Programmable Temperature & Humidity Controller
62
Zone D
Zone C
Zone B
Zone A
Low
temperature
High
temperature
Setting item
Function
L.SV
Low set value
Set lower limit.
M.SV
Middle set value
Set median.
H.SV
High set value
Set upper limit.
Lu
Low limit deviation setting
Set lower limit offset.
Hd
High limit deviation setting
Set upper limit offset.
T1~T4
Temperature 1~4
Zone setting by temperature-side group (Group 4)
H1
H
Zone setting for humidity side (Group 1)
Zone separation
Description
Zone A (PV≥H.SV)
Always OFF regardless of offset
Zone B
(M.SV≤PV≺H.SV)
1) Hd=0(Always OFF regardless of offset)
2) Hd≠0(Refer to Fig. 91). OFF : PV≺SV+Hd ON : PV≥SV+Hd
Zone C
(L.SV≤PV≺M.SV)
1) Lu=0(Always ON regardless of offset)
2) Lu≠0(Refer to Fig. 92). OFF : PV≤SV-Lu ON : PV≻SV-Lu
Zone D (PV≺L.SV)
Always OFF regardless of offset
By L.SV, M.SV, and H.SV, the range has 4 zones: A, B, C, and D.
Setting condition is L.SV < M.SV < H.SV.
Temperature
Temperature
Time
Time
Setting value
Lower limit
Measurement
Setting value
Higher limit
Measurement
Output
Output
Temperature
Temperature
Time
Time
Setting value
Lower limit
Measurement
Setting value
Higher limit
Measurement
Output
Output
Fig. 90) ON/OFF zone separation
Fig. 91) Zone setting 1
Fig. 92) Zone setting 2