Operation mode

 LT4 Operation mode

 LT4S Operation mode

         

(SIGNAL ON DELAY mode)

POWER

②-⑦

START

③-②

RESET

④-②

OUT

⑧-⑥

1. When START signal is applied, timing starts. 
   (START signal holds ON status)
2. When the time value reaches the set value OUT turns ON, 
    output and time value are held.
3. When START signal is cancelled, OUT output, time value are initialized.
4. When RESET signal is applied, OUT output, time value are initialized.
5. When RESET signal is cancelled, timing restarts if the START signal 
    is applied.
* In function setting mode, when output time ‘OUTT’  is set as  ‘HOLD’, 
  OUT output holds output status, when output time ‘OUTT’  is set as  ‘00.01~99.99’ sec, OUT turns ON
  during set time (ONE-SHOT output).

Tout

Tout

Tout

Tout

self-hold output

ONE-SHOT output  

set value

set value

default operation

power

         

(TWIN – ON START mode)

POWER

②-⑦

RESET

OUT1

①-③

OUT2

⑧-⑥

1. When power is applied  OUT1 turns OFF, 
   OUT2 turns ON, Ton time timing starts.
2. When the time value reaches the ON set value OUT1 turns ON, 
   OUT2 turns OFF, and Toff time timing starts
   after time value initialization.
 3.When the time value reaches the OFF set value OUT1 turns
    OFF, output and time value are held.
4. When RESET-KEY is applied, output, time value are initialized.
    When RESET is unlocked, it is displayed from Ton time.  
   * Ton time and Toff time can be set individually.
   * In operation mode, Ton time is displayed on PV display,Toff time is displayed on SV display.
   * In operation modes TWON, TWOF, S-D, the contact configuration CONT is fixed as ‘time limit 2c’ 

Ton

Toff

Ton

Toff

Ton

Toff

ON set value

ON set value

OFF set value

OFF set value

         

 (TWIN – OFF START mode)

POWER

②-⑦

RESET

OUT1

①-③

OUT2

⑧-⑥

1. When power is applied  OUT1 and OUT2 turn OFF , 
    Toff time timing starts.
2. When the time value reaches the OFF set value OUT2 turns ON,
   and after time value initialization, Ton time timing starts.
3. When the time value reaches the ON set value OUT1 turns ON, 
   output and time value are held.
4. When RESET-KEY is applied,output, time value are initialized. 
    When RESET is unlocked, it is displayed from Toff time.  
* Ton time and Toff time can be set individually.
* In operation mode, the Toff time is displayed on the PV display, and the Ton time is displayed on the 
   SV display.
* In operation modes TWON, TWOF, S-D, the contact configuration CONT is fixed as ‘time limit 2c’.

Toff

Ton

Toff

Ton

Toff

Ton

Toff: OFF set time  Ton: ON set time

ON set value

ON set value

OFF set value

OFF set value

         

(STAR-DELTA mode)

POWER

②-⑦

RESET

OUT1 (

Δ)

①-③

OUT2( )

⑧-⑥

1. When power is applied  OUT1 turns OFF, OUT2 turns ON, 
   Ton time timing starts.
2. When the time value reaches the ON set value 
    OUT2  turns OFF, and Toff time timing starts
    after time value initialization.
 3.When the time value reaches the OFF set value OUT1 
    turns ON , output and time value are held.
4. When RESET-KEY is applied, output and time value are 
    initialized. When RESET is unlocked, it is displayed from Ton time.  
   * Ton time and Toff time can be set individually.
   * In operation mode, the Ton time is displayed on the PV display, and the Toff time is 
     displayed in the SV display.
   * In operation modes TWON, TWOF, S-D , the contact configuration CONT is fixed as
      ‘time limit 2c’.
   * OUT1 operates as a 'Δ' output, OUT2 operates as a '   'output.
   * Toff set time is the 'Δ

 

-  ' operation switching time.  

Ton

Toff

Ton

Toff

Ton

Toff: OFF set time   Ton: ON set time

ON set value

ON set value

OFF set value

OFF set value

Toff

Ton

default operation

power

Toff

Ton

default operation

power

Ton

Toff

default operation

power

         

(POWER ON INTERVAL mode)

POWER

②-⑦

RESET

OUT1

①-③

OUT2

⑧-⑥

1. When power is applied, OUT1 and OUT2 turn ON, and timing starts.
    * When 'CONT' is set as 1C.1C in function setting mode, OUT1
       turns ON, when power is applied (instantaneous output)
    * When 'CONT' is set as 2C in function setting mode, 
       OUT1 operates in synchronization with OUT2.
2. When time value reaches set value, OUT2 turns OFF, time value is held.
3. When RESET-KEY is applied, OUT2 output and time value are initialized.

t : set time

set value

set value

default operation

power

         

(POWER ON FLICKER – ON START mode)

POWER

②-⑦

RESET

OUT1

①-③

OUT2

⑧-⑥

1. When power is applied, OUT1 and OUT2 turn ON, and Ton time
    timing starts.
    * When 'CONT' is set as 1C.1C in function setting mode, 
      OUT1 turns ON when power is applied (instantaneous output)
    * When 'CONT' is set as 2C in function setting mode, OUT1 
      operates in synchronization with OUT2.
2. When the time value reaches the ON set value, OUT2 turns OFF 
    and  Toff time timing starts after time value initialization,
3. OUT2 turns ON when time value reaches OFF set value.
4. Depending on the Ton set time and Toff set time, the output repeats the above ON and OFF 
    operations.
5. When RESET-KEY is applied, OUT2 output and time value are initialized. When RESET is unlocked, it
    is displayed from Ton time.
* Ton time and Toff time can be set individually.
* In operation mode, the Ton time is displayed on the PV display, and the Toff time is displayed on the 
   SV display.

Ton

Toff

Ton

Toff

Ton

Toff

Ton

Toff

Ton

Toff

Toff : OFF set time  Ton : ON set time

OFF set value

OFF set value

ON set value

ON set value

Ton

Toff

Ton

Toff

default operation

power

* when CONT : 1C.1C

         

(POWER ON FLICKER - OFF START mode)

POWER

②-⑦

RESET

OUT1

①-③

OUT2

⑧-⑥

1. When power is applied  OUT1 turns ON, OUT2  turns OFF, 
   Toff time timing starts.
    *When 'CONT' is set as 1C.1C in function setting mode, 
      OUT1 turns ON when power is applied (instantaneous output)
    *When 'CONT' is set as 2C in function setting mode, 
      OUT1 operates in synchronization with OUT2.
2. When the time value reaches the OFF set value OUT2 turns ON, 
    and after time value initialization, Ton time timing starts.
3. OUT2 turns OFF when time value reaches ON set value.
4. Depending on the Ton set time and Toff set time, the output repeats the above ON and OFF  
    operations.
5. When RESET-KEY is applied, OUT2 output and time value are initialized. When RESET is unlocked, It is 
displayed from Toff time. 
* Ton time and Toff time can be set individually.
* In operation mode, Toff time is displayed on the PV display, and Ton time is displayed on SV display.

Toff

Ton

Toff

Ton

Toff

Ton

Toff

Ton

Toff

Ton

Toff: OFF set time  Ton: ON set time

ON set value

ON set value

OFF set value

OFF set 

Toff

Ton

Toff

Ton

default operation

power

*When CONT : 1C.1C

         

(POWER ON DELAY mode)

POWER

②-⑦

RESET

OUT1

①-③

OUT2

⑧-⑥

1. When power is applied  OUT1 turns ON, and timing starts.
    * When 'CONT' is set as 1C.1C in function setting mode, OUT1
       turns ON when power is applied (instantaneous output)
    * When 'CONT' is set as 2C in function setting mode, 
       OUT1 operates in synchronization with OUT2.
2. When the time value reaches the set value OUT2 turns ON, 
    output and time value are held.
3. When RESET-KEY is applied, OUT2 output and time value 
    are initialized.
   * In function mode, when output time ‘OUTT’  is set as  ‘HOLD’, OUT2 output holds the output status,
     when output time  ‘OUTT’ is set as  ‘00.01~99.99’ sec , OUT2 output is ON only during set time.
     (ONE-SHOT output)

Tout : output operating time  

 t : set time 

self-hold  output

ONE-SHOT output  

set value

set value

default operation

power

UP

DOWN

UP

DOWN

UP

DOWN

UP

DOWN

UP

DOWN

UP

DOWN

UP

DOWN

UP

DOWN

* When CONT : 1C.1C

* When CONT : 1C.1C

t : set time

Toff: OFF set time  Ton: ON set time

Tout : output operating time  

 t : set time 

Summary of Contents for LT4 Series

Page 1: ...ontact with your body or conductive substances DANGER The contents of this manual may be changed without prior notification Please make sure that the product specifications are the same as you ordered...

Page 2: ...N TWON TWOF S D SFKF SNFN SNFF S FKN operation modes MODE KEY enters and quits function setting mode automaticaly saves function set value during termination SHIFT KEY enters set value change mode and...

Page 3: ...play when START signal is applied OFF timing starts START signal holds ON status when displayed time reaches Toff set time output turns ON after displayed time initialization ON timing starts when dis...

Page 4: ...changing the set value of SV display press to save the changed set value and return to operation mode If ON time set value and OFF time set value are 0 even if you press it does not return to operati...

Page 5: ...s configured as time limit 2c in operation mode TWON TWOF S D it is automatically fixed to time limit 2c Minimum input time selection displayed only on LT4S models selects START INHIBIT RESET minimum...

Page 6: ...e POWER RESET OUT1 OUT2 1 When power is applied OUT1 and OUT2 turn ON and timing starts When CONT is set as 1C 1C in function setting mode OUT1 turns ON when power is applied instantaneous output When...

Page 7: ...elled during ON time timing OUT turns ON time value is initialized Toff time is displayed 6 If START signal is applied suring OFF time timing OUT turns OFF time value is initialized Ton time is displa...

Reviews: