 142 Valve Lifter 2 Part Description Qty 143 Push Rod 2 144 Crankcase Body 1 145...

Page 28: ...Page 28 For technical questions please call 1 888 866 5797 ITEM 59134 Safety Setup Operation Maintenance Assembly Diagram 1...

Page 29: ...Page 29 For technical questions please call 1 888 866 5797 ITEM 59134 Safety Setup Operation Maintenance Assembly Diagram 2...

Page 30: ...f Road Engine In California new equipment that uses small off road engines must be designed built and equipped to meet the State s stringent anti smog standards HFT must warrant that the emissions con...

Page 31: ...shipping the product for repair 5 Notwithstanding the provisions herein warranty services or repairs will be provided at all retail stores or by contacting HFT product support at 1 888 866 5797 or pr...

Page 32: ...26677 Agoura Road Calabasas CA 91302 1 888 866 5797...

Reviews: