29
●
Program
1) Programming is to the Figure below.
2) Wait Zone: 3.0 ℃, Wait Time: 30Mins.
1H
1SEG
1H
3SEG
1H 30M
2SEG
200.0
100.0
0.0
TS2
TS1
TS3
TS4
TS5
ON
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
ON
ON
ON
Push SET key at least 3 seconds from Operating Display.
Program from PROG menu G. PRG.
Select Pattern number
• Menu Display Push key : OPERFUCNSTUP PROG display sequentially
• PROG Push key and go G.PRG Push SET key
Select Pattern Number PT.NO = 1. Push SET key to select it.
Select Segment number
• Segment Number SEGNO = 0 display. It means 0 segment.
Push key to select it
Set Wait Zone
• Wait Zone WZ = OFF display. Set WZ=3.0˚C ? by key.
Push key to select it
Set Wait Time
• Wait Time WTM =OFF display. Set WTM=00h 30m ? by and key.
Push key to select it
Set Repeat
• Repeat Set REPEAT= 1 display. Push key to select it
Set Time Signal Mode
• Time Signal Mode TS.MD=ON/OFF 1 display. Set TS.MD=TIME 5 ? by key.
Push key to select it
Set Start Set Value
• Start Set Value ST.SV=-200.0’C display. Set ST.SV=50.0’C ?
by and key.
Push key to select it
Set Start Mode
• Start Mode ST.MD=SSV display. Push key to select it
Set Pattern End Segment • Pattern End Segment END.SEG=OFF display. Push key to select it
Set Pattern End Mode
•Pattern End Mode END .MD = RESET display. Set END.MD=HOLD ? by key.
Push key to select it
Set End Signal Time
•End Signal Time END.TM = OFF display. Push key to select it
* Segment Number Seg.NO=0 display.
Setting finish and set segment parameter Seg.NO = 1~3
Summary of Contents for NP200