background image

3

Parameter

Operation description

 ● POWER ON DELAY
 ● uses 1 set time (set time displayed on SV display)
 ● when power is applied, output turns OFF, timing starts
 ● when displayed time reaches set time, output turns ON, 
     displayed time is held (ONE-SHOT output selectable)

POND

● POWER ON FLICKER - OFF START
● uses 2 set times, Ton and Toff (Toff set time displayed on PV 
   display, Ton set time displayed on SV display)
● when power is applied, OFF timing starts
● when displayed time reaches Toff set time, output turns ON, 
    after displayed time initialization ON timing starts
● when displayed time reaches Ton set time, output turns OFF, 
    after displayed time initialization OFF timing starts
● output repeats ON/OFF operations according to Ton and Toff 
    set times

PFKF

● POWER ON FLICKER - ON START
● uses 2 set times, Ton and Toff (Ton set time displayed on PV 
    display, Toff set time displayed on SV display)
● when power is applied, output turns ON, ON timing starts
● when displayed time reaches Ton set time output turns OFF, 
    after displayed time initialization OFF timing starts
● when displayed time reaches Toff set time, output turns ON, 
    after displayed time initialization ON timing starts
● output repeats ON/OFF operations according to Ton and Toff 
    set times

PFKN

● POWER ON INTERVAL
● uses 1 set time (set time displayed on SV display)
● when power is applied, output turns ON, timing starts
● when displayed time reaches set time, output turns OFF, 
    displayed time is held

PINT

● TWIN - ON START
● uses 2 set times, Ton and Toff (Ton set time displayed on PV 
    display, Toff set time displayed on SV display)
● when power is applied, OUT1 output turns OFF, OUT2 output 
    turns ON, ON timing starts
● when displayed time reaches Ton set time OUT1 output turns 
    ON, OUT2 output turns OFF, after displayed time initialization 
    OFF timing starts
● when displayed time reaches Toff set time, OUT1 output turns
    OFF, holds output and displayed time

TWON

● TWIN - OFF START
● uses 2 set times, Ton and Toff (Toff set time displayed on PV 
    display, Ton set time displayed on SV display)
● when power is applied, OUT1 and OUT2 outputs turn OFF, OFF
    timing starts
● when displayed time reaches Toff set time, OUT2 output turns
    ON, after displayed time initialization ON timing starts
● when displayed time reaches Ton set time, OUT1 output turns 
    ON, holds output and displayed time

TWOF

● STAR – DELTA
● uses 2 set times, Ton and Toff (Ton set time displayed on PV 
    display, Toff set time displayed on SV display)
● when power is applied, OUT1 output turns OFF, OUT2 output
    turns ON, ON timing starts
● when displayed time reaches Ton set time, OUT2 output turns
    OFF, after displayed time initialization OFF timing starts
● when displayed time reaches Toff set time, OUT1 output turns
    ON, holds output and displayed time
● OUT1 operates as 'Δ' output, OUT2 operates as ' ' output.
● Toff set time is  'Δ -  ' operation switching time

S - D

Parameter

Operation description

● SIGNAL ON DELAY
● uses 1 set time (set time displayed on SV display)
● when START signal is applied, timing starts (START signal holds ON status )
● when displayed time reaches set time output turns ON, holds output and
    displayed time (ONE-SHOT output selectable)
● When START signal is cancelled, initializes output and displayed time

SOND

● SIGNAL ON FLICKER - OFF START
● uses 2 set times, Ton and Toff (Toff set time displayed on PV display, Ton
    set time displayed on SV display)
● when START signal is applied,OFF timing starts (START signal holds ON status)
● when displayed time reaches Toff set time, output turns ON, after displayed
    time initialization ON timing starts
● when displayed time reaches Ton set time output turns OFF, after displayed
    time initialization OFF timing starts
● output repeats ON/OFF operations according to Ton and Toff set times
● when START signal is cancelled, initializes output and displayed time

SFKF

● SIGNAL ON INTERVAL
● uses 1 set time (set time displayed on SV display)
● When START signal is applied, output turns ON, timing starts (START signal
     holds ON status )
● when displayed time reaches set time output turns OFF,displayed time is held
● When START signal is cancelled, initializes output and displayed time 

SINT

● SIGNAL ON INTERVAL
● uses 1 set time (set time displayed on SV display)
● When START signal is applied, output turns ON, timing starts (START signal
     holds ON status )
● when displayed time reaches set time, output turns OFF, displayed time is held
● when START signal is cancelled, initializes output and displayed time 

SNFN

● SIGNAL ON/OFF DELAY - OFF START
● uses 2 set times, Ton and Toff (Ton set time displayed on PV display, Toff
    set time displayed on SV display)
● when START signal is applied, ON timing starts
● when displayed time reaches Ton set time output turns ON,displayed time is held
● When START signal is cancelled, output holds ON output status,OFF timing starts
● when displayed time reaches Toff set time  output turns OFF, displayed
    time is held

SNFF

● SIGNAL OFF DELAY
● uses 1 set time (set time displayed on SV display)
● when START signal is applied, output turns ON (START signal holds ON 
   status )
● when START signal is cancelled, holds output and timing starts
● when displayed time reaches set time output turns OFF, displayed time is held
● when START signal is cancelled, initializes output and displayed time 

SOFD

● SIGNAL TRIGGER ON DELAY
● uses 1 set time (set time displayed on SV display)
● when START signal is applied, timing starts
● when displayed time reaches set time output turns ON, holds output and
    displayed time (ONE-SHOT output selectable)
● when START signal is repeatedly applied, only uses the first START signal

S.OND

● SIGNAL TRIGGER ON FLICKER - ON START
● uses 2 set times, Ton and Toff (Toff set time displayed on PV display, Ton
    set time displayed on SV display)
● when START signal is applied, output turns ON, ON timing starts
● when displayed time reaches Ton set time output turns OFF, after displayed
    time initialization OFF timing starts
● when displayed time reaches Toff set time, output turns ON, after displayed
    time initialization ON timing starts
● output repeats ON/OFF operations according to Ton and Toff set times
● When START signal is repeatedly applied, only uses the first START signal

S.FKN

● SIGNAL TRIGGER ON INTERVAL
● uses 1 set time (set time displayed on SV display)
● when START signal is applied, output turns ON, timing starts
● when displayed time reaches set time output turns OFF, displayed time is held
● When START signal is repeatedly applied, only uses the first START signal
● after reaching set time, when START signal is applied, 
    output turns ON, and after time value initialization timing starts 

S.INT

● SIGNAL TRIGGER ON DELAY – RESET
● when START signal is applied, timing starts
● when displayed time reaches set time, output turns ON, holds output and
    displayed time (ONE-SHOT output selectable)
● when START signal is re-applied during timing, timing starts after displayed
    time initialization 

S.ODR

Operation overview

 LT4

 LT4S

Summary of Contents for LT4 Series

Page 1: ...ontact with your body or conductive substances DANGER The contents of this manual may be changed without prior notification Please make sure that the product specifications are the same as you ordered...

Page 2: ...N TWON TWOF S D SFKF SNFN SNFF S FKN operation modes MODE KEY enters and quits function setting mode automaticaly saves function set value during termination SHIFT KEY enters set value change mode and...

Page 3: ...play when START signal is applied OFF timing starts START signal holds ON status when displayed time reaches Toff set time output turns ON after displayed time initialization ON timing starts when dis...

Page 4: ...changing the set value of SV display press to save the changed set value and return to operation mode If ON time set value and OFF time set value are 0 even if you press it does not return to operati...

Page 5: ...s configured as time limit 2c in operation mode TWON TWOF S D it is automatically fixed to time limit 2c Minimum input time selection displayed only on LT4S models selects START INHIBIT RESET minimum...

Page 6: ...e POWER RESET OUT1 OUT2 1 When power is applied OUT1 and OUT2 turn ON and timing starts When CONT is set as 1C 1C in function setting mode OUT1 turns ON when power is applied instantaneous output When...

Page 7: ...elled during ON time timing OUT turns ON time value is initialized Toff time is displayed 6 If START signal is applied suring OFF time timing OUT turns OFF time value is initialized Ton time is displa...

Reviews: