※ Time Signal-3 (TS3) is activated (ON) at the beginning of the Segmen-1 and deactivated (OFF)
after 30 minutes. No more segments exist so that TS is inactive (OFF) thereafter.
※ Time Signal-4 (TS4) is activated (ON) after 30 minutes from the beginning of the Segment-3, and deactivated
(OFF) after 4 hours. The length of OFF TM is longer than 1 hour so that the output continues to the next segment.
※ Time Signal 5 (TS5) is inactive (OFF). TS is not used.
●
Start Set Value
•The starting conditions of each
program vary depending on
Start Mode.
1) Start Mode (ST.MD)=SSV: Start at SV
•In SSV mode, the program will begin with at a specified
temperature (Start Set Value) regardless of PV.
•And the program will ramp to the SV1 over the time
designated in Time Segment-1(TM1).
① First Soak at Segment-2:
•If PV is in a ~ c : Segment-1 is ignored and the program will start
at the beginning of the first soak (segment-2).
•If PV is in d : The program will start at the Segment-1
(D: PV=SV). In this case, the time designated from
E to D in Segment-1 is ignored, and the program
will run for the time designated from D to C.
2) Start Mode (ST.MD)= PV1: Start at PV (Pattern)
•PV1 mode, the program will start at the PV but it is related to SSV, PV, Soak and n, TM.
(Refer to the Figures below for additional information.)
•If PV is lower than SSV, the program will start at the SSV.
•Soak Segment is present in the program: If PV is higher than Soak SV, the program will start at the Soak Segment.
•Pattern is reversed during the program running: If PV is higher than SV, the program will start at corresponding segment.
•Program starts at the middle of pattern: Time designated in corresponding segment is ignored.
Start Mode
Program Start Behavior
SSV
Start from start setting value
PV1
Start from process value and pattern priority
PV2
Start from process value and time priority
Starting PV at Program Activation Program Start Point
a
C
b
C
c
C
d
D
e
E (SSV)