※ Output turns ON after the setup time in the ON time mode and the output turns OFF after the setup time of OFF time. 

※ The ON time and OFF time setup of n pattern time signal-2 is the same as the setup method of time signal -1. 

Operation (RUN)

Time signal

ON time

OFF time

1) Selection of Pattern Number :

  NP100 temperature controller can set up pattern 1, and pattern 2. Select “pattern 1” to operate in the setup 
  item of pattern number selection. (Pattern refers to one setup program.)

2) Selection of segment number :

  It is designed to set up to 10 segments for each pattern.  At the beginning, choose “0” segment then 
  set up basic condition of the program.

3) Setup of Start Set Value :

  In the program temperature controller, start temperature value can be set up.  It could either start from the  
  current temperature in the beginning of the first operation of the system or can even start from the 
  set value in the start set value. 

4) Selection of Start Type :

  Select the start conditions when operating the program.
  If process value (PV) is selected, it starts from the currently sensed temperature and if the start set value   
  (SSV) is selected, it starts from the temperature set up in the start set value item. 

5) Setup of n pattern time signal-1 ON time :

  It turns ON after the set time of time signal -1 of already selected pattern. 

6) Setup of n pattern time signal -1 OFF time :

  It turns OFF after the set time of time signal -1 of already selected pattern. 

7) Program Completion Mode :

  ·When pattern 1 is selected as mode upon the completion of pattern 1, the system operates until the 
     program repetition frequency set in the system and then resets. However, when HOLD is selected, the 
     last set value is maintained. 
 ·When pattern 2 is selected upon the completion of pattern 1, patterns 1 and 2 get connected. 
 ·When pattern 1 is selected upon the completion of pattern 2, pattern 1 will be connected.
 ·When pattern 2 is selected upon the completion of pattern 2, it operates repeatedly for the number of RPT 
    frequency.  For example, when selecting the pattern 2 as mode upon completing the program Pattern 1 
    and after setting 3 times for the program repetition frequency, patterns 1 and 2 will be operated once and 
    then the pattern 2 will be operated twice. 

8) Selection of n pattern and n segment PID group number :

 

  PID group can be applied to each pattern and each segment of 4 types of PID group to be controlled. 
  However, stable control result can be acquired when group 1 is operated besides the peculiar situations. 

9) Setup of Target Value :

 

  Set up the target temperature value for each pattern and segment under control.

10) Time Setup of n pattern and n segment :

  Set up the time that reaches or maintains the target temperature value for each pattern and segment under control.  

※ Each segment can set up to 10 segments with the above method.  

Summary of Contents for NP100

Page 1: ...Manual NP100 Programmable Controller...

Page 2: ...IMENSION PANEL CUTOUT 5 INPUT OUTPUT Input Signal and Measurement Range Output type 6 NAME FUNCTION 7 LIST OF SETUP ITEMS 8 SETUP METHOD Program Setup 9 SPECIFICATION Input Function 10 ALARM TYPE CODE...

Page 3: ...essive induction trouble static electricity or magnetic noise 1 If there is a possibility of an accident caused by errors or malfunctions of this product install external protection circuit to prevent...

Page 4: ...of operation is rather high In this case SSR output type is recommended Electromagnetic switch Proportional cycle time is Min 20 sec SSR Proportional cycle time is Min 1 sec Contact output life Mechan...

Page 5: ...d each segment s parameter Feature Function Description Option RS 485 422 Time signal 2 points PV display Digit number 4 digits Accuracy 0 1 Sampling time 250 ms Input type Universal input selectable...

Page 6: ...tion ground wiring Ground connection cable is a thick wire that is over 2 in width Wire with more than the third type ground connection below 100 ground connection resistance The length of the ground...

Page 7: ...1 199 9 999 9 T 1 199 9 400 0 R 0 1700 0 15 of F S 1digit B 2 0 1800 S 0 1700 L 1 199 9 900 0 0 1 of F S 1digit N 200 1300 0 2 of F S 1digit U 1 199 9 400 0 0 1 of F S 1digit W 0 2300 Platinel 0 1390...

Page 8: ...when WAIT is in operation while the program is running on HOLD display lamp Lights when HOLD is in operation while the program is running on MAN display lamp Lights while manually operating AL1 displa...

Page 9: ...the parameter Press 2 5 seconds or longer to alternate the operation indicator mode and the engineering mode Exit running program and convert to stop Exit runing MAN operation and convert to reset mod...

Page 10: ...when the button is pressed continuously Rounding Off 4 Maximum Minimum Indication It indicates the greatest or the least of the selected item when it gets out of the range of the selected item parame...

Page 11: ...indicated in running Operation indicator mode Engineering mode Power ON Process value Set value Process value Output value Display remain time of segment 2 5 sec or PID OFF Displayed in running condit...

Page 12: ...Mode setup is recommended after completing the Program operation since the set value varies in accordance with the setup of the specific parameter Each parameter may not be indicated in accordance wi...

Page 13: ...ss value Output value Display remain time of segment Operation indicator mode PT NO n PT NO 0 We recommend you to use program mode after engineering mode is closed A set up value is changed and initia...

Page 14: ...ch segment s parameter Power ON Press 2 5 second Engineering group Program group 1 Input setup group 8 1 1 8 1 2 8 1 3 8 1 4 8 1 5 8 1 6 8 1 7 8 1 8 2 Output setup group 3 Communication setup group 4...

Page 15: ...to compensate voltage for the terminal temperature Otherwise it will show declination as much as the terminal temperature surrounding temperature 6 Selection of Process Value Filter When instability o...

Page 16: ...the control output 5 Preset Output Volume This is useful when preheating condition must be maintained through continuous output volume previously set up by disconnecting the output from the PID calcu...

Page 17: ...PCL 1 PC LINK SUM Option PCL 0 Communication rate BAUD RATE 600 1200 2400 4800 9600 bps 9600 PARITY NONE EVEN ODD NONE STOP BIT 1 or 2 bit 1 DATA LENGTH 7 or 8 except PC Link 8 8 ADDRESS 1 99 max 31...

Page 18: ...utput When using the retransmission output it is impossible to use the SPS function for sensor SPS Output Wiring for Sensor Must disconnect the controller and external power source when setting up rem...

Page 19: ...Alarm 2 set value 0 0 Patter 1 End OFF PUL CONT code 21 selection OFF Patter 2 End OFF PUL CONT OFF 1 Alarm Select 1 or 2 Types Select code number of the Alarm type from the Alarm Type and Code list...

Page 20: ...ion of time unit 3 Setup of Wait Zone Process value must agree in accord to the process of programmed set value in program temperature controller but unpredicted events occur Here if the temperature v...

Page 21: ...the PID group in agreement with the selected number from the auto tuning selection in the auto tuning setup group is applied to each pattern segment of 4 types due to the selection of pattern segment...

Page 22: ...the 10 of the set value The symbol for the auto tuning setup group is only indicated in operative period The auto tuning output is not indicated if ON OFF has been already selected 1 Selection of Aut...

Page 23: ...ss for 2 5 seconds Engineering group Program groupt Repeat time setup 1 Pattern has been assigned See page 24 of 0 segment parameter of program setup Set up segment number 1 See 1 segment parameter Se...

Page 24: ...p items Repeat frequency setup 0 limitless frequency 1 99 Always 1 Setup group for program repeat frequency is indicated if the system is operated as follow when power is ON Power ON 2 5 sec 1 Set up...

Page 25: ...ime signal 1 ON time OFF 00 00 99 59 Segment 0 OFF Setup of n pattern time signal 1 OFF time OFF 00 00 99 59 ON time OFF time Segment 0 OFF Setup of n pattern time signal 2 ON time OFF 00 00 99 59 Seg...

Page 26: ...pattern 6 Setup of n pattern time signal 1 OFF time It turns OFF after the set time of time signal 1 of already selected pattern 7 Program Completion Mode When pattern 1 is selected as mode upon the c...

Page 27: ...nge Input resistance Thermocouple mV input 1 M min V DC input Approx 1 M Allowable signal source resistance Thermocouple max 250 mV V DC input max 2 K Allowable wiring resistance RTD input max 10 1 wi...

Page 28: ...solution 0 1 or 10 ms Current output SCR output 4 20 A DC Current output range 4 20 mA DC Resistive load 600 max Accuracy 0 3 of full scale 4 20 mA range Resolution Approx 3 000 Output ripple 0 1 P P...

Page 29: ...ontinuous vibration 5 14 Hz Forward width 1 2 mm max 4 150 Hz 4 9 0 5 G max Vibration 14 7 1 5 G 15 sec max each 3 direction Shock 147 15 G 11msec max 6 direction each 3 times Normal operation conditi...

Page 30: ...on Resistance Primary terminal Secondary terminal MIN 500 V DC 20 M Primary terminal Ground MIN 500 V DC 20 M Ground Secondary terminal MIN 500 V DC 20 M 9 11 Dielectric strength Primary terminal Seco...

Page 31: ...action Select Direct or Reverse action in output group Emergency Preset 0 5 105 0 of output value ON OFF Hysteresis 0 0 100 0 of range When selecting ON OFF control follow the HYS set up of output gro...

Page 32: ...d alarm 8 18 DEV ALM DEV ALM DEV ALM HYS DEV ALM HYS High absolute alarm inverted 9 19 PV ALM PV ALM HYS Low absolute alarm inverted 10 20 PV ALM PV ALM HYS Pattern ending signal 21 Pattern ending sig...

Page 33: ...rm 8 High Low band 9 High absolute inverted 10 Low absolute inverted 11 High absolute with hold function 12 Low absolute with hold function 13 High deviation with hold function 14 Low deviation with h...

Page 34: ...he introduction manual please refer to a sign which is displayed as FND is marked as following English characters for some reason Alphabet FND Alphabet FND Alphabet FND A N 1 B O 2 C P 3 D Q 4 E R 5 F...

Page 35: ...ime 8 1 8 Auto tuning AT type AT operation 8 2 1 Program repeat frequency Frequency 8 1 7 PID setup group ARW P I D Manual reset Group 1 Group 2 Group 3 Group 4 Segment Mode 1 2 3 4 5 6 7 8 9 10 Patte...

Page 36: ...HANYOUNG NUX CO LTD 28 Gilpa ro 71 beon gil Nam gu Incheon Korea TEL 82 32 876 4697 FAX 82 32 876 4696 http www hynux com E mail overseas hynux com MA0102E140110...

Reviews: